1.5. Maintenance, service and faults 

 

The UPS system operates with hazardous voltages. Repairs may be carried out only 
by qualified maintenance personnel.   

 

Caution - risk of electric shock. Even after the unit is disconnected from the mains 
(building wiring outlet), components inside the UPS system are still connected to the 
battery and electrically live and dangerous.   

 

Before carrying out any kind of service and/or maintenance, disconnect the batteries 
and verify that no current is present and no hazardous voltage exists in the terminals 
of high capability capacitor such as BUS-capacitors.   

 

Only persons are adequately familiar with batteries and with the required 
precautionary measures may replace batteries and supervise operations. 
Unauthorized persons must be kept well away from the batteries.   

 

Caution - risk of electric shock. The battery circuit is not isolated from the input 
voltage. Hazardous voltages may occur between the battery terminals and the 
ground. Before touching, please verify that no voltage is present!   

 

Batteries may cause electric shock and have a high short-circuit current. Please take 
the precautionary measures specified below and any other measures necessary 
when working with batteries:   

  remove wristwatches, rings and other metal objects   
  use only tools with insulated grips and handles.   

 

When changing batteries, install the same number and same type of batteries.   

 

Do not attempt to dispose of batteries by burning them. This could cause battery 
explosion.   

 

Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin 
and eyes. It may be toxic.   

 

Please replace the fuse only with the same type and amperage in order to avoid fire 
hazards.   

 

Do not dismantle the UPS system. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание UPS 1K

Страница 1: ...Online UPS 1K 2K 3K Uninterruptible Power Supply System USER MANUAL EN ...

Страница 2: ...s 2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 4 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 10 3 6 Operating Mode Description 13 3 7 Faults Reference Code 14 3 8 Warning indicator 14 4 Troubleshooting 15 5 Storage and Maintenance 16 6 Specifications 17 ...

Страница 3: ...r trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to ...

Страница 4: ...d persons must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below...

Страница 5: ...le Model Type Model Type 1K Standard 1K L Long run 2K 2K L 3K 3K L 2 1 Rear panel view 1K L TOWER 2K L TOWER 3K L TOWER 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication port 9 ...

Страница 6: ...aintain maximum altitude of 1000m to keep UPS normal operation at full load UPS If it s used in high altitude area please reduce connected load Altitude derating power with connected loads for UPS normal operation is listed as below 4 Place UPS It s equipped with fan for cooling Therefore place the UPS in a well ventilated area It s required to maintain minimum clearance of 100mm in the front of t...

Страница 7: ... power cord is attached to the UPS The input plug is a NEMA 5 15P for 1K and 1K L models NEMA 5 20P for 2K and 2K L models Note For Low voltage models Check if the site wiring fault indicator lights up in LCD panel It will be illuminated when the UPS is plugged into an improperly wired utility power outlet Refer to Troubleshooting section Step 3 UPS output connection For socket type outputs there ...

Страница 8: ... pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 7 Turn on the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Install software For opt...

Страница 9: ...tton Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 3 seconds to enter UPS setting mode when...

Страница 10: ...ad level by 0 24 25 49 50 74 and 75 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverte...

Страница 11: ...nding every 10 seconds 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery BAH Battery AH CHA Charger current CBV Charger boost voltage CFV Charger float voltage CF Converter ON ON EP EPO TP Temperature CH Charger FU Bypass frequency unstable EE EEPROM error FA Fan failure BR Battery Replacement ...

Страница 12: ...ing output voltage 100 present output voltage is 100Vac 110 present output voltage is 110Vac 115 present output voltage is 115Vac 120 present output voltage is 120Vac Default 127 present output voltage is 127Vac 02 Frequency Converter enable disable Interface Setting Parameter 2 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converte...

Страница 13: ...127 VAC models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable disable when UPS is off Interface Setting Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass voltage range setting Interface Setting Parameter 2 3 Set the acceptable high voltage point and a...

Страница 14: ...eter 3 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 10 Programmable outlets setting Interface Setting Parameter 3 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode Default 999 11 Autonomy limita...

Страница 15: ...m 2 20 V cell to 2 33V cell Default 2 28V cell 00 Exit setting 3 6 Operating Mode Description Operating mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass...

Страница 16: ...Over load 43 Inverter voltage Low 13 x Charger failure 45 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every 2 seconds Overload Sounding every 2 seconds Battery is not connected Sounding every 2 seconds Over Charge Sounding every 2 seconds Site wiring fault Sounding every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger fai...

Страница 17: ... incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact yo...

Страница 18: ...o replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every 2 seconds Fan is locked or not working Check fans and notify dealer Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output and battery voltage is less than 10V PC Contact your dealer 5 Storage and Maintenance Operation The UPS sy...

Страница 19: ... Battery Type 12V 7AH 12V 7AH 12V 9AH Numbers 3 6 6 Typical Recharge Time 4 hours recover to 90 capacity Charging Current máx 1 5 A max Charging Voltage 41 0 VDC 1 82 1 VDC 1 Long run Model Battery Type Depending on the capacity of external batteries Charging Current máx 1 2 4 6 8 A Selectable via LCD setting Charging Voltage 41 0 VDC 1 82 1 VDC 1 CONNECTORS Current outputs 4xIEC 8xIEC 6xIEC Termi...