Configuring the UDS Using Telnet or the Serial Port
UDS200 User Guide
22
Using the Serial Port
For local configuration, you can connect a terminal or a PC running a terminal
emulation program to the unit’s serial port (channel 1). Configure the terminal (or
emulation) for 9600 baud, 8-bit, no parity, 1 stop bit, and no flow control.
1. Cycle the unit’s power (power off and back on). After power-up, the self-test
begins and the diagnostic and status LEDs start blinking.
2. Type three lowercase
x
characters (
xxx
)
within one second
after powering up
in order to start the configuration mode. The Setup Mode window displays. (See
the example in
Using a Telnet Connection
.)
Note:
The easiest way to enter Setup Mode is to hold down the
x
key on
your keyboard while powering up the unit.
3. Select an option on the menu by entering the number of the option at the
Your
choice ?
prompt and pressing
Enter.
4. To enter a value for a parameter, type the value and press
Enter,
or
to confirm a
default value, just press
Enter
.
5. When you are finished, save the new configuration (option
9
). The unit reboots.
Server Configuration (Network Configuration)
Type
0
at the
Your choice ?
prompt and press
Enter
. Current values display in
parentheses. The rest of this section describes the configurable settings within the
Server configuration menu.
Figure 5-3. Network Configuration
IP Address
The IP address must be set to a unique value in your network. If the IP address has
not been assigned by DHCP, enter it manually. Enter each octet, pressing
Enter
after
each.