Lantronix
EDCA-DIO-01 Install Guide
33790 Rev. C
8
EDCA-DIO-01Install Procedure
1. Mount a mechanical door closure contact switch near the enclosure door so that the opening and closing of the
door will trigger the switch.
2. Connect the
12VDC Relay
port to the sensor or door contact closure switch.
3. Connect the
ALARM
Out
port to the Digital input port on the Ethernet Switch.
4. Connect to
DC Input
power last.
5. Verify that the
PWR
LED is lit.
Switch Software Configuration
When the EDCA-DIO-01 is installed with a Lantronix managed hardened Ethernet PoE switch, you can set up alarm
notifications and clear the logged alarm from either the switch Web UI or the CLI. See the related manual for your
particular switch model.
Related Manuals
•
EDCA-DIO-01 Quick Start Guide, 33796
•
SISPM1040-582-LRT Install Guide, 33755
•
SISPM1040-582-LRT Web User Guide, 33756
•
Install Guide, SISPM1040-362-LRT and SISPM1040-384-LRT-C, 33727
•
Web User Guide, SISPM1040-362-LRT and SISPM1040-384-LRT-C, 33728
Troubleshooting
Follow the steps below to resolve problems.
1. Check the PWR LED.
2. Verify proper EDCA-DIO-01 installation; see
the EDCA-DIO-01Install Procedure above.
3. Verify the Installation steps above.
4. Verify connected sensor or alarm and connections.
5. Verify connection with the Lantronix Managed Hardened Ethernet PoE Switch.
6. Record device and site information; see
Recording Information
below.
7. Contact Lantronix Tech Support.