FOCUS kWh Solid-State Meter Technical Manual
Bulletin 160
Revision 2.1
Страница 1: ...FOCUS kWh Solid State Meter Technical Manual Bulletin 160 Revision 2 1 ...
Страница 2: ...n permission of Landis Gyr Inc 2003 Landis Gyr Inc All rights reserved For further information contact Landis Gyr Inc Meter Division 2800 Duncan Road Lafayette IN 47904 5012 USA Tel 765 742 1001 Document History Title FOCUS Solid State Meter Technical Manual Document Number Bulletin 160 Revision Date Description Level Issued Original 1 0 1 04 Initial Issue 2 0 10 19 04 Rev Cellnet FCC 2 1 11 8 04 ...
Страница 3: ...PECIFICATIONS VII FCC INFORMATION VII 1 INTRODUCTION TO THE FOCUS 1 BASEPLATE ASSEMBLY 2 ELECTRONIC HOUSING ASSEMBLY 3 2 THE FOCUS METER FAMILY 4 REGISTER TYPES 4 3 METER ASSEMBLY 5 REMOVAL OF THE ELECTRONICS HOUSING FROM THE BASEPLATE 5 INSTALLATION OF THE ELECTRONICS HOUSING ONTO THE BASEPLATE 5 SEALING THE METER 5 4 APPLICATION INFORMATION 8 AVAILABLE METER FORMS 8 4 1 1 S BASE 8 4 1 2 K BASE 8...
Страница 4: ... 1 7 ERROR CODE MAPPING ERROR BOOKMARK NOT DEFINED 5 1 8 ERROR DISPLAY POWER OUTAGE COUNTER AND USER ACCESS 15 6 CONFIGURING THE METER 16 6 1 CONFIGURATION PORT 16 INITIAL POWER UP AND OPERATION 16 6 1 2 BILLING DATA RESET PRESET 16 6 1 3 DISPLAY MULTIPLIER 16 7 METER CALIBRATION 17 CALIBRATION LED 17 7 1 1 FACTORY CALIBRATION 18 7 1 2 CUSTOMER CALIBRATION ADJUSTMENT 18 DATA RETENTION 18 8 PULSE O...
Страница 5: ...IPLIER 20 TABLE OF FIGURES FIGURE 1 BASIC OPERATION DIAGRAM 1 FIGURE 2 METER ASSEMBLY 1 FIGURE 3 METER ASSEMBLY EXPLODED VIEW 2 FIGURE 4 BASEPLATE ASSEMBLY EXPLODED VIEW 2 FIGURE 5 ELECTRONICS HOUSING ASSEMBLY EXPLODED VIEW 3 FIGURE 6 KWH FOCUS 4 FIGURE 7 REMOVAL OF ELECTRONICS HOUSING 5 FIGURE 8 UNUSED T SEALS FIGURE 9 FORMED T SEAL AFTER INSTALLATION 7 FIGURE 10 T SEAL INSTALLED 7 FIGURE 11 FORM...
Страница 6: ...BLE 5 FORM 3S SPECIFICATIONS 10 TABLE 6 FORM 4S SPECIFICATIONS 11 TABLE 7 METER ERRORS 15 Purpose This technical manual contains the following information Installation instructions construction characteristics and maintenance information Performance and technical data Target Group The contents of this technical manual are intended for technically qualified personnel of energy supply companies resp...
Страница 7: ...metering equipment can present a danger of electrical shock All work on this product should be performed only by qualified electricians and metering specialists in accordance with local utility safety practices utility requirements and procedures outlined in Chapter 14 of The Handbook for Electricity Metering 9th Edition The information contained within this manual is intended to be an aid to qual...
Страница 8: ...ions December 27 1995 Canadian Specifications National Standard of Canada Specifications for Approval of Type of Electricity Meters Instrument Transformers and Auxiliary Devices CAN3C17M84 Ontario Hydro Oscillatory Transient Interference Immunity Test A 28M 82 Canadian Standard for Terminal Equipment Terminal Systems Network Protection Devices Connection Arrangements and Hearing Aids Compatibility...
Страница 9: ...ion This equipment uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the eq...
Страница 10: ... induction meter The meter is based on reliable field proven digital multiplication measurement technique The meter platform will measure energy accurately over varying environmental conditions It is designed to be stable over its long expected life A diagram of basic operation is noted below Figure 1 Basic Operation Diagram Figure 2 Meter Assembly 1 ...
Страница 11: ...g assembly snaps onto the baseplate and creates a weatherproof seal when the cover is installed The cover includes an emboss to align an optical probe for register configuration purposes Baseplate Assembly Figure 4 Baseplate Assembly Exploded View The baseplate module is constructed of highly durable thermoplastics Inside the baseplate are the current transformer and current carrying parts 2 2 ...
Страница 12: ...and any optional electronics assemblies such as option boards or communication devices It also contains the liquid crystal display LCD on which meter readings and other pertinent data can be displayed The Electronics Housing assembly snaps onto the baseplate and can be removed and reinstalled many times without damage to the meter 3 3 ...
Страница 13: ...cus kWh is an active energy kWh only meter It is capable of measuring and displaying kilowatt hours delivered to and received from a load The energy accumulation register has capacity to display 999999 kWh for all meter forms without overflowing The meter supports four energy metric displays kWh energy delivered to the load kWh energy received from the load NET kWh the net energy consumed by the l...
Страница 14: ...ging the spring contacts located on the base assembly Installation of the Electronics Housing onto the Baseplate Before installing the Electronics Module onto the Baseplate make sure that the Electronics Module and Baseplate are free of foreign debris and that any cables are properly routed to prevent interference with the meter s electrical connectors Attach current input lead connector onto mati...
Страница 15: ...6 6 can be installed through the FOCUS cover and baseplate assembly ...
Страница 16: ...T seal is installed by fully inserting it through the cover and through the baseplate assembly Bend the T seal tab to prevent extraction Next bend the T seal over so that it resides within the baseplate assembly pocket Finally bend the top of the T seal over so that it is flush against the cover 7 7 ...
Страница 17: ...ed Class 10 20 3S 4S Self contained class 100 1S Self contained class 200 2S 12S and 25S Network Self contained class 320 2SE 4 1 2 K Base Self contained class 480 2K Meter Form Schematic Diagrams Self contained meter forms Figure 11 Form 1S Table 1 Form 1S Specification Form Class Test Amps Volts Wire Kh 1S 100 15 120 2 1 8 8 8 ...
Страница 18: ... 2S 2SE Table 2 Form 2S 2SE Specifications Form Class Test Amps Volts Wire Kh 2S 200 30 240 3 7 2 2S 200 50 240 3 7 2 2SE 320 50 240 3 12 2SE 320 30 240 3 12 Figure 13 Form 12S Network Figure 14 Form 25S Network 9 9 ...
Страница 19: ...e 15 Form 2K Table 4 Form 2K Specifications Form Class Test Amps Volts Wire Kh 2K 480 30 240 3 14 4 2K 480 50 240 3 14 4 Transformer Rated Meter Forms Figure 16 Form 3S Table 5 Form 3S Specifications Form Class Test Amps Volts Wire Kh 3S 10 2 5 120 2 3 3S 20 2 5 120 2 3 3S 10 2 5 240 2 6 3S 20 2 5 240 2 6 10 10 Figure 17 Form 4S ...
Страница 20: ...ged 2 Make sure that the meter type form and class match the installation 3 Install meter in the appropriate socket Warning All applicable electrical codes and standards must be followed Any work performed around the meter including installation must be conducted by qualified metering personnel Failure to use proper safety practices could cause serious personal injury property damage and or death ...
Страница 21: ... the meter is wired properly 2 Install the meter on the studs in the K mounting device 3 Tighten down nuts securely to torque requirements listed inside the socket 4 Check to make sure that the LCD operates and sequences through the display items which were programmed into the meter ...
Страница 22: ...user with Focus Configuration Tool The scroll sequence can consist of up to 16 individual displays The display choices are kWh kWh NET kWh ADDED kWh Security Segment Check with Active DPI Line Voltage s Duplicate display choices are permitted as long as the total number of display choices in the scroll sequence does not exceed 16 The time of display can be programmed from 1 to 15 seconds in one se...
Страница 23: ...or codes or line voltage readings 5 1 4 Digital Power Indicator The Focus kWh has a digital power indicator similar to the Landis Gyr traditional caterpillar and consists of six segments The DPI moves from left to right at a rate proportional to energy delivered to the load and moves from right to left at a rate proportional to the energy received from the load The DPI makes one revolution for eac...
Страница 24: ...atile Memory Error EEPROM 1 010000 Measurement Error 1 100000 Table 7 Meter Errors All diagnostic errors are displayed at the end of the scroll sequence by means of a single six digit diagnostic status word The user has the ability to mask each individual error code from being displayed via the configuration tool 5 1 7 Power Outage Counter The user has the ability to read a power outage counter vi...
Страница 25: ...6 1 2 Billing Data Reset Preset The contents of the kWh and kWh accumulation registers are user programmable through an optical configuration port In its simplest form this feature allows the user to reset the contents of the kWh and kWh accumulation registers This feature also enables the user to clear any accumulated energy following meter verification testing The user also has the ability to en...
Страница 26: ...front of the meter cover The user can fix an LED pickup device to the front of the meter The calibration LED is enabled to produce stable pulses in no more than two seconds following meter power up The calibration LED produces pulses in response to energy whether it is delivered positive or received negative Registration verification testing requires no more than 30 seconds at full load The calibr...
Страница 27: ...ns of a calibration utility and the configuration port The factory FL series and individual element when applicable calibration value cannot be altered by user calibration adjustment Any individual element FL user calibration bias is stored in separate nonvolatile memory locations accessible through the configuration port The user calibration biases are scaled to represent percent registration bia...
Страница 28: ...ock position in the meter base The pulse initiator output responds in accordance with energy delivered to the load No pulses are emitted when energy is received from the load The pulse initiator option is user installable in a meter shop environment Communications Focus kWh provides two scalable TTL level pulse outputs for interfacing with pulse accumulating AMR modules Each output is user configu...
Страница 29: ...PI Burden Burden 1 8 Watts Starting Load Starting Load 50 mA or 12 Watts Forms Meter forms 1S 2S 2SE 2K 3S 4S 12S 25S Operating Temperature Operating Temperature 40º to 85ºC Accuracy Class Load Performance Accuracy Class 2 Display Options Energy Metrics kWh kWh Net kWh and added kWh Security Metric Display format 4 x 1 4 x 10 5 x 1 or 6 x 1 AMR Platform AMR platform Modular and Integrated Selectab...
Страница 30: ...21 21 Selectable meter multiplier up to 240 1200 5 CT Operating Voltage Range value ...