Operation
31/56
D000027979 en t – E350 Series 2, 3-Phase ZxF100Ax/Cx – User Manual
© Gyr
Always indicates the sum of the three phases:
+P
positive active energy direction (imported from power company)
-P
negative active energy direction (exported to power company)
+P
-P
positive active energy direction, but negative active energy
direction of individual phases (arrow -P flashes); only in three-
phase four-wire circuit (only with magnitude summation).
+P
-P
negative active energy direction, but positive active energy
direction of individual phases (arrow +P flashes); only in three-
phase four-wire circuit (only with magnitude summation)
Always indicates the sum of the three phases:
+Q
positive reactive energy direction
-Q
negative reactive energy direction
+Q
-Q
positive reactive energy direction, but negative reactive energy
direction of individual phases (arrow -Q flashes); only in three-
phase four-wire circuit (only with magnitude summation)
+Q
-Q
negative reactive energy direction, but positive reactive energy
direction of individual phases (arrow +Q flashes); only in three-
phase four-wire circuit (only with magnitude summation)
Indicates in which quadrant the present measurement is made:
+Q
+P
1
st
quadrant
-Q
-P
3
rd
quadrant
+Q
-P
2
nd
quadrant
+P
-Q
4
th
quadrant
The reactive no-load indication (a diamond) shows that the kvarh registers
have entered anti-creep mode. No energy is flowing through the meter (no
reactive energy direction indicator displayed).
The active no-load indication (a circle) shows that the kWh registers have
entered anti-creep mode. No energy is flowing through the meter (no active
energy direction indicator displayed).
Active energy
direction indication
Reactive energy
direction indication
Quadrant
Reactive no-load
indication
Active no-load
indication