Landis & Gyr Ultrasonic UH50 Скачать руководство пользователя страница 6

UH50 Ultrasound Heatmeter 

 

Configuration Instructions 

UH 106-101c 

Page 6 / 13 

Parameter setting for standard pulses 

Output mode 

Output value 

CE 

(count energy) 

Pulses for quantity of heat 

Chan.1 

C2 

(count tariff 2) 

Pulses for tariff register 2 

CV 

(count volume) 

Pulses for volume 

CT 

(count tariff 1) 

Pulses for tariff register 1 

Channel 2 

RI 

(ready indication) 

Pulses for the operating states 

"Ready / Fault" 

Parameter setting for “fast pulses” 

Channel 1 

Channel 2 

CV 

(count volume) 

CE 

(count energy) 

(no function) 

CV 

(count volume) 

CV 

(count volume)

 

(no function) 

CV 

(count volume) 

CE / CV *) 

(count energy / count volume) 

(no function) 

*) automatic output of the higher pulse rate

 

Labeling pulse 

module 

Type 

 

open collector  

Voltage 

maximal 30 V = 

Current 

maximal 30 mA  

Dielectric strength 

500 V

rms 

against ground 

Classification 

OB (per EN 1434-2) 

Voltage drop 

approx. 1.3 V at 20 mA 

Classification 

OC (per EN 1434-2) 

Voltage drop 

approx. 0.3 V at 0.1 mA 

Output connection 
(standard version): 

 

A special version of the pulse module is available 
with an Opto-MOS output. 
Advantages: low voltage drop and polarized 
(bipolar). 

Standard pulses 

 

Standard pulse significances 

kWh *)

MJ *)

10

15

25

40

2,5 3,5

60

Nom. flowrate in m³/h

10 MJ

0,6

1 kWh

10 kWh

1 m³

0,1 m³

100 MJ

1 MJ

*) depending on the unit for heat display

 
Pulses for quantity of heat, volume, tariff register 

Period duration 

> 200 ms 

Pulse duration  

100 ms conducting 

 

Pulses for operating states: 

“Ready” 

pulsed “conducting”, i.e. 

 

100 … 200 

µ

s pulse duration, 

 

500 ms period 

 

“Fault” constantly 

“non-conducting” 

 

Fast pulses 

 

Note: In battery operation, a D cell is required! 
For applications, such actuating controllers or as 
flowrate transmitters, higher pulse rates are 
required. The parameters required for this (pulse 
significance, pulse duration), can be configured with 
the PappaWin software.  
The maximum pulse frequency is 33 Hz. 
The following can be set: 

  Pulse type: “linear” or “scaled” pulses *)   

  Pulse output: energy or volume 

  Pulse duration, if only 1 pulse module is fitted: 

     from 2 ms to 100 ms in steps of 1 ms; 
Pulse duration, if 2 pulse modules are fitted: 
     von 5 ms to 100 ms in steps of 5 ms 

The pulses can be received and evaluated with a 
suitable device. The settings must be made in 
accordance with the information on the data sheet of 
the controller. 
*) Linear pulses are output proportionally to the 
measured value. In the case of scaled pulses, the 
number of pulses at the upper and lower end of the 
range can be defined. In this case, the pulse 
receiving device can detect, for example, a 
connection error. 

 

Linear pulses 

Scaled pulses (example)

CL module  

CL module

RTX+,

RTX- 

 

The CL module can be used to set up a point-to-
point link enabling the heat meter to be read 
remotely, for example, at the front door. 
Display in LCD 

CL

 (current loop) 

Standard 

per EN 1434-3 

Type 

passive current loop 

Baudrate 

2400 Baud, fest 

Isolation galvanic 

 

Polarity yes 
Voltage 

30 V maximal 

Current 

30 mA maximum 

Voltage drop 

< 2 V at 20 mA 

Literature TKB 

3415 

Содержание Ultrasonic UH50

Страница 1: ...temperature 20 to 60 C Max height 2000 m above MSL Ambient temperature 5 to 55 C Ambient humidity 93 rel Housing degree of prot IP 54 per EN 60529 Safety class Line 110 230 V AC II per EN 61558 Line 24 V ACDC III per EN 61558 Response threshold f T0 2 K Temperat difference T 3 K to 120 K Temperat meas range 2 180 C Sensors Type Pt500 or Pt100 per EN 60751 Temperature range 0 150 C 45 mm overall le...

Страница 2: ...r outlet sections are necessary However if the heat meter is installed in the shared return of two heating systems e g heating and hot water the mounting location must be a sufficient distance from the T element that forms the junction min 10 DN to allow the different water temperatures to mix well The sensor can be mounted in ball valves or in pockets The sensors must be inserted at least up to t...

Страница 3: ...d of the loop Accumulated quantity of heat with tariff status Tariff register 1 optional Accumulated volume Segment test Error message with error code number LCD button 1 is used to switch the display from the user loop to the selection of service loops LOOP 1 n Service loop selection Service loop 1 Service loop 2 LOOP n Service loop n LCD button 1 advances the display to the next loop After the l...

Страница 4: ...re difference flow temperature and return temperature with their date stamps on a yearly set day Monthly values The electronic unit stores the meter readings for quantity of heat volume the tariff register missing time and flowrate measuring time as well as the monthly maxima for flowrate power temperature difference flow temperature and return temperature with their date stamp for 18 months on th...

Страница 5: ... end ferrules 0 25 1 5 mm conductor sizes 26 14 AWG Multiple conductor connection 2 conductors of same cross section rigid or flexible 0 2 0 75 mm flexible with end ferrules without plastic sleeve 0 25 0 34 mm flexible with TWIN ferrules with plastic sleeve 0 5 0 75 mm Recommended screwdriver 0 6 x 3 5 mm Tightening torque 0 4 Nm Permissible combinations of modules Slot for module 2 is equipped wi...

Страница 6: ...conducting Pulses for operating states Ready pulsed conducting i e 100 200 µs pulse duration 500 ms period Fault constantly non conducting Fast pulses Note In battery operation a D cell is required For applications such actuating controllers or as flowrate transmitters higher pulse rates are required The parameters required for this pulse significance pulse duration can be configured with the Papp...

Страница 7: ...and maximum power measuring period with maxima for power flowrate and temperatures actual values for power flowrate and temperatures F0 pre warning setting and resetting a user lock setting the date and time and the primary and secondary address Special version with minimum update rate of 30 s can be supplied WZU MB 30 but it has a shorter battery life Data scope for fast readout Update after a mi...

Страница 8: ...l mode The data are packed and output in various telegram types Data content All telegrams are preceded by the time stamp date and time and the property number Telegram type Content Basic Cumulated values and error status Previous year Cumulated previous year s values and error status Previous month Cumulated previous month s values and error status Extended Current instantaneous values stored max...

Страница 9: ...ated or all tariffs can be deactivated Surcharge quantity tariff by means of return temperature tariff T12 The quantity of heat is summated depending on the return temperature in tariff registers 1 or 2 The summated quantity of heat is calculated from the difference of the return temperature from the defined return temperature threshold instead of from the temperature difference Above return thres...

Страница 10: ...thly set day parameterized 21 Master reset performed 22 All times deleted 23 Missing time deleted 24 Event occurs Maxima deleted Read out is performed via the optical interface with the PappaWin software Data logger optional The data logger permits the archiving of data that the user can select from a predefined set of values The data logger contains four archives whose 8 channels can be assigned ...

Страница 11: ... length 190mm nominal pressure PN16 connection G 1 B 23 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection flanged DN 20 24 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection G 1 B 25 Nominal flowrate 2 5 m h length 130mm nominal pressure PN16 connection G 1 B 36 Nominal flowrate 2 5 m h length 130mm nominal pressure PN25 connection G 1 B 37 Nominal flowrate...

Страница 12: ... mounted in the tube F Sensor Pt500 removable mounting in the tube as an option G Sensor Pt500 removable mounted in the tube within a pocket H Sensor Pt100 not removable not mounted in the tube N Sensor Pt100 not removable mounted in the tube P Sensor Pt100 not removable mounting in the tube as an option R Sensor Pt100 not removable mounted in the tube within a pocket S Hardware dependent features...

Страница 13: ...supply 24V AC DC with plug WZU ACDC24 00 Communication modules Code Analog module WZU AM CL Module WZU CL M bus module WZU MB M bus module with 30s minimum reading cycle WZU MB 30 M bus module with guaranteed data set WZU MB GR Pulse module WZU P2 Pulse module with OptoMOS WZU P2L Radio module WZU RM Radio module with external antenna WZU RM EXT Notes Regulations on the use of heat meters must be ...

Отзывы: