Note:

 Calculators up to 2.5 l/p can be parameterized to 

kWh. Calculators with 1 l/p can be parameterized to MJ. 

The pulse values are restricted by following connection condi-
tions: 

Pulse 

Max. power 

Max. flow 

[l/p] 

[MW] 

[m³/h] 

3.3 

24 

2.5 

3.3 

24 

10 

33 

240 

25 

33 

240 

100 

330 

2400 

250 

330 

2400 

1.000 

330 

2400 

2.500 

330 

2400 

The full range of functions of  LCD is described in detail in the 
“Operating Instructions” (enclosed). 

7. 

Error messages 

The calculator continuously runs a self-diagnosis and can thus 
recognise  and  display  various  installation  or  meter  error  mes-
sages. 

Error 
code 

Error 

Service guidelines 

DIFF   
nEG 

Negative temperature difference 

Check installation point of the 
temperature sensors; exchange 
if necessary 

if necessary in exchange with: 

F1 

Interruption in the hot side tempera-
ture sensor 

Check hot side temperature 
sensors; replace if necessary 

F2 

Interruption in the cold side tem-
perature sensor 

Check cold side temperature 
sensors; replace if necessary 

F3 

Electronics for temperature evalua-
tion defective 

Exchange the calculator 

F4 

Problem with the power supply; 
Battery flat; 

Check connection;  
Change battery 

F5 

Short-circuit hot side temperature 
sensor 

Check hot side temperature 
sensors; replace if necessary 

F6 

Short-circuit cold side temperature 
sensor 

Check cold side temperature 
sensors; replace if necessary 

F7 

Fault in internal memory holding 

Exchange the calculator 

F9 

Fault in the electronics 

Exchange the calculator 

8. 

Notes 

The  following  applies  for  MID  conforming  appliances  in  Ger-
many:  For  new  installations  in  pipework  less  than  or  equal  to 
DN 25,  the  installation  of  short  sensors  must  only  be  made  if 
they are directly immersed.  
 
 

Gyr GmbH 

Humboldtstrasse 64 

90459 Nuremberg 

Germany 

 

Содержание ULTRAHEAT T550

Страница 1: ...d As far as disposal is concerned the calculator is a waste electronic appliance in the sense of European Directive 2012 19 EU WEEE and it must not be disposed of as domestic waste The relevant national legal regulations must be observed as the appliance must be disposed of via the channels provided for this purpose The local and currently valid legislation must be observed The calculator may cont...

Страница 2: ...erature sensors into the pockets ball valves or T pieces The end of the temperature sensors must reach at least to the centre of the pipe cross section Seal the temperature sensors to protect against manipula tion Put the housing cover in position and press it gently until all the lugs click into place audibly 3 2 Connection of flow sensor Note The flow sensor must be installed at the same circuit...

Страница 3: ...and press it gently until all the lugs click into place audibly Installing power supply module Note The 110 V 230 V connections may only be made by an electrician To install a power supply module proceed as follows Move the red locking hatch to the left Move the right outside rubber sleeve upwards and out wards Pull the sealing plug Thread the module s mains voltage connetion cable through the sle...

Страница 4: ...n modules Note You will find the technical details and data on communication modules in their documentation Note You will find the permitted combinations in the T550 UC50 technical description Note The meter recognises the inserted modules automatically 30 seconds at most after installation and is ready for communications or pulse output Note The type of module inserted can be displayed within the...

Страница 5: ...t To close the parameterisation proceeds as follows Press the service button during parameterisation ESC function The LCD display shows the last valid value 4 9 Service software With the service software tariffs and communication modules can be set in parameterisation mode 5 Getting started Attention Calculators with one time adjustable pulse value and adaptable mounting place being characterized ...

Страница 6: ...ary in exchange with F1 Interruption in the hot side tempera ture sensor Check hot side temperature sensors replace if necessary F2 Interruption in the cold side tem perature sensor Check cold side temperature sensors replace if necessary F3 Electronics for temperature evalua tion defective Exchange the calculator F4 Problem with the power supply Battery flat Check connection Change battery F5 Sho...

Отзывы: