Landis & Gyr T450 Скачать руководство пользователя страница 1

1 General

Note

These operating instructions remain with the end user after

commissioning.

Note

In the following text, the term "meter" is used to refer to

both the heating meter as well as the cooling meter unless

otherwise stated.

1.1 Use

The meter is used to measure the heat or cold consumed in

heating/cooling systems.

The meter consists of two temperature sensors and a calculator,

which calculates the energy consumption based on the volume

and temperature difference.

1.2 General information

The meter has left the factory in a technically safe condition.

Further technical support is provided by the manufacturer on

request. The meter's calibration-relevant security symbols must

not be damaged or removed. Otherwise, the warranty and

calibration validity of the meter will be invalidated.

Keep the packaging in a safe place so that you can transport

the meter in its original packaging after the calibration

validity has expired.

Lay all cables at a minimum distance of 500 mm from power

and high-frequency cables.

A relative humidity of < 93 % at 25°C is permissible (non-

condensing).

Avoid overpressure cavitation throughout the system, i.e. at

least 1 bar for qp and approx. 3 bar for qs (applies for

approx. 80 °C).

The control line must not be cut, shortened or extended.

In the case of a heat meter or combined heat/cooling 

meter, the cold side installation location corresponds to the
return 

 and the warm side installation location

corresponds to the supply 

.

In the case of a cooling meter 

, the warm side

installation location corresponds to the return 

 and the

cold side installation location to the supply 

.

2 Safety instructions

Caution

The meters may only be used in building installations and

only for the applications described.

Caution

The local regulations (installation, etc.) must be observed.

Caution

The operating conditions on the nameplate must be

observed during use. Failure to comply with these

regulations can cause dangerous situations and voids all

claims arising from liability for defects as well as liability on

the basis of any expressly granted guarantees.

Caution

Comply with the requirements for circulation water (CEN /

TR 16911:2016).

Caution

The meter is only suitable for circulation water in heating

systems.

Caution

The meter is not suitable for drinking water.

Caution

Do not lift the metre on the calculator.

Caution

Pay attention to sharp edges on threads, flanges and the

measuring tube.

Caution

Only personnel trained in the installation and operation of

meters in heating/cooling systems may install and remove

the meter.

Caution

Only install or remove the meter on an unpressurised

system.

Caution

After installing the meter, check the leak tightness of the

system.

Caution

Breaking the safety marks relevant for calibration voids the

warranty and the validity of the calibration.

Caution

Avoid contact of the meter housing with silicone oils or

substances containing silicone oil.

en

Operating Instructions

Ultrasonic Heat and Cooling Meter

3221101003_a

07.02.2020

Translation

T450

© Gyr

Subject to change without prior notice

07.02.2020

1

Содержание T450

Страница 1: ...esponds to the supply In the case of a cooling meter the warm side installation location corresponds to the return and the cold side installation location to the supply 2 Safety instructions Caution The meters may only be used in building installations and only for the applications described Caution The local regulations installation etc must be observed Caution The operating conditions on the nam...

Страница 2: ...he meter contains lithium batteries Do not dispose of the meter and batteries as household waste Observe local regulations and laws regarding disposal Warning After lithium batteries have been used you can return them to the manufacturer for proper disposal When shipping batteries please observe legal regulations which among other things govern the labelling and packaging of hazardous goods Warnin...

Страница 3: ...ranged in multiple loops LOOPs The default state is LOOP 0 Proceed as follows to switch between the LOOPs Press button 2 until the desired LOOP appears After the last loop LOOP LE LOOP 0 is displayed again 3 3 2 Advancing in a loop To advance to the next display value within a loop proceed as follows Press button 1 After the last display value the first display value appears again 3 3 3 Loop LOOP ...

Страница 4: ...e 5 55 C Housing protection class IP 54 IP 68 optional EN 60529 Response limit for ΔT 0 2 K Temperature difference ΔT 3 K 120 K Temperature measurement range 0 180 C LCD 8 digit Optical interface Standard EN 62056 21 Communication Optional e g M bus Splitability Always removable cable length optional Temperature sensor Type Pt500 or Pt100 EN 60751 Temperature range 0 150 C up to 45 mm overall leng...

Страница 5: ...6 Declaration of conformity Landis Gyr GmbH Humboldstrasse 64 90459 Nuremberg Germany Landis Gyr Subject to change without prior notice 07 02 2020 5 ...

Отзывы: