
17
Maintenance
For higher altitudes, the air band opening may need to
be increased; for lower altitude, the .air band may need
to be decreased.
For higher humidity, the air band opening may need to
be increased; for lower relative humidity, the .air band
may need to be decreased.
For higher ambient temperatures the air band opening
may need to be increased; for lower ambient tempera-
tures, the air band opening may need to be decreased.
Adjust to your operating location’s environment as-
needed for best smoke spot and performance
compliant with local, state, and federal regulations
CAUTION: If white smoke appears from burner
exhaust vent during start-up or operation,
discontinue use and readjust air bands.
NOTE:
If a flue is installed, have a professional
serviceman adjust your burner for a #1 or #2 smoke
spot on the Bacharach scale.
Coil Removal
Removal of coil because of freeze breakage, or to
clean soot from it can be done quickly and easily.
Step 1
Disconnect hose from pump to inlet
side of the coil.
Step 2
Disconnect electrical connection
to the thermostat.
Step 3
Remove quick coupler from discharge
side of coil.
Step 4
Remove burner assembly from
combustion chamber.
Step 5
Remove the 3-3/8" bolts from each
side of coil and tank assembly (these
bolts are used to fasten tank to
chassis).
Step 6
Disconnect 1/2" pipe nipples from inlet
and discharge side of coil.
Step 7
Remove top tank wrap exposing
insulation and coil and fold back
insulation.
Step 8
Remove bolts that hold down coil to
bottom wrap.
Step 9
Remove coil.
Replace or repair any insulation found to be torn
or broken.
Coil Reinstallation
Reinstall new or cleaned coil by reversing the steps
above.
Final Note
The DC motors used on 12V DC burners can draw as
much as 20 amps! For the burner to run properly, the
battery and engine charging system must be kept in
good condition, and the engine must run fast enough to
adequately charge the battery. Do not throttle down the
engines for any length of time.
Landa MHP Operator’s Manual 8.913-925.0 - T