background image

7

/

7

Using the percentages of the reference value

You can use the percentages of the reference value to help you determine the strength of the site. Table 6
lists ranges of reference value percentages, and the action you should take.

% of the

reference

value

Battery condition

Action

>80%

Good

Check the battery to look for physical damage

60-80%

Serviceable with
maintenance

Check for problems and refer to
• Test results or other information about the site to
determine the cause of low readings.
• Your company maintenance procedures for battery
maintenance
• IEEE standard 1188-1996: Recommended Practice
for
Maintenance, Testing and Replacement of
valve-Regulated,
Lead-Acid (VRLA) Jars for Stationary Application

<60%

Unserviceable

Replace the jars. Refer to your company jar
replacement procedures or IEEE standard 1188-1996.

Содержание CTE-3000

Страница 1: ...es the status of a battery in voltage and conductance values It displays conductance values in Siemens S Ampere hours Ah are a typical measurement of jar capacity however they are difficult to measure...

Страница 2: ...ange of 300 2200S batteries about 30Ah 300Ah Data Storage CTE 300 can store 100 groups of test results and you can output the test results to your computer with the USB cable Parts of the analyzer CTE...

Страница 3: ...g For this reason the following options are listed in the order you should take to obtain a reference value 1 Consult your company documentation for previous reference values that were created for the...

Страница 4: ...test all batteries of the group and use the average conductance value as your reference value Chapter 3 Testing 3 1 1 Connect Tester Shake the clamps back and forth to make sure they are well connect...

Страница 5: ...up interface Default voltmeter is ON refer to figure 1 Figure 1 Startup Interface with Voltmeter on At the middle bottom of the startup interface it displays the voltmeter value which can be used as D...

Страница 6: ...w Results view all of your tested results supported maximum 100 groups of testing results 3 4 2 Export Data You may output the tested results to your computer Firstly you should install the software P...

Страница 7: ...to look for physical damage 60 80 Serviceable with maintenance Check for problems and refer to Test results or other information about the site to determine the cause of low readings Your company main...

Отзывы: