27
Call 1-888-370-6531 for Technical Support
6.3.4 Air Compressor Maintenance
How often?
Check pressure regularly. Adjust, clean and replace vanes as necessary.
Tools Required:
9/64 inch Allen wrench, 3/8 and 7/16 inch wrenches, small flat-blade screwdriver, GAST
compressor cleaning fluid, shop towel, rubber gloves, safety glasses.
Procedure:
1. Wear all safety equipment.
2. Replace the compressor air filter
annually (PN 20210112).
3. Start the burner by moving the wall
thermostat above room temperature
and note the air compressor output on
the gauge. If the gauge reading is in
the 3-4 PSI range, the air compressor
is operating as designed and no further
maintenance is required.
4. If the gauge reading is below 3 PSI,
try to increase the pressure by
adjusting the air bleed valve. If you
are unable to achieve 3 psi,
check/do the following:
Vanes
Air Compressor
Cover Plate
Carbon Gasket
Filter
Pressure
Adjustment
Vanes (4)