17
Call 1-888-370-6531 for Technical Support
5.5 Everyday Operation of Your Used Oil Heater
Once installed and inspected, operate your heater as follows:
Daily Operation.
•
Set the room thermostat to the desired temperature. The heater should cycle on and off
automatically based on the temperature.
•
When the fuel level starts to get low, a float switch in the tank will cut the thermostat
circuit and the “Low Fuel” light will illuminate. Add sufficient fuel to tank and operation
should resume on its own.
•
Do not shut power off to the heater unless it will not be used for an extended
period of time (over 2 weeks). This will keep the oil hot and ready to fire.
Manage the Used Oil.
•
Do not put unapproved substances into your used oil storage tank. See section 1.4 for a
list of approved fuels.
•
Monitor the bottom of your tank for water and drain it off on a regular basis.
•
To extend the cleaning interval of the in-tank filters, pre-screening the oil prior to putting it
into the tank is recommended.
Monitor the System.
•
After your initial set up, monitor the system gauge readings on a regular schedule to
assure that the system is stable. Record the readings and any maintenance performed
in a maintenance log (see Sect. 8.3) to track your system performance over time. An
hour meter is provided on the wiring box to keep track of run hours.
•
Maintain your heater. Regular maintenance will help to keep the heater running reliably
and efficient for many years.
•
To shut down the heater in an emergency, turn off the power at the
professionally installed, switched junction box or main breaker.
•
Do shut power off to the heater if it will not be used for 2 weeks or longer. This
will prevent oil from cooking in the nozzle block.
Содержание MX 75
Страница 2: ......
Страница 41: ...8 Appendices 8 1 Wiring Diagram ...
Страница 42: ......
Страница 43: ...34 Call 1 888 370 6531 for Technical Support 8 2 Primary Control Instructions ...
Страница 44: ...35 Call 1 888 370 6531 for Technical Support Not used with RES 75 kBTU h units ...
Страница 45: ...36 Call 1 888 370 6531 for Technical Support No latch up with RES 75 kBTU h units ...
Страница 46: ...37 Call 1 888 370 6531 for Technical Support ...
Страница 54: ...45 Call 1 888 370 6531 for Technical Support 9 ...