Commissioning
NOTICE
The P-factor (proportionality factor, parameter 899) is specified by the parameter setting. The
new correction is obtained from two input quantities, deviation and P-factor. This would be
transmitted to the VMS as an output. The procedure is repeated after lag time's expiry. If the
internal firing rate has changed during this time, the O
2
controller exits this routine. It must then
be reactivated again as described above, via channel key 2 (4).
Deactivate test mode
Select channel key 2 (4) downwards
6.6.5.6 Lag time (Parameters 898 / 900)
Setting the control parameter:
t1 __ t4 = controlled system’s dead time
Specified by parameters 898 and 900.
The calculated value should be entered into parameter 898.
Factory setting: 15 seconds.
In parameter 900, the dead time can be adjusted according to the firing rate.
The dead time is reduced at full firing rate, due to the high gas velocities.
Factory settings: dead time is reduced by 3 seconds
To calculate dead time at full firing rate: proceed as described above.
Guideline for 2 or 3-draught boiler:
Parameter 898
12 seconds
Parameter 900
3 seconds
The P-factor should be adjusted so that a target/actual value deviation of 1...2 vol.% O
2
is cor-
rected within 4...6 steps without overshooting.
6.6.5.7 P-factor (Parameter 899)
Actuation pulse too short
increase P-factor in parameter 899
Overshooting
reduce P-factor in parameter 889
Repeat until the target value is corrected within approx. 4 ... 6 steps.
Check controller setting at intermediate and full firing rate.
Содержание VMS Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...