44
8
Options
8.1.2
Factory Setting of Analogue Outputs via LSB Module
The module is activated at the factory. In case of a later installation or exchange, the LSB ad-
dress 19 must be set on the module using only 2 rotary switches.
Analogue output 1 (O
2
measurement value)
•
Setting range
0 … 25 % O
2
adjustable
•
Factory setting: 0 … 10 Vol.% O
2
4 … 20 mA, fault 0 mA
1
Analogue output module
Terminal assignment:
2
LSB terminal resistance, 120
1+ / 1-
Analogue output 1
3
Rotary switch for setting the tens
LSB address
2+ / 2-
Analogue output 2
4
Rotary switch for setting the ones
LSB address
3+ / 3-
Analogue output 3
5
Jumper plug
4+ / 4-
Analogue output 4
24 VDC
Voltage supply for LT3 Terminals
77-/78+
CAN H/L
LAMTEC SYSTEM BUS for LT3
Terminals 74 H/75 L