99
14
Appendix
1
The product must not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
1
The product must not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
Connecting/extension cable
Type
14-wire, shielded (e.g. LiYCY)
Cable length
Maximum extension after 3 m (9.84 ft.) of connecting cable at
a supply voltage of 20.4 V:
Cross-section 0,5 mm
2
/20 AWG length 100 m/328.08 ft
Cross-section 1,0 mm
2
/17 AWG length 200 m/656.17 ft
Deviating cable lengths such as:
Cross-section: 0.5 mm
2
/20 AWG length 150 m/492.12 ft
150 : 0.5 x 0.0059 +19.2 = 21.0 V
The supply voltage must be > 21.0 V.
Wear parts
None
Technical capacity
Operating mode
Continuous operation
72 hours of operation in accordance with TRD 604
Safety integrity level
DIN EN 61508:2011, SIL 3 part 1 to 7
Overvoltage category
IEC 60730-1:2010, ÜKIII
Susceptibility to interference
IEC 60730-1:2010
Emitted interference
DIN EN 55022:2006, Class B
Climatic range
Protection class:
DIN EN 60529:2000, IP67, NEMA 4X
Operating temperature range
Operating temperature (F300K)
1
- 40 … + 85 °C/-40 °F ... 185 °F (device-internal display)
Relative humidity
0 % ... 95% non-condensing
Storage/transport conditions
Storage location
Enclosed spaces
Air temperature (F300K)
1
- 40 … + 85 °C/-40 °F ... 185 °F
Use in potentially explosive atmospheres
Device group/category, potentially explosive
area, standard
1
II 3G, Zone 2, 22 IEC60097-0, DIN EN 60079-0
Class I Division 2 ANSI/ISA-12.12.01, CAN/CSA C22.2
No. 213
Identification marking
Ex nA nC ic IIC T6...T5 Gc X, Ex tb IIIC 85°C Dc X, Cl I Div2
GrA T5
Relative humidity
0 % ... 95% non-condensing
Operating temperature range
Ambient temperature
1
T5 -40 °C … + 80 °C/-40 °F ... 176 °F
T6 -40 °C … + 70 °C/-40 °F ... 158 °F
Additional specifications
1
Read the section entitled "Important information on protection
in potentially explosive atmospheres".
Содержание F300K IR-2
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F300K Compact Flame Scanner ...
Страница 2: ......
Страница 26: ...25 5 User Interface 5 2 Menu tree ...
Страница 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Страница 46: ...45 6 Commissioning The data has now been determined and sent to the flame scanner Fig 6 21 Successful transfer ...
Страница 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Страница 122: ...121 14 Appendix ...
Страница 125: ...124 14 Appendix ...