8   Internal Burner Firing Rate Controller

8

Internal Burner Firing Rate Controller

8.1

Purpose

The internal firing rate controller calculates the burner firing rate against a pre-defined setpoint 

value (e.g. as a function of temperature or pressure) by comparison with the actual value. This 

position will be transferred to the electronic fuel/air ratio control as a default value.

8.2

Moving Screen "Actual Temperature is too high"

8.3

Changing Setpoint of Burner-Firing-Rate Controller

see chapter 

8.5 How to Change the Burner-Firing-Rate Controller with the Customer Interface

8.4

Burner-Firing-Rate specified by hand

It is also possible to switch the ETAMATIC OEM to "Manual Control" with the terminals. By 

short-circuiting the Pt100 signal (e.g. bridge terminal 19 and 20) the burner firing rate control

-

ler is switched off. The fuel/air ratio controller then directly follows the input at the default firing 

rate input. The display shows LE instead of HA.

NOTICE

Only use manual control while monitoring the system.

8.5

How to Change the Burner-Firing-Rate Controller with the Customer Interface

Keep pressing the HAND key for more than 5sec., to switch the customer interface to the 

mode „set setpoints of burner firing rate controller“. This is only possible when burner firing 

rate controller is activated. At the same time, the HAND mode for manual firing rate input ends.
In the mode „setting firing rate controller“ the LED in the manual-key flashes. The lower display 

line shows the output regulator adjustment, the setpoint value and the actual value.

Active constant controller:

The Gerät can be started nevertheless by pressing the manual mode key provided that 

the maximum temperature is not exceeded.   

By pressing the manual mode key once more you switch to AUTO mode.

Press key MANUAL to move the regular firing rate input of the firing rate controller.
Press the keys 2 and 3 to variegate the burner firing rate.
Press key MANUAL again to cancel firing rate controller.

Press the key for 5 s long. Display = actual setpoint 1 or  2. 

This depends on the choice of setpoint values of terminal 50:

Terminal 50 = 0 V = setpoint value 1

Terminal 50 = 24 V = setpoint value 2

Содержание ETAMATIC OEM

Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Quick Reference for Endusers ETAMATIC OEM ETAMATIC S OEM...

Страница 2: ......

Страница 3: ...s 10 6 2 Recalling Fault History 10 6 3 Resetting Faults 10 7 CO O2 Control 11 7 1 What happens if a fault occurs in the O2 trim 13 7 2 Resetting O2 Errors 13 7 3 Calling Fault History O2 trim 13 7 4...

Страница 4: ...regulations DIN EN 298 2012 11 DIN EN 1643 2014 09 DIN EN 13611 2011 12 DIN EN 60730 2 5 2015 10 DIN EN 60730 1 2012 10 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive 2014 68 EU Pressure E...

Страница 5: ...ility of imminent danger If it is not avoided it may result in death or very serious injury The plant including its surroundings could be damaged CAUTION This draws the user s attention to the possibi...

Страница 6: ...ugh the optionally available PC software or operating unit For dis play to end customers connect to customer interface via LAMTEC SYSTEM BUS The oper ation via PC software is written in a seperate man...

Страница 7: ...d Once all the channels have reached the ignition position the ignition transformer is activated on ist own for 3 seconds Before the valves open the respective fuel safety interlock chain has to be cl...

Страница 8: ...Fuel air ratio control O2 Flame intensity Operating hours Fig 5 2 Display with external burner firing rate controller Fig 5 3 Display in automatic mode Fig 5 4 Display in manual mode 70 setpoint of f...

Страница 9: ...after 5 s Fault of the O2 controller which lasts longer than 30 s would be saved After an idle time of 3 seconds provided that there is no operation of the keys within this time the display shows a d...

Страница 10: ...e RESET key effects as follows Leaving the 2nd display level in the lower display line Status report in the upper display line Disable manual mode Deactivate mode set burner firing rate controller Dis...

Страница 11: ...ponding operating hours counter value In initial state not MANUAL mode provided that no fault message of the ETAMATIC OEM is pending the upper display line is switching over 6 3 Resetting Faults NOTIC...

Страница 12: ...y Display of CO is replacing O2 display values as soon as CO control is active Fig 7 2 CO control display Startup Manager Display Example I O2 actual value II O2 setpoint III Operating status a Thresh...

Страница 13: ...a Threshold position Reduce air Raise air b 11 11 optimisation steps are already car ried out c big letter C optimisation with increasing firing rate small letter c optimisation with decreasing firin...

Страница 14: ...ee chapter 5 3 5 RE SET By pressing RESET you set back the O2 fault message The O2 fault is set back with every burner start up automatically This is applicable because with every burner start up a 10...

Страница 15: ...control while monitoring the system 8 5 How to Change the Burner Firing Rate Controller with the Customer Interface Keep pressing the HAND key for more than 5sec to switch the customer interface to t...

Страница 16: ...TE CON TROLLER mode Press the key for 5 s long Display actual setpoint 1 or 2 and actual value This depends on the choice of setpoint values of terminal 50 Terminal 50 0 V setpoint value 1 Terminal 50...

Страница 17: ...ng at both customer interfaces the shift key for a long time or one customer interfaces is disconnected temporarily Keep pressed the SHIFT key for a long time One after the other is shown CRC 16 of le...

Страница 18: ...ASE FIRING RATE EG SETTING BASE FIRING RATE as BASIC FIRING RATE but ETA MATIC OEM on SETTING NA POST PURGE AU BURNER OFF no signal present EL SETTING SL CLEAR MEMORY EV SETTING PRE PURGE as PRE PURGE...

Страница 19: ...EC 60127 2 Sheet 5 1500A 250VAC melting integral I t 40 A s e g Littelfuse 0215002 M XP Fuses which fulfills these requirements are ceramic tube fuses with the label T2AH 250V Fig 9 3 Rear view ETAMAT...

Страница 20: ...19 9 Appendix 9 3 EU Declaration of Conformity...

Страница 21: ...20 9 Appendix...

Страница 22: ...21 9 Appendix...

Страница 23: ...22 9 Appendix...

Страница 24: ...KG Wiesenstra e 6 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Publication no DLT2015 20 aEN 006 The information in this publication is subject to t...

Отзывы: