8.1
For Your Safety
The following factors must be taken into consideration for the assignment of the set-point val-
ues of the actuators for controlling the quantity of fuel and air and for setting the parameters
for correctional intervention:
•
Combustion chamber pressure
•
Fuel pressure
•
Temperature and pressure of the combustion air
•
Calorific value of the fuel
In the process, a safe, stable firing operation must be guaranteed across the entire output
range and in all firing operating modes.
This must be documented by measuring the characteristic values for an operation of the fur-
nace at the shut-off limits of the ratio control, as well as the set limits of the correction circuits
(e.g. an O
2
trim). To help you assess the situation, you should also refer to the informative
commissioning report.
It is essential that the procedure in chapter
6.3.4.1 Run to Shut-off Limits
For an equipment of the furnace with a failsafe CO controller, the check in the air deficiency
direction can be omitted. Instead, the shut-off limit of the CO controller (0.4 Vol.% O
2
) must
6.3.4.1 Run to Shut-off Limits
The correction limit in the excess air direction must also be limited to a non-critical range in
the event of CO controller operation.
If two or more systems of the CMS type are combined with a CO control device (e.g. two or
more burners for a combustion chamber), the safe operation of the combustion must be en-
sured with an additional flue gas monitoring system.
8.2
Safety Concept
The CO controller attempts to keep the combustion process within in the range of complete
combustion, i.e. just above the CO edge. To do this, the controller outputs a correction signal
which is evaluated by the electronic ratio control in order to move the positions of the actuating
devices in the direction of less or more air.
The set maximum correction range limits the possible influence of the controller. It is not pos-
sible to leave this range.
The position of the electronic ratio curve and correction range must be set in such a way that
the electronic ratio control can exceed the CO edge towards less air under all operating con-
ditions. The CO edge towards excess air must not be exceeded.
The following figure depicts this once more.
Содержание AEC-TPS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...