background image

49

SWITCHING OFF

PROLONGED SWITCHING OFF

If the boiler should remain inactive at length close the gas tap and cut electrical power supply to the appliance.

TEMPORARY SWITCHING ON/OFF

Proceed in one of the following ways:

use the room thermostat;

use the adjustment potentiometer (on the instrument panel).

MAINTENANCE

Note:

With a new boiler or after a long period of
inactivity, the locking of the circulating pump can
occur. In this case it is necessary to unscrew the
front stopper and make the motor shaft rotate
with a screwdriver.

To ensure long-lasting product functionality and efficiency within the limits prescribed by the laws and stand-
ards in force, the unit must undergo regular maintenance.
Frequency of inspection depends on the specific conditions of installation and use but it is advisable to have the
unit checked 

once a year

 by authorised 

Lamborghini Service

 personnel. Only properly qualified personnel

with specific knowledge in the field of safety, efficiency, environmental hygiene and combustion may carry out
work on the unit. To ensure proper maintenance it is also required that such personnel be fully updated on the
constructive and functional characteristics of the boiler.
Should work or maintenance be carried out on any structures situated near fume ducts and/or fume discharge
devices and their accessories always switch off the boiler and, when work is over, have its efficiency checked
by qualified personnel

IMPORTANT

: before doing any cleaning or maintenance work on the unit switch off the electrical power supply

via the switch on the boiler itself and via the system main switch. Then shut off the gas supply by closing the tap
on the boiler. The above stated, work generally involves the following:
- rimozione delle eventuali ossidazioni dai bruciatori;
- rimozione delle eventuali incrostazioni degli scambiatori;
- verifica dei collegamenti tra i vari tronchi di tubo, fumo e aria;
- verifica e pulizia generale del ventilatore (mod. MS);
- pulizia generali dei tubi;
- controllo dell’aspetto esterno della caldaia;
- controllo accensione, spegnimento e funzionamento dell’apparecchio sia in sanitario (eventuale) che in

riscaldamento;

Содержание XILO T 24 M W TOP

Страница 1: ...TO MANUALE D USO AL SIG UTENTE PLEASE MAKE SURE THAT THE USE MANUAL IS HANDED OVER TO THE USER TENGAN LA AMABILIDAD DE ENTREGARLE AL USUARIO EL MANUAL DE USO FAVOR ENTREGAR O MANUAL DE USO AO SR UTENT...

Страница 2: ...this manual at they give important safety instructions regarding installation and maintenance Keep this manual for future reference Installation must be carried out by qualified personnel who will be...

Страница 3: ..._______________________________ 36 GAS NOZZLE CALIBRATION __________________________________________ 37 ELECTRICAL CONNECTIONS WIRING DIAGRAMS _______________________ 38 MALFUNCTIONS AND ADJUSTMENTS _...

Страница 4: ...astic bags foam etc must not be left within reach of children as they are potential sources of danger This boiler is designed to heat water to a temperature below boiling atmospheric pressure It must...

Страница 5: ...E CONTROL probe in the down draught diverter detects variations in temperature and shuts down the boiler Efficient operation of this safety system depends on observance of the following Do not deactiv...

Страница 6: ...eading point 17 Expansion tank 18 Thermohydrometer 19 Malfunction warning light 20 ON OFF warning light 21 Lock out warning light 22 Hot water potentiometer if any 23 Function selector 24 Heating adju...

Страница 7: ...I kg XILO T 24 MS W TOP Return kW kW kcal h Return Heater 3 4 3 4 3 4 3 4 3 4 Thermal capacity Min thermal capacity Connections Expansion tank Weight Input Output kcal h XILO T 24 M W TOP 3 4 3 4 3 4...

Страница 8: ...s pressure mbar Gas type G20 20 mbar Natural Gas G30 28 30 mbar LPG G31 37 mbar LPG Burner jets mm 1 25 0 77 0 77 L C V kcal h 8 550 29 330 22 360 Delivery XILO T 24 MS XILO T 24 M m3 h 3 04 0 89 1 16...

Страница 9: ...with safety REGULATIONS IN FORCE Grounde connections are compulsory Connect the boiler to an efficient grounding system To gain access to the electrical panel which houses the power supply terminal bl...

Страница 10: ...TA Room thermostat if any TL Limit thermostat if any TIMER Boiler timer adjustment TST Safety thermostat VG Gas valve 1 Heating potentiometer 2 Selector Off Heater Heater Heating Reset Test 3 Hot wate...

Страница 11: ...ing sensor SS Hot water sensor if any TA Room thermostat if any TL Limit thermostat if any TIMER Boiler timer adjustment TST Safety thermostat VG Gas valve VN Fan 1 Heating potentiometer 2 Selector Of...

Страница 12: ...LA Timer G30 G31 LPG G20 Natural Gas post circ off heating post circ on 2 5 minutes JP2 JP1 Increase Increase Legend Off On Slow ignition adjustment Boiler timer adjustment R max Increase Max heating...

Страница 13: ...ening for the connections Attach the boiler to the hooks through the holes at the back of the frame push it up against the wall Make the necessary water connections LEGEND G Gas 1 2 3 4 see tap suppli...

Страница 14: ...tap 6 Safety valve 7 No water pressure switch 8 Circulator 9 Burner 10 Expansion tank 11 Fume pressure switch 12 Fan 13 Automatic air bleed valve 14 Total safety thermostat 15 Flue control 16 By pass...

Страница 15: ...s wall of the approved type The flexible corrugated metal pipes must be installed in such a way that their length in a state of maximum extension is not greater than 2000 mm The boilers are calibrated...

Страница 16: ...nal section perpendicular to the opposite internal wall of the chimney of being firmly fixed and sealed at the entrance without protruding beyond the inner walls of the chimney of receiving preferably...

Страница 17: ...not require any special ventilation it can also be located in small rooms lumber rooms laboratories In addition there are various possibilities for combustion fume evacuation and external air intake...

Страница 18: ...CENTRIC FLUE PIPE 3 m Maximum length of DOUBLE FLUE PIPE Intake Exhaust 30 m Installing an elbow to connect the boiler to the chimney will cause a drop in pressure The values set out in the table belo...

Страница 19: ...fter its stop when reaching the temperature selected on the heating potentiometer bridge off 2 5 minutes MODULATION MAXIMUM PRESSURE ADJUSTMENT remove the protecting cover G place the function selecto...

Страница 20: ...ency environmental hygiene and combustion may carry out work on the unit To ensure proper maintenance it is also required that such personnel be fully updated on the constructive and functional charac...

Страница 21: ...on of ignition electrode checking position of detection electrode checking combustion and efficiency parameters checking the no gas safety device checking combustion fumes outlet safety device mod M w...

Страница 22: ...r checking proper positioning of seal gaskets for model MS Then act as follows For transformation from G20 Natural Gas to G30 G31 LPG Insert the gas diaphram fig 2 Move jumper JP1 to ON position fig 3...

Страница 23: ...e A Flue cross section or height with joint not suitable for the boiler B Excessive gas consumption combustion is imperfect C Flames tend to detach D Flame has yellow tips A Replace unsuitable compone...

Страница 24: ...ge tap PAC S 80 450 mm PAC S 120 600 mm WATER CONNECTION MR Heating delivery RR Heating return MB Water heater delivery RB Water heater return ACS Hot water EAF Cold water inlet RIC Recirculation V No...

Страница 25: ...as illustrated in the wiring diagram Disconnect the boiler power supply Undo the two grating screws fig 1 Undo the two casing fixing screws fig 2 Raise the casing and then pull it towards you fig 3 To...

Страница 26: ...ANEL Turning dial A to the Heating Hot Water position as illustrated in the figure readies the boiler for operation with the heater Hot water temperature adjustment is effected by means of dial B on t...

Страница 27: ...thermostat if any TIMER Boiler timer adjustment TST Safety thermostat VG Gas valve 1 Heating potentiometer 2 Selector Off Heater Heater Heating Reset Test 3 Hot water potentiometer if any ASSEMBLY DIA...

Страница 28: ...sensor if any TA Room thermostat if any TL Limit thermostat if any TIMER Boiler timer adjustment TST Safety thermostat VG Gas valve VN Fan 1 Heating potentiometer 2 Selector Off Heater Heater Heating...

Страница 29: ...58...

Страница 30: ...rtuno per l evoluzione del prodotto The illustrations and data given are indicative and are not binding on the manufacturer LAMBORGHINI reserves the right to make those changes considered necessary fo...

Страница 31: ...MODULATING USER MANUAL For the attention of the INSTALLATION TECHNICIAN make sure that this manual is handed over to the USER IT 2 CALDAIA MURALE A GAS TERMO ALTO RENDIMENTO MODULANTE MANUALE PER L UT...

Страница 32: ...ULT FINDING CHART _________________________________________________15 Dear User you now own a product result of a thorough project and of advanced construction systems granting you the utmost reliabil...

Страница 33: ...rts of the boiler which during the operation become overheated These parts can be dangerous for children or inexperienced persons Do not obstruct the inlet or dissipation screens Do not make the boile...

Страница 34: ...me in this case switch gas main supply electricity and water supply off by their own cocks and switches As soon as one decides not to use the appliance further one should take care to render innocuous...

Страница 35: ...t for other installations beyond not being ideal for such a use it could in short bring serious damage to the other appliances connected to it Ask qualified personnel LAMBORGHINI SERVICE to check a th...

Страница 36: ...P 1 Lock out warning light 2 ON OFF warning light 3 Malfunction warning light 4 Heating adjustment potentiometer 5 Hot water adjustment potentiometer 6 Function selecto 7 Thermohydrometer CONTROL PANE...

Страница 37: ...on corresponding to desired water temperature HEATING HEATER MODE IF ANY Turn the selector switch 6 to Heating Heater position Regulate the heating potentiometer 4 to a position that corresponds to de...

Страница 38: ...ide boiler A Call technical service A Flue section or height with joint not suitable for the boiler B Excessive gas consumption combustion state is imperfect C Flames tend to move away or have yellow...

Страница 39: ...l evoluzione del prodotto The illustrations and data given are indicative and are not binding on the manufacturer LAMBORGHINI reserves the right to make those changes considered necessary for the impr...