38
GB
By doing this, access the reset request confirmation display with duration of 5s.
Pressing the key again determines the reset of the anomalies log and the returnto the position 1 log display for
functioning hours.
flashing
P
ARAMETERS
MENu
The
PARM MENU
is organised as per table 4.
BURNER TYPE
This parameter allows to set the type of burner and manage (two-stage or modulating burner).
Press key i to access the PARAMETER VALUE MODIFICATION mode, during which the value of the parameter
displayed flashes.In MODIFY PARAMETER VALUE mode, use the + and – keys to modify the value.
Press key i to memorise the current value displayed.To exit this mode without memorising the value, press key R
or wait 10s without pressing the keys.
FLAME SENSOR TYPE
- parameter not managed -
SEALING CONTROL
It is possible to enable or disable the sealing control procedure of the gas ramp safety valves.
MENU
RAPPRESENTATION
SETTABLE VALuES
MENU
PARAM
Burner type
2 stages / modulating
Flame sensor type
not managed
Sealing control
ON / OFF
Post-ventilation time
0 - 255 s
First stage solenoid valve advance opening
0 - 80
Second stage solenoid valve advance opening
(Not managed if MODULATING BURNER)
0 - 80