41
UK
CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a
drop in combustion air pressure. It will be calibrated at a pressure below 1st stage rated-flow
on-burner air pressure, checking that CO values do not exceed 10,000 p.p.m.
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to
shut it down if the gas pressure falls below the minimum required level. This setting should
be 40% lower than the gas pressure obtained with the burner operating at maximum delivery.
Pressure
connector
PRESSURE SWITCH
Type:
LGW 3 A2
GW 50 A5
GW 150 A5
Remove the cover and
adjust dial A
Model
Air pressure switch
DUNGS type
Setting range
mbars
Gas pressure switch
DUNGS type
Setting range
mbars
EM 16-E
EM 16/L-E
LGW 3 A2
0,4 - 3
GW 50 A5
GW 150 A5
5 - 50
5 - 150
EM 26-E
LGW 3 A2
0,4 - 3