TABLE FOR SOFTENED WATER VOLUMES IN RELATION TO HARDNESS
(regeneration times and floater position)
DOUBLE
35
RED Ejector
DOUBLE
50
RED Ejector
DOUBLE
65
RED Ejector
litres
floater
time
litres
floater
time
litres
floater
time
water
H mm
1’
water
H mm
1’
water
H mm
1’
20
10.500
100
13.750
260
20.600
150
25
8.400
100
11.000
260
16.400
150
30
7.000
100
9.100
260
13.700
150
35
6.000
100
7.800
260
11.700
150
40
5.200
100
6.800
260
10.300
150
45
4.600
100
6.100
260
9.100
150
Water
hardness
in
°
F
SET 1C 05 - 2C 10 - 3C 15 - 4C 8
SET 1C =8 - 2C= 10 - 3C = 20 - 4C = 12
SET 1C = 8 - 2C = 30 - 3C = 15 - 4C = 15
DEFINITION OF THE REGENERATION FREQUENCY FOR THE TIME SYSTEM :
volume of water treated (softened)
volume of water for daily consumption
E.g.:
Supposing that for DOUBLE 85 a daily consumption of 4200 litres is required (with hardness of 30
°
F)
17.000:4200=4 the number to set (in this case regeneration takes place every 4 days).
CORRESPONDING REGENERATION TIMES:
1 C =
6 minutes backwash
2 C =
30 minutes brine suction
3 C =
30 minutes slow rinse
4 C =
8 minutes rapid rinse
Height of floater = 500 mm
SYSTEM VOLUME - VOLUME TIME
N.B.
The number of litres of water to be set on the display is 1/100 that found in the table. E.g. value in table is 17.000.
The value to be set (17.000:100) = 170.
The litres are counted with a pulse every 100 litres, without changing the actual quantity of water.
N.B.
The litres of softened water shown in this table are obtained with intake water with a total hardness of max. 45
°
F
and salinity not exceeding 500 PPM, without oils, colourless and without turbidity.
Water consumption per regeneration is calculated as a function of the following parameters:
- time of each phase
- water flowrate at the drain
- operating pressure