Vega 900 Handbook
�
Part Number 17155
Modules
Note Output Range
Current
Slots
Turns
Max. Current
Limit
Settings for hazard-
ous energy
Standard Modules
H5/3
16.2-28V
5A
1
5
7.5A
>32V
9.1-15.5
6A
3
7.5A
-
H5/4
16.2-28V
5A
1
5
7.5A
>32V
16.3-24V
4.5A
4
6A
-
Seriesed Modules
BB4
32.6-40V
10A
2
8
12.5A
>19.2V
CC3
18.2-30V
18A
2
6
22.5A
>10.6
CC5
48.1-60V
10A
2
10
12.5A
>19.2V
DD4
28-36V
18A
3
8
22.5A
>10.6V
DD5
42-56V
15A
3
10
18.75A
>12.8V
EE2
7.6-15V
55A
4
4
75A
>3.2V
EE4
28-38V
30A
4
8
37.5
>6.4
EE5L
40-48V
18A
4
10
33.8
>7.1
EE5H
48-56V
18A
4
10
31.3
>7.6
HH5/3
25.3-38V
5A
1
8
7.5A
>32V
HH5/4
32.5-46V
4.5A
1
9
6A
>40V
C5B4
43-48V
10A
2
9
12.5A
>19.2V
Paralleled Modules
Z2(D1L+D1L)
1.8-3.4V
95A
3
1+1
125A
>1.9V
Z3(E1+E1)
1.8-3.4V
114A
4
1+1
150A
>1.6V
Z4(D1H+D1H)
3.9-5.1V
95A
3
1+1
125A
>1.9V
Z6(E2+D1H)
3.9-5.1V
104.5A
3.5
2+1
137.5A
>1.7V
Z7(D3+D3)
8-15V
45.6A
3
3+3
60A
>4V
Z18(L1+L1)
4.2-5.1V
66.5A
2
1+1
87.5A
>2.7V
Z19 (E5H+D5)
24-28V
36
3.5
5+5
40.05A
>5.9
Wide Range Modules
W5
5
0.25-32V
8.5A
1
5
9.5A
18>25.2V
1
C1Y module is only permitted in slot.
2
For PSUs with three D modules fitted or two D modules and an E module in slots
4/5 then D1L &
D1H in slots 2/3 is limited to 42A and in slots 4/5 is limited to 47A.
D2 in slots 2/3 is limited to 40A.
3
E2 module fitted in slots 4/5 is limited to 55A.
4
SELV and Outputs connected in Series
Outputs are SELV except as described below
- Non-earthed outputs that have secondaries with 2 or more turns are non-SELV as
a single fault in the secondary may make them exceed the SELV limit between
output and earth.
- Non-earthed ouputs that are connected in series are non-SELV unless all the
seriesed outputs use 1 turn secondaries and there are no more than 3 outputs
connected in series.
- Outputs connected in series are non-SELV if the total output v 20% of the
max, rated output voltage of the output with the highest rated voltage exceeds
60dc (the 20% addition allows for a single fault in any one individual channel)
- The total voltage of a seriesed output must not exceed 160V
- If any ouput or seriesed output is non-SELV then all the outputs in the PSU must
be considered non-SELV
Note
- Non-SELV outputs must be gaurded or a deflector fitted during installation to
avoid a service
engineer making inadvertent contact with the output terminals, or dropping a tool
onto them.
- All outputs operational spacings to earth, and due consideration must be given to
this in the end product design.
5
W5 is followed by V or R indicating Voltage or Resistance programming, both
followed by #
6
Actual voltage and current output of an X module is dependent, and limited by, the
ratings of the modules from which it is fed. The ratings given above for the X module
are additional rating li
mitations imposed by the X module itself.
7
The maximum power output of psu’s fitted with X modules is reduced from 900W b
y the
following power:
Power=0.55 x (Total X1 current) + 0.7 x (Total X2 + X4 current) + 0.9 x (Total X8 cur-
Module Limitations- Notes:
Safety approvals
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC/EN60950-1 - BSI Kitemark and CE mark.
CE marking when applied to any Vega product, indicates compliance with the Low Voltage Directive
(73/23EEC) as modified by the CE Marking Directive
(93/68/EEC) in that it complies with EN60950-1.
IEC/EN61010-1 and IEC/EN60601-1. CB Report .and BSI Kitemark
UL60601-1 and UL61010-1-UL Recognised, C-UL for Canada.
8.
Adjusting output voltage beyond the stated range may cause overvoltage protection
(OVP) to operate, whereby all outputs will turn off. To reset OVP, turn back output
voltage adjustment and remove the mains supply for 30 seconds and then will switch
back on.
Approval Limitations: Use in North America (AC units only)
When this product is used on 180VAC-250VAC mains with no neutral, connect the two live wires
to L(live) and N (neutral) terminals on the input connector. In this instance double pole fusing is
required.
High Voltage Warning
Dangerous voltages present within the power supply. Do not remove covers.
External Hot Surfaces
Section 6 of the Health and Safety at Work Act requires that manufacturers have an obligation to
protect service engineers as well as users. In order to comply with this, a label must be fitted to
these products which is clearly visible to service personnel accessing the overall equipment, and
which legibly warns that surfaces of these products may be hot and must not be touched when the
products are in operation.
Safety Earthing Screw
On products with an enclosure, special safety earthing screws are used which connect the cover to
the chassis. They must not be removed.
Safety Class of Protection
These products are designed for the following parameters : Material Group IIIb, Pollution Degree 2,
Overvoltage Category II, Class 1 (earthed), Indoor use as part of an overall equipment such that
the product is accessible to service engineers only.
Energy Hazards
Certain modules are capable of providing hazardous energy (240VA) according to output voltage
setting. Final equipment manufacturers must provide protection to service personnel against
inadvertent contact with these module output terminals. If set such that hazardous energy can
occur then the module terminals or connections must not be user accessible.
Servicing
These products are not customer serviceable. Repairs may only be carried out by Lambda UK or
their authorised agents. These products are not authorised for use as critical components in nuclear
control systems, life support systems or equipment for use in hazardous environments without the
express written approval of the Managing Director of Coutant Lambda Ltd.
Important safety instructions
The Vega family of component power supplies is designed for use within other equipment or
enclosures which restrict access to authorised competent personnel only. For safe installation and
operation of this product, carefully follow the instructions listed below.
i) The unit covers/chassis are designed to protect only skilled personnel from hazards and must
not be made user accessible.
ii) These products are Class 1 and must therefore be reliably earthed and professionally installed
in accordance with the prevailing electrical wiring regulations and the safety standards covered
herein.
iii) These products are IPX0, and therefore chemicals/solvents, cleaning agents and other liquids
must not be used.
iv) If the earth terminal of the Vega PSU is connected to the main incoming earth conductor of
the end equipment, the installer must cover the Vega earth symbol with a label bearing the earth
symbol of IEC60417-5019.
General installation instructions
Emissions :
EN55022 Conducted RFI-Class A or B (depending on product - Consult Technical
Sales). Radiated RFI - Class A
EN61000-3-2 / A14 - Pass - Class A and D. EN61000-3-3 / A1 - Pass
Immunity:
EN61000-4-2 - Level 4 Criteria B EN61000-4-3 - Level 3 Criteria B
EN61000-4-4 - Level 4 Criteria B EN61000-4-5 - Level 4 Criteria B, (Installation Class 4, Criteria B)
EN61000-4-6 - Level 3 Criteria B EN61000-4-11 - Pass
EMC performance
Dielectric Strength testing is carried out as follows
Primary mains circuit to earth - 2.25 - 2.35kVDC
Primary mains circuits to transformer core - 4.25 - 4.35kVDC*
Primary mains circuits to secondary -4.25 - 4.35kVDC*
Outputs to each other and to earth are isolated to 200VDC.
*This test is not possible with modules fitted to the unit as damage to RFI capacitors will occur)
Environmental parameters
Operation
Temperature 0 to 50
0
C (derating 2.5%
0
C above 50
0
C to 65
0
C - Not covered by approvals).
Humidity 5 to 95% RH non-condensing. Air Pressure 78kPa to 106kPa.
Altitude -200m to 3000m.
Storage and Transportation
Temperature -25
0
C to +85
0
C. Humidity 5% to 95% RH non-condensing.
Air Pressure 54kPa to 106k
Pa. Altitude -200m to 5000m.
Vibration and shock
10-200Hz @ 1.5G sinewave, 20G for 15 minutes in 3 axes random vibration / 3000 bumps, 10G
(16mS) half sinewave.
Cooling
Provided that the fan air intake and air outlet slots are not impeded, these units may be mounted
in any of 4 orientations: Horizontal, on either side, or vertical with airflow upwards. For correct
airflow, allow 50mm clearance around the side and ends of the product.
Level of insulation
Input markings and symbols
Terminal Block
Fast-ons
N
L
L
N
alternating current (a.c.)
direct current (d.c.)
danger, shock hazard
caution, refer to supplementary documents.
Earth
L
Live
N
Neutral
Custom Model
Model: NS-THE/V9FSSF B/S 28E5HS (K90036)
Input: 90-264Vac, 47-63Hz
Maximum output: 28V, 25A, maximum output power: 700W