15
-
Ext Fan Failed
-
Door Unlocked
AVR Feature:
Enable or disable Buck and Boost function. Factory default
setting is
“d
isable
”
.
Line Qualify:
Set AC recovery time after the line is qualified
. It’s
to make sure
the line is stable. The selectable options are: 3 seconds, 10 seconds or 30
seconds. Default value is
“
30 seconds
”
.
Line Detect ▼
Sense Type
Bat Temp Comp
Ext. Fan
Line Detect:
It allows users to set up detection levels for AC input voltages,
setting points to go in and out from battery mode, boost or buck modes.
-
Line High: When input voltage exceeds this level, unit will transfer from
Line Mode to Battery Mode.
-
Line Low: When input voltage is lower than this level, unit will transfer
from Line Mode to Battery Mode.
-
High Gap: The voltage gap between Line High and High Back, Buck High
and Buck Back.
-
Low Gap: The voltage gap between Line Low and Low back, Boost Low
and Boost Back.
-
Boost Low: When AVR function is enabled and input voltage drops between
Boost Back point and this level, unit will transfer to Boost Mode.
-
Buck High: When AVR function is enabled and input voltage increase
between Buck Back point and this level, unit will transfer to Buck Mode.
Sense Type
: Users can change the Sense Type according to operation
condition. Two types for selection:
-
Normal mode: The UPS can operate successfully with general line
conditions. The maximum transfer time is 12ms.
-
Generator mode: This setting allows UPS to work with the fluctuations
caused by a generator or noisy line. The maximum transfer time is 25ms.
Bat. Temp Comp:
It adjusts the battery temperature compensated voltage to
2.5, 3.0, 3.5 or 4.0 mV/°C/Cell. The factory default setting is 3.0 mV/°C /Cell.
Ext. Fan:
It indicates ambient temperature setting to switch on the external
fan. The default value is 25°C.
Bat Low Volt ▼
Charger I
Backup Timer
Default UPS
Bat. Low Volt:
It’s a
llowed to set the low battery warning voltage. The default
value is 46V.
Charger I:
It’s to c
onfigure the charger current. There are 2, 4, 6, 8 or 10Amp
for selection. The default value is 10A.
Backup Timer:
It’s to c
onfigure the warning time for backup time. This
function is available only when timer is set in dry contact. The adjustable range
is 0 to 480 minutes. The default value is 120 minutes.
Default UPS:
Restore factory settings of UPS.
Default SNMP
Test Timer
Set Date/Time
Password
▲
Default SNMP:
Restore factory settings of SNMP.
Test Timer:
It’s t
o define the time of Self-Test. The adjustable range is 1 to
255 minutes.
Set Date/Time:
It indicates setting for date and time.
Password:
The Password to access Setting and Control Menu can be changed
here. Use the SCROLL key with ENTER keys to enter a correct Password. Re-
entry is required if an error occurs when entering the password.