15 

 

-

 

Ext Fan Failed 

-

 

Door Unlocked 

AVR  Feature: 

Enable  or  disable  Buck  and  Boost  function.  Factory  default 

setting is 

“d

isable

Line Qualify: 

Set AC recovery time after the line is qualified

. It’s 

to make sure 

the  line  is  stable.  The  selectable  options  are:  3  seconds,  10  seconds  or  30 
seconds. Default value is 

30 seconds

 

 
 

 
 

     Line Detect     ▼
     Sense Type
     Bat Temp Comp
     Ext. Fan        

 

Line Detect:

 It allows users to set up detection levels for AC input voltages, 

setting points to go in and out from battery mode, boost or buck modes. 

-

 

Line High: When input voltage exceeds this level, unit will transfer from 
Line Mode to Battery Mode. 

-

 

Line Low: When input  voltage is lower  than this level, unit  will  transfer 
from Line Mode to Battery Mode.  

-

 

High Gap: The voltage gap between Line High and High Back, Buck High 
and Buck Back.  

-

 

Low Gap: The voltage gap between Line Low and Low back, Boost Low 

and Boost Back.  

-

 

Boost Low: When AVR function is enabled and input voltage drops between 
Boost Back point and this level, unit will transfer to Boost Mode.  

-

 

Buck  High:  When  AVR  function  is  enabled  and  input  voltage  increase 
between Buck Back point and this level, unit will transfer to Buck Mode.  

Sense  Type

:  Users  can  change  the  Sense  Type  according  to  operation 

condition. Two types for selection: 

-

 

Normal  mode:  The  UPS  can  operate  successfully  with  general  line 
conditions. The maximum transfer time is 12ms. 

-

 

Generator  mode:  This  setting  allows  UPS  to  work  with  the  fluctuations 
caused by a generator or noisy line. The maximum transfer time is 25ms. 

Bat. Temp Comp: 

It adjusts the battery temperature compensated voltage to 

2.5, 3.0, 3.5 or 4.0 mV/°C/Cell. The factory default setting is 3.0 mV/°C /Cell. 

Ext. Fan:

 It indicates ambient temperature setting to switch on the external 

fan. The default value is 25°C. 

 
 

       Bat Low Volt ▼
       Charger I
       Backup Timer 
       Default UPS

 

Bat. Low Volt:

 

It’s a

llowed to set the low battery warning voltage. The default 

value is 46V. 

Charger I:

 

It’s to c

onfigure the charger current. There are 2, 4, 6, 8 or 10Amp 

for selection. The default value is 10A. 

Backup  Timer:

 

It’s  to  c

onfigure  the  warning  time  for  backup  time.  This 

function is available only when timer is set in dry contact. The adjustable range 
is 0 to 480 minutes. The default value is 120 minutes. 

Default UPS:

 Restore factory settings of UPS. 

 

       Default SNMP       
       Test Timer
       Set Date/Time  
       Password     

 

 

Default SNMP: 

Restore factory settings of SNMP. 

Test Timer: 

It’s t

o define the time of Self-Test. The adjustable range is 1 to 

255 minutes. 

Set Date/Time: 

It indicates setting for date and time. 

Password:

 The Password to access Setting and Control Menu can be changed 

here. Use the SCROLL key with ENTER keys to enter a correct Password. Re-

entry is required if an error occurs when entering the password. 

 

 

 

Содержание ODUPS

Страница 1: ...tion Manual This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com 106 Bradrock Dr Des Plaines IL 60018 1967 CPN 144266 Instruction Drawing Number P25 LACUPS 2 Tel 847 299 1188 Fax 847 299 3061 Revision A01 Rev Date 01 21 ECN 2279 ...

Страница 2: ...ct with any internal components Do not operate this UPS outside the input and output ratings listed on the UPS nameplate Do not use this UPS for any purpose not described in the operation manual Mechanical Safety This UPS or parts of the UPS may get very hot during normal operation use care when working nearby Do not expose equipment to rain or snow Always install in a clean dry location Do not op...

Страница 3: ...ke pictures and contact the carrier immediately to file a damage claim Contact La Marche for a Return Material Authorization number to have the UPS sent back for evaluation and repair CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for any physical damages reported for repair Returns for Service Save the original s...

Страница 4: ... 5 2 Sensor cable wiring to the UPS 9 1 5 3 Wiring External Batteries 10 2 0 Operation 11 3 0 Menu Page 13 3 1 Status Menu 13 3 2 Event Menu 14 3 3 Setting Menu 14 3 4 Control Menu 16 3 5 Help Menu 16 4 0 Trouble Shooting 17 4 1 For PTS Module 17 4 2 For UPS Module 18 5 0 Approximate Back up Time 19 6 0 Specifications 20 6 1 Line Mode Specifications 20 6 2 Battery Mode Specifications 20 6 3 Charge...

Страница 5: ...ad over the specified input voltage frequency and ambient temperature range Optional Power Transfer Switch PTS that provide backup power when the UPS is under maintenance These components should be mounted inside an enclosure to provide protection from most weather conditions Understanding the Model Number The ODUPS model number is coded to describe the options that are included Find the model num...

Страница 6: ...nal block is the UPS AC power output 4 AC Output Breaker This circuit breaker is a resettable protective thermal circuit breaker to protect UPS output from overload and short circuits 5 Input Contact To activate a programmable alarm by shorting this input contact 6 Dry Contact Six sets of dry contacts will energize when programmable event occurs 7 Internal Fan It s to cool down inside temperature ...

Страница 7: ...ed to connect the UPS to the computer for remote control and monitoring 21 Intelligent Slot This optional slot is for SNMP card insertion to communicate with UPS The UPS can be monitored and controlled via a web browser or with SNMP protocols 1 2 PTS Module Optional The Power Transfer Switch PTS shown below allows the UPS to be removed for service replacement or maintenance without interrupting po...

Страница 8: ...no other parts needed It can be rack mounted or secured to a shelf such as in an outdoor cabinet with the mounting brackets shown in the following figure The brackets and the screws to attach them to the UPS case are available as part of the standard packaging Figure 3 UPS with Bracket for rack mounting 1 4 Mounting the PTS Optional The power transfer switch PTS is designed and factory installed w...

Страница 9: ... connectors on the UPS 2 Connect the AC input wires to the AC input terminal blocks on the PTS Ensure proper polarity Line Neutral and Ground to the respective terminal 3 Connect AC output wires to the AC output terminal blocks on the PTS Ensure proper polarity Line Neutral and Ground to the respective terminal Figure 5 Wiring the PTS to the UPS 1 5 2 Sensor cable wiring to the UPS 1 Connect the t...

Страница 10: ...10 1 5 3 Wiring External Batteries Unit supports 48Vdc battery Connect all battery packs as below chart It s suggested to connect at least 100Ah capacity battery Figure 7 Battery Connection Chart ...

Страница 11: ...h output LED on to show UPS is running from utility power Note If UPS keeps switching between inverter and line mode because of a noisy line the setting of UPS Sense type should be changed from Normal to Generator Switch off procedure For any reason you need to switch off UPS please follow below procedure 1 Switch off output circuit breaker 2 Switch off input circuit breaker 3 Switch off battery c...

Страница 12: ...loads At the same time batteries are charging Boost The unit automatically transfers to Boost mode to raise the lower input line voltage when output voltage drops to the user programmable preset limit Buck The unit automatically transfers to Buck mode to reduce the higher input line voltage when output voltage achieves the user programmable preset limit Battery The unit automatically transfers to ...

Страница 13: ...urn to default page Menu item LCD display Explanation Page 1 1 Serial No xxxxxxxxxxxxxx 2 I P V xxx xV 3 I P F xx xHz The Serial number of UPS The input line utility voltage The input line utility frequency Page 2 4 BAT V xx x V 5 BAT T xx C 6 O P V xxx x V 7 O P F xx xHz The average battery voltage The temperature of battery terminal The output voltage true RMS The output frequency Page 3 8 O P P...

Страница 14: ...vent number 3 3 Setting Menu User can set various critical parameters in this menu Choose the desired function on the screen by pressing ENTER button Press ESC button to return to default page To enter in Setting menu use default password 11111 Setting page Explanation Dry Contact Input Contact AVR Feature Line Qualify Dry Contact It indicates programmed values of C1 C6 contacts Factory default se...

Страница 15: ...Normal mode The UPS can operate successfully with general line conditions The maximum transfer time is 12ms Generator mode This setting allows UPS to work with the fluctuations caused by a generator or noisy line The maximum transfer time is 25ms Bat Temp Comp It adjusts the battery temperature compensated voltage to 2 5 3 0 3 5 or 4 0 mV C Cell The factory default setting is 3 0 mV C Cell Ext Fan...

Страница 16: ... minute Off All dry contacts are ineffective This action will be finished automatically after 1 minute Cancel Cancel this test immediately Ext Fan Test On Off Cancel Starts the external fan test On The external fan has power from battery This action will be finished automatically after 1 minute Off Cut off battery power This action will be finished automatically after 1 minute Cancel Cancel this t...

Страница 17: ...rify if power cord from UPS OUT on PTS is properly connected to the AC output terminal blocks on UPS UPS INPUT circuit breaker on PTS is open status Reset breaker Black and red control wires from PTS are not connected to PTS control connector of UPS Connect black and red control wires from PTS to PTS control connector of UPS 48VDC signal not available at the PTS control connector on the UPS Replac...

Страница 18: ... breaker Battery is not fully charged Recharge the battery and then test discharge time Dead battery Replace with new batteries UPS fault Return to repair center Alarm LED is lit Abnormal conditions are detected Solve the problem according to alarm information in Figure 21 Batteries will NOT charge Battery circuit is open 1 Check if battery cable is connected firmly and make sure battery connectio...

Страница 19: ...ck up Time Model Load VA Backup Time 48Vdc 100Ah Minutes Backup Time 48Vdc 200Ah Minutes 2KVA 200 1581 3161 400 751 1581 600 491 1054 800 331 760 1000 268 615 1200 221 508 1400 172 387 1600 136 335 1800 120 295 2000 106 257 ...

Страница 20: ...ut PTS Normal mode 12ms maximum Generator mode 25ms maximum Overload Protection 5seconds 125 150 load 60seconds 110 125 load Output short circuit Input Output Breaker Site fault detection Yes Efficiency Line mode 95 Efficiency AVR mode 90 External PTS power capacity 30A 6 2 Battery Mode Specifications Output Waveform Pure sine wave Output Voltage Regulation 120 or 230VAC 5 Output Frequency 50 60Hz...

Страница 21: ...95 non condensing Audible Noise 48dB Cooling Forced Air EMI Class A FCC CISPR EN50091 2 1995 Surge protection IEEE ANSI C 62 41 2KV L N Appropriate battery type AGM Charging Current 2Amp 4Amp 6Amp 8Amp 10Amp adjustable Max charger current limitation 10 8 Temperature C Charger Current A 40 50 Charging Algorithm 3 Step Charger Operating Temperature Range 20 C to 50 C Temperature C 70 230 240Vac mode...

Страница 22: ...e arrangements Should minor adjustments be required the local La Marche sales representative should be contacted to provide this service only All sales are final Only standard La Marche chargers will be considered for return A 25 restocking fee is charged when return is factory authorized Special chargers are not returnable In no event shall La Marche Manufacturing Co have any liability for conseq...

Страница 23: ...23 Appendix B Document Control and Revision History Part Number Instruction Number Issue ECN ...