Liquid Cooling System

WL 3000
1201.38ae

Laird Technologies Liquid Cooling Systems

 

www.lairdtech.com

User  

ManUaL

4  MainTenance

Check the coolant level and antifreeze regularly and refill if necessary.

4.1 heaT exchanger

In order to achieve maximum cooling capacity, the heat exchanger of the cooling unit must be kept clean. 
Check the heat exchanger every three months for cleanliness. If cleaning is required, perform the following:
 

1.  Disconnect the cooling unit from the main power source.

 

2.  Remove the side cover.

 

3.  Clean the heat exchanger with compressed air, a damp cloth or shop vacuum.

 

4.  Mount the side cover.

4.2 pUMp

The pump has incorporated a coolant filtering mechanism to keep debris out of the pump. It is 

 

recommended to check the filter every three months to make sure it is clean. If cleaning is required,

 

then perform the following:

 Note:

 If the filter is not cleaned, then degradation to pump may occur.

 

1.  Disconnect the cooling unit from the main power source and external hoses.

 

2.  Drain the coolant from the reservoir.

 

3.  Remove the side cover.

 

4.  Close the ball cock.

 

5.  Unscrew the filter cap with a wrench that can accommodate a 24 mm nut.

 Note:

 Some coolant may run out from the pump. Collect in a suitable container.

 

6.  Remove the filter and clean with mild soap and water or replace.

 

7.  Insert the filter into the housing and tighten the nut.

 

8.  Open the ball cock.

 Note:

 Do not operate the cooling unit when the ball cock is closed, as this can damage the pump.

 

9.  Mount the side cover and reposition the cooling unit on its legs.

 

10.   Refill the coolant in reservoir and run for 10 minutes to deaerate. 

 

Check the coolant level and refill if necessary.

Ball Cock

System 

Pressure

Содержание WL 3000

Страница 1: ...rwise cooling capacity will be reduced Clean the filter periodically otherwise the pump may degrade over time Use cooling hoses that can handle max pressure of liquid circuit and is resistant to corrosion from coolant Never operate the unit if it is damaged or leaking Before starting any service work on the cooling unit please disconnect from the main power source Page 1 9 WL 1000 1201 38ae Laird ...

Страница 2: ... Water circulates in a closed loop between the ambient cooling system and a cold plate at the heat source Heat is removed from water by an air cooled heat exchanger The capacity of the cooling unit is dependent on the temperature differential which is defined as the difference between the ambient temperature and the water outlet temperature The cooling unit is designed to remove 3000 W of heat at ...

Страница 3: ... L 2 2 Performance data Cooling capacity 3000 W Flow rate 6 0 L min at 4 bar Mains voltage 230 V 10 50 60 Hz Current consumption 2 5 A Noise level 55 dB A 50 Hz 59 dB A 60 Hz distance 1 m in any direction 2 3 Environmental specifications Ambient temperature 5 C to 40 C Storage temperature 25 C to 70 C storage without water Air humidity 20 to 80 2 4 Settings Maximum forward pressure 8 bar 0 5 bar F...

Страница 4: ...nnect the cable to the terminals according to the terminal diagram use a 3 mm screwdriver to connect the wires to the terminal block 5 Fill the cooling unit with approximately 3 7 L of coolant Note The coolant level must be approximately 3 cm above the fins to maintain peak cooling performance otherwise the cooling capacity will be reduced 6 Allow the cooling unit to run for 10 minutes and deaerat...

Страница 5: ...o check the filter every three months to make sure it is clean If cleaning is required then perform the following Note If the filter is not cleaned then degradation to pump may occur 1 Disconnect the cooling unit from the main power source and external hoses 2 Drain the coolant from the reservoir 3 Remove the side cover 4 Close the ball cock 5 Unscrew the filter cap with a wrench that can accommod...

Страница 6: ... Flow switch 95140538 4 Thermal switch 95160045 5 Lid 95179902 6 Motor 95205201 7 Pump 95205202 8 Flexible coupling 95205203 9 Fan 95251621 10 Capacitor for fan 95290701 11 Filter 6299012 5 Placing out of Operation 1 Disconnect the cooling unit from the main power source 2 Remove the electrical connections 3 Remove the hoses from the cooling unit 4 Remove the cap and drain the coolant in a suitabl...

Страница 7: ...Page 7 8 WL 3000 Liquid Cooling System WL 3000 1201 38ae Laird Technologies Liquid Cooling Systems www lairdtech com User Manual 6 Spare parts list and Illustration 9 8 4 11 7 1 3 6 3 10 6 5 ...

Страница 8: ...cific or general uses Laird Technologies shall not be liable for incidental or consequential damages of any kind All Laird Technologies products are sold pursuant to the Laird Technologies Terms and Conditions of sale in effect from time to time a copy of which will be furnished upon request Copyright 2012 Laird Technologies Inc All Rights Reserved Laird Laird Technologies the Laird Technologies L...

Отзывы: