Maintenance and Cleaning
Cleaning of Strainer
29
Laird Thermal Systems s.r.o
Operation Manual, 387009851
Date: 08/09/2022
Version: 1.0
Liquid-Air Cooling Unit LA 5000
387009381
9.4 Cleaning of Strainer
Fig. 11:
Locations of ball valve and strainer
1 Strainer cover
2 Ball valve
1)
Disconnect the unit from mains.
2)
Remove the side panel.
3)
Close the ball valve.
CAUTION
A small amount of coolant will leak from the pump.
Use a cloth or an appropriate vessel for absorption.
4)
Remove the strainer cover using a metric AF24 wrench.
5)
Take off the strainer and clean it. In case of damage the strainer must be replaced.
6)
Remount the strainer and screw on the cover.
7)
Re-open the ball valve.
8)
Should any coolant leak from the strainer the cover must be screwed on using a little more force.
9)
Remount the side panel.
CAUTION
Risk of damage to the pump, if the unit is operated with a fully closed ball valve!
Never start the unit, when the ball valve is closed.
1