E1, E3, E5, E10,  and E14 Series

Options
Flow Control

Models with an “F” in the 4th position of the model number are equipped with an output which functions as a flow 

switch to conform with dry five protection of UL1563. When the flow of the pump is equal to or greater than 26pm the 

contacts will close and remain closed until the flow drops below 16pm. The contact will remain open until the flow is 

26pm or greater, this is a low voltage isolated circuit, the contact is rated 5A at 250vac or 30vdc.

Variable Control

Models with a “V” in the 4th position of the model number are equipped with a dial that controls the pump speed.

Temperature Control

Adjustable models with a “B” in the 4th position of the model number are equipped with a dial that controls the pump 

to come on when the temperature drops below the set level. This can be adjusted between 68ºF (20ºC) to 158ºF 

(70ºC).

Operation

1. Completely fill the system before operating the pump. Do not start the pump until the system has been filled. Make 

sure the isolation valves are fully open and that there is water in the pump.

2. Purge air from the system prior to operating the pump. These two steps are very important. The pump should never 

be allowed to run dry. This can severely damage the pump and will void the warranty.

Mounting

 

For installation purposes the arrows on the side of the pump housing

indicate the direction of water flow through the pump. Check to make sure 

the pump is adequately supported and that neither the pump or the piping 

is severely stressed. Install the pump at a point closest to the highest static 

pressure point, but above the absolute lowest point in the system to avoid 

dirt and sediment build-up. If required by application and code, install a 

safety relief valve to protect against over temperature and pressure. Do not 

mount with the motor above the impeller. This can cause the pump to run dry 

leading to premature failure of the pump which voids the warranty. Refer to 

the figures below for proper orientation before installing the pump.

Correct Installation

Improper Installation - 

Do NOT mount in these orientations

Electrical

 

These instructions must be followed to reduce risk of electrical shock. All work should be performed by a qualified 

electrician and in accordance with the current national and local electrical codes and regulations. Consult the 

nameplate for electrical data. The motor is impedance protected. Make certain that a properly sized circuit is 

available. Wire size should be based on the current carrying (amp) capacity of the conductor. The pump must be 

grounded in accordance with the current national and local codes. Ground wire should be copper with a current 

capacity at least equal to that of the wire carrying power to the pump. Observe all minimum code requirements for 

your jurisdiction. For pumps supplied with a power cord, the current carrying capacity of the cord is suitable for proper 

operation. Make certain the receptacle is properly configured and in good working order. Check to make certain that 

the circuit is properly sized for the load. Isolation valves are recommended for both sides of the pump. Valves should 

be positioned to avoid leakage onto the motor and electrical compartment. All elbows, tees, and sharp bends in the 

piping should be installed sufficiently upstream or downstream of the suction and discharge ports. Avoid welding or 

soldering close to the pump, which could cause damage to the unit. The pumps are exclusively for built-in use. After 

installation, the end product must comply with the relevant product standard. Product standard regulations must be 

observed during fitting and electric installation. For E5 95190 and E5 95191 types, where 2 cables are attached, both 

cables for live (non SELF) voltage and are to be considered untouchable, as are all further connections and 

connected parts. Installation and electric connections shall be carried out by professionals only.

E1, E3, and E5

E10 and E14

Green

White

Black

Содержание Ecocirc E1 Series

Страница 1: ...trol 5th 1 110 120 Volts AC 2 208 240 Volts AC 3 100 240 Volts AC 6th W With Cord Blank No Cord 7th xx two digit suffix numbers changes with minor mechanical variations pump construction Installation Operating Manual Please read this manual carefully before attempting to install operate or maintain the product described Failure to comply with the information provided in this manual could result in...

Страница 2: ...10 95 203 10 32 150 50 122 30 22 100 240V 50 60Hz 12 3600 E1 Plastic 10 60 140 3 5 51 50 122 30 22 100 240V 50 60Hz 12 3600 E3 Brass 10 95 203 10 32 150 50 122 30 22 100 240V 50 60Hz 27 4800 E3 Brass Vario 10 95 203 10 32 150 50 122 30 22 100 240V 50 60Hz 27 4800 E3 Plastic 10 60 140 3 5 51 50 122 30 22 100 240V 50 60Hz 27 4800 E5 Strong Brass 10 80 176 10 32 150 50 122 30 22 100 240V 50 60Hz 50 5...

Страница 3: ... or any other reason a backup system s should be used Failure to follow any warning can result in personal injury and or property damage 1 Locate pump as close to the fluid source as possible thus making the suction line as short and direct as possible The unit should be placed where the motor and electrical components are protected from the weather and humidity 2 Attach piping suction line to suc...

Страница 4: ...ry leading to premature failure of the pump which voids the warranty Refer to the figures below for proper orientation before installing the pump Correct Installation Improper Installation Do NOT mount in these orientations Electrical These instructions must be followed to reduce risk of electrical shock All work should be performed by a qualified electrician and in accordance with the current nat...

Страница 5: ...t may mean there is still air in the system Turning the pump on and off several times will generally clear the remaining air If this gurgling noise persists recheck the system and re purge the air System and pump should now operate quietly and efficiently 4 Dry Run Protection Some pumps are equipped with Dry Run Protection After a series of start attempts if the pump does not detect that it is pum...

Страница 6: ...hat LAING shall not be liable or responsible for any costs incurred for labor services transportation or any other charges which may arise in connection with the removal of the product and or installation of repaired or replacement product LAING also shall not be liable for any injury loss or damage direct incidental or consequential including but not limited to incidental or consequential damages...

Отзывы: