Version 3.11
| HPI Combi Flow User Guide |
47
www.lafert.com
Par.
Name
Minimum
Maximum
Default
Units
P5-04 Modbus RTU / BACnet MSTP Data Format
-
-
-
-
Sets the expected Modbus telegram data format as follows:
-
:
No Parity, 1 stop bit.
-
:
No parity, 2 stop bits.
-
:
Odd parity, 1 stop bit.
E-
:
Even parity, 1 stop bit.
P5-05 Communications Loss Timeout
0.0
5.0
1.0
Seconds
Sets the watchdog time period for the communications channel. If a valid telegram is not received by the HP Combi Flow within this time
period, the drive will assume a loss of communications has occurred and react as selected below (P5-07).
P5-06 Communications Loss Action
0
3
0
-
Controls the behaviour of the drive following a loss of communications as determined by the above parameter setting (P5-06).
0 : Trip & Coast To Stop
1 : Ramp to Stop Then Trip
2 : Ramp to Stop Only (No Trip)
3 : Run at Preset Speed 4
P5-07 Fieldbus Ramp Control
0
1
0
-
Selects whether the acceleration and deceleration ramps are control directly via the Fieldbus, or by internal drive parameters P1-03
and P1-04.
0 : Disabled.
Ramps are control from internal drive parameters.
1 : Enabled.
Ramps are controlled directly by the Fieldbus.
P5-08 Fieldbus PDO4 Data Select
0
7
1
-
When using an optional Fieldbus interface, this parameter configures the parameter source for the 4th process data word transferred
from the drive to the network master during cyclic communications:
0 : Motor torque.
Output torque in % to one decimal place, e.g. 500 = 50.0%.
1 : Motor power.
Output power in kW to two decimal places, e.g. 400 = 4.00kW.
2 : Digital input status.
Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
3 : Analog input 2 signal level.
0 to 1000 = 0 to 100.0%.
4 : Heatsink temperature.
0 to 100 = 0 to 100°C.
5 : User register 1.
Can be accessed by PLC program or group 9 parameters.
6 : User register 2.
Can be accessed by PLC program or group 9 parameters.
7 : P0-80 value.
P0-80 value can be selected by P6-28.
P5-09 BACnet Device Instance Number (Low)
0
65535
1
-
P5-10
BACnet Device Instance Number (High)
0
63
0
-
When using BACNet MS/TP, these parameter together allow a unique Device Instance Number to be programmed into the drive. For
further information on using BACnet MS/TP, refer to section
P5-11
BACnet Maximum Masters
1
127
127
-
Parameter defines the maximum address of any BACnet masters that can exist on the current local MSTP BACnet network. Refer to
section 10.3. BACnet MSTP for further information.
When the device is polling for the next master in the network it will not poll about the value set in P5-11. For example, if the value is set
to 50 then when the drive finishes communicating and needs to pass control to the next master it will poll up to address 50 looking for a
response before rolling back to address 0.
P5-12
Fieldbus PDO-3 Data Select
0
7
0
-
When using an optional Fieldbus interface, this parameter configures the parameter source for the 3rd process data word transferred
from the drive to the network master during cyclic communications:
0 : Motor current.
With one decimal place, e.g. 100.
1 : Motor power.
Output power in kW to two decimal places, e.g. 400 = 4.00kW.
2 : Digital input status.
Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
3 : Analog input 2 signal level.
0 to 1000 = 0 to 100.0%.
4 : Heatsink temperature.
0 to 100 = 0 to 100°C.
5 : User register 1.
Can be accessed by PLC program or group 9 parameters.
6 : User register 2.
Can be accessed by PLC program or group 9 parameters.
7 : P0-80 value.
P0-80 value can be selected by P6-28.
P5-13
Fieldbus PDI-4 Function Select
0
1
0
-
When using an optional Fieldbus interface, this parameter configures the parameter source for the 4th process data word transferred
from the network master to the drive during cyclic communications:
0 : User ramp time.
In second with two decimal places.
1 : User Register 4.
Can be accessed by PLC program or group 9 parameters.
9
Extended P
arameters