Thank you for having chosen an LAE electronic product. Before installing the instrument, please read this instruction booklet carefully in order to
ensure maximum performance and safety.

1. INSTALLATION

1.1

The LDU15, size 77x35x77 mm (WxHxD), is inserted into the panel through a hole measuring 71x29 mm and is fixed by

pressing gently into the relative clamps. The rubber gasket should be inserted between the instrument frame and the panel, checking
that it adheres perfectly in order to prevent infiltration.

1.2

The instrument should work with room temperatures between -10°.. +50°C and relative humidity between 15%.. 80% inclusive.

Supply voltage, switched powers and connection set-up should scrupulously comply with the indications given on the container. To
reduce the effects of electromagnetic disturbance, keep the sensor and signal cables well separate from the power wires.

1.3

The sensor T1 measures the air temperature and activates in the thermostat control cycle; it should be placed inside the appliance

in a point that truly represents the temperature of the stored product.

CAUTION

: should the relays have to changeover a heavy load frequently, it is advisable to contact the manufacturer for indications on the lifetime

of the contacts.
Whenever products must be kept within very severe specifications or the products have considerable value, the use of a second instrument is
recommended, which activates upon or warns of any malfunction.

2. CONFIGURATION

The controller or regulator is adapted to the controlled system by suitably programming the configuration parameters, that is, through
the setup. The setup is accessed by pressing the buttons 

in succession and keeping them pressed simultaneously for 3

seconds. The available parameters appear in table 1 as shown below.
Press the button 

to pass from one parameter to the next and the button 

to go back. Press 

to display the value correlated to

the parameter and press 

and 

or 

simultaneously to change it. Exit from setup is by pressing 

or is automatic after 30 seconds

of not using the keypad. Setpoint 

SP

display and adjustment is also possible during normal operation of the controller by pressing the

and 

or 

buttons. The range in any case remains within the limits 

SPL

and 

SPH

.

3. DISPLAYS

Upon switching on, just the central line (autotest) appears on the display for approximately three seconds and the subsequent
indications depend on the operating status of the controller. Table 2 gives the indications associated with the various states.
The temperature measured by the sensor T1 is handled by the microprocessor so that it is displayed in the most representative way. In
other words, the parameter 

SCL

is used to select the display in °C  with 0.1/1° auto-range (SCL=1°C), in °C with 1° fixed resolution

SET

AUX

SET

SET

SET

INSTRUCTIONS FOR INSTALLATION AND USE.

LDU15

SPL

-10.0.. SPH [°]

Minimum temperature set point

SPH

SPL.. +25.0 [°]

Maximum temperature set point

SP

SPL.. SPH [°]

Effective temperature set point

HYS

+0.1.. +10.0 [°]

Thermostat hysteresis

CRT

0.. 30 [min]

Compressor rest time

CDC

0.. 10

Compressor regulation with sensor T1 failure

DFR

0.. 24

Defrosting frequency /24h

DTO

1.. 120 [min]

Defrosting duration

DDY

1.. 60 [min]

Defrosting display control

ATL

-12.0.. 0 [°]

Low alarm differential

ATH

0.. +12.0 [°]

High alarm differential

ATD

0.. 120 [min]

Temperature alarm delay

ACC

0.. 52 [weeks]

Condenser periodic cleaning

OAU

NON/SBY/MAN/DEF/ALR

Auxiliary output mode of operation

BAU

NON/SBY/MAN

Auxiliary button mode of operation

SCL

1°C/2°C/°F

Readout scale

OS1

-12.5.. +12.5 [°]

Sensor T1 correction

SIM

0.. 100

Display slowdown

ADR

1.. 255

Peripheral address

TABLE  1