background image

AD3-5 INSTRUCTIONS FOR USE

Thank you for having chosen an LAE electronic product. Before installing the instrument, please read this instruction booklet 
carefully in order to ensure safe installation and optimum performance.

DESCRIPTION

 

 

 

INDICATIONS

     

 

 

 

     

 

 

   Thermostat output

     

 

 

   Fan output

     

 

 

   Defrost output

     

 

 

    Activation of 2nd parameter set

     

 

 

   Alarm 

 

 

     

Fig.1 — Front panel

  Info / Setpoint button. 

 

 

  Increase / manual activation button.           

  Manual defrost  / Decrease button. 

 

 

  Exit / Stand-by button.

INSTALLATION 

  Insert the controller through a hole measuring 71x29 mm.
  Make sure that electrical connections comply with the paragraph “wiring diagrams”. To reduce the effects of electromagnetic 

disturbance, keep the sensor and signal cables well separate from the power wires. 

  Fix the controller to the panel by means of the suitable clips, by pressingly gently;  if fi tted, check that the rubber gasket 

adheres to the panel perfectly, in order to prevent debris and moisture infi ltration to the back of the instrument.

  Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
  Place the probe T2 on the evaporator where there is the maximum formation of frost. 
  The function of probe T3 is determined by the parameter T3. With 

T3

=DSP the probe measures the temperature to be 

displayed. With 

T3

=CND the probe measures the condenser temperature, it must therefore be placed between the fi ns of the 

condensing unit. With 

T3

=2EU the probe measures the temperature of the second evaporator and it must therefore be placed 

where there is the maximum formation of frost. With 

T3

=NON, the third probe is disabled.

OPERATION

DISPLAY

During normal operation, the display shows either  the temperature measured or one of the following indications: 

DEF

Defrost in progress 

HP

Condenser high pressure alarm 

REC

Recovery after defrost

HI

Room high temperature alarm

OFF

Controller in stand-by 

LO

Room low temperature alarm

CL

Condenser clean warning 

E1

Probe T1 failure

DO

Door open alarm

E2

Probe T2 failure

HC

Condenser high temperature alarm

E3

Probe T3 failure

INFO MENU

The information available in this menu is:

T1

Instant probe 1 temperature

TLO

Minimum probe 1 temperature recorded

T2

Instant probe 2 temperature

CND

 Compressor working weeks

T3

Instant probe 3 temperature

LOC

 Keypad state lock

THI

 Maximum probe 1 temperature recorded 

   

Access to menu and information displayed. 

  Press and immediately release button  .
  With button 

 

or 

 

select the data to be displayed.

  Press button 

 

to display value.

  To exit from the menu, press button 

X

 

or  wait for 10 seconds.

Reset of THI, TLO, CND recordings

  With button 

 

or 

 

select the data to be reset.

  Display the value with button  .
  While keeping button 

 

pressed, use button 

X

 

.

SETPOINT (display and modifi cation of desired temperature value) 

  press button 

 

for at least half second, to display the setpoint value.

  By keeping button 

 

pressed, use button 

 

or 

 

to set the desired value (adjustment is within the minimum 

SPL

 and the 

maximum 

SPH

 limit).

  When button 

 

is released, the new value is stored.

STAND-BY

Button 

, when pressed for 3 seconds, allows the controller to be put on a standby or output control to be resumed (with  

SB

=YES only). 

KEYPAD LOCK

The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controllers is operating 
in a public place. In the INFO menu, set parameter 

LOC

=YES to inhibit all functions of the buttons. To resume normal operation 

of keypad, adjust setting so that 

LOC

=NO.

SELECTION OF SECOND PARAMETER GROUP

It’s possible to select control parameters between two different pre-programmed groups, in order for the fundamental control 
parameters to be adapted quickly to changing needs.  
Changeover from Group 

I

 to Group 

II

 may take place manually by pressing button 

M

 

for 2 seconds (with 

IISM

=MAN), or 

automatically when heavy duty conditions are detected (with 

IISM

=HDD), or when the auxiliary input DI2 is activated (

IISM

=DI2). 

The activation of Group II is signalled by the lighting up of the relevant LED on the controller display. If 

IISM

=NON, switchover 

to group II is inhibited.

DEFROST
Automatic defrost.

 A defrost is started automatically as soon as the time set with parameter 

DFT

 has elapsed. 

  Timed defrost. With 

DFM

=TIM the timer increment is continuous and defrosts take place at regular intervals. For example, 

with 

DFM

=TIM and 

DFT

=06, a defrost will take place every 6 hours.

  Optimised defrost. With 

DFM

=FRO the timer is only increased when the conditions occur for frost to form on the evaporator, 

until the time set with parameter DFT is matched. If the evaporator works at 0°C, defrost frequency depends on the thermal load 
and climatic conditions.  With setpoints much lower than 0°C, defrost frequency mainly depends on the refrigerator operating 
time. 

  Defrost time count backup. At the power-up, if 

DFB

=YES, the defrost timer resumes the time count from where it was left off 

before the power interruption. Vice versa, with 

DFB

=NO, the time count re-starts from 0. In stand-by, the accumulated time count 

is frozen.

Manual or remote defrost start.

 It’s possible to manually start a defrost, by pressing button 

 

for 2 seconds, or defrost may 

be started remotely, if 

DI2

=RDS, through the making of the auxiliary contact DI2.

Defrost type.

 Once defrost has started, Compressor and Defrost outputs are controlled according to parameter 

DTY

. If 

FID

=YES, the evaporator fans are active during defrost.

Defrost termination.

 The actual defrost duration is infl uenced by a series of parameters.

  Time termination: 

T2

=NO and T3 different from 2EU: the evaporator temperature is not monitored and defrost will last as long 

as time 

DTO

.

  Temperature monitoring of one evaporator: 

T2

=YES and T3 different 

from 2EU. In this case, if the sensor T2 measures the temperature 

DLI

 

before the time DTO elapses, defrost will be terminated in advance.

  Temperature monitoring of two evaporators: 

T2

=YES, 

T3

=2EU, 

OAU

=2EU. This function is for the control of two independent 

evaporators and it switches off the individual heating of the evaporator 
which gets to temperature DLI fi rst, waiting for the second evaporator 
to get to that temperature before the time DTO elapses (see fi gure).

Resuming thermostatic cycle.

 When defrost is over, if 

DRN

 is 

greater than 0, all outputs will remain off for DRN minutes, in order for 
the ice to melt completely and the resulting water to drain. Moreover, if 
probe T2 is active (T2=YES), the fans will re-start when the evaporator 
gets to a temperature lower than FDD; Vice versa, if probe T2 is not 
active (

T2

=NO) or after defrost has come to an end, such condition does not occur by end of the time FTO, after FTO minutes 

have elapsed the fans will be switched on anyway.

Caution: if  

DFM

=NON or 

C-H

=HEA all defrost functions are inhibited; if 

DFT

=0, automatic defrost functions are excluded. During 

a high pressure alarm, defrost is suspended. During defrost, high temperature alarm is bypassed.

CONFIGURATION PARAMETERS

  To get access to the parameter confi guration menu, press button 

X

+

 

for 5 seconds.

   With button 

 

or 

 

select the parameter to be modifi ed.

  Press button 

 

to display the value.

  By keeping button 

 

pressed, use button 

 

or 

 

 to set the desired value.

  When button 

 

is released, the newly programmed value is stored and the following parameter is displayed.

  To exit from the setup, press button 

X

 

or wait for 30 seconds.

PAR

RANGE

DESCRIPTION

SCL

1°C;
2°C;

°F

Readout scale.
1°C (only with 

INP

=SN4): measuring range  -50/-9.9 … 19.9/80°C

2°C : measuring range   -50 … 120°C
°F : measuring range   -55 … 240°F

Caution: upon changing the SCL value, it is then absolutely necessary to reconfigure the parameters relevant to the 
absolute and relative temperatures (

SPL

SPH

SP

ATL

ATH

, etc..)

SPL

-50..SPH

Minimum limit for 

SP 

setting

SPH

SPL.120°

Maximum limit for 

SP

 setting

SP

SPL... SPH

Setpoint (value to be maintained in the room).

C-H

REF; HEA

Refrigerating (REF) or Heating (HEA) control mode

HYS

1...10°

OFF/ON thermostat differential

                 Refrigerating control (C-H=REF )                                          Heating control  (C-H=HEA)

CRT

0...30min

Compressor rest time. The output is switched on again after CRT minutes have elapsed since the previous 
switchover. We recommend to set 

CRT

= 03  with 

HYS

<2.0°.

CT1

0...30min

Thermostat output run when probe T1 is faulty. With 

CT1

= 0 the output will always remain OFF.

CT2

0...30min

Thermostat output stop when probe T1 is faulty. With 

CT2

= 0 and 

CT1

>0  the output will always be ON.

Example: 

CT1

= 4, 

CT2

= 6: In case of probe T1 failure, the compressor will cycle 4 minutes ON and 6 minutes OFF.

CSD

0..30min

Compressor stop delay after the door has been opened (active only if 

DS

=YES).

2CD

0...120sec

Auxiliary compressor start delay. If 

OAU

 = 2CU the auxiliary output is switched on  with a delay of 2CD seconds after 

the main compressor has cut-in. Both compressors are turned off at the same time. 

DFM

NON;

TIM;

FRO

Defrost start mode
NON : defrost function is disabled (the following parameter will be FID).
TIM : the defrost time count is increased continously. 
FRO : the defrost time count is only increased when the conditions occur for frost to form on the evaporator 
(optimised time increase). 

DFT

0...99 hours

Time interval among defrosts. When this time has elapsed since the last defrost, a new defrost cycle is started.

DFB

NO/YES

Defrost timer count backup. With

 DFB

=YES, after a power interruption, the timer resumes the count from where it 

was left off with ±30 min. approximation. With 

DFB

=NO, after a power interruption, the defrost timer will re-start 

to count from zero.

DLI

-50...120°

Defrost end temperature.

DTO

1...120min

Maximum defrost duration.

DTY

OFF;
ELE;
GAS

Defrost type
OFF: off cycle defrost (Compressor and Heater OFF).
ELE: electric defrost (Compressor OFF and Heater ON). 
GAS: hot gas defrost (Compressor and Heater ON). 

DRN

0...30min

Pause after defrost (evaporator drain down time).

DDY

0...60min

Display during defrost. If

 DDY

= 0 during defrost the temperature continues to be displayed. If 

DDY

 > 0, during defrost 

the display shows DEF, when defrost is over REC is displayed during DDY minutes.

FID

NO/YES

Fans active during defrost.

FDD

-50...120°

Evaporator fan re-start temperature after defrost.

FTO

0...120min

Maximum evaporator fan stop after defrost.

FTC

NO/YES

Optimised fan control enabling. With 

FTC

 = NO the fans remain on all the time.

                                                                Fig.2   Optimised fan control (FTC=YES)

FT1

0...180sec

Fan stop delay after compressor stop. See Fig. 2

FT2

0...30min

Timed fan stop. With 

FT2

= 0 the fans remain on all the time.

FT3

0...30min

Timed fan run. With 

FT3

= 0, and 

FT2

 > 0, the fans remain off all the time.

ATM

NON;
ABS;

REL

Alarm threshold management.
NON: all temperature alarms are inhibited (the following parameter will be ADO).
ABS: the values programmed in ALA and AHA represent the real alarm thresholds.
REL: the values programmed in ALR and AHR are alarm differentials referred to SP and SP+HY.

         Temperature alarm with relative thresholds,                               Temperature alarm with relative thresholds, 
          refrigerating control (ATM=REL, CH=REF).                                      heating control (ATM=REL, CH=HEA).

ALA

-50... 120°

Low temperature alarm threshold.

AHA

-50... 120°

High temperature alarm threshold.

ALR

-12... 0°

Low temperature alarm differential.

AHR

0... 12°

High temperature alarm differential.

ATI

T1; T2; T3

Probe used for temperature alarm detection.

ATD

0... 120min

Delay before alarm temperature warning.

ADO

0... 30min

Delay before door open alarm warning.

AHM

NON;

ALR;
STP;

Operation in case of high condenser alarm
NON : high condenser alarm inhibited.
ALR : in case of alarm, “HC” flashes in the display and the buzzer is switched on.
STP : in addition to the alarm symbols displayed, the compressor is stopped  and defrosts are suspended.

AHT

-50...120°

Condensation temperature alarm.

ACC

0...52

weeks

Condenser periodic cleaning. When the compressor operation time, expressed in weeks, matches the ACC value 
programmed,  “CL” flashes in the display.

HDS

1...5

Controller sensitivity for the automatic switchover from Group 1 to Group 2 (1=minimum, 5 =maximum)

IISM

NON;

MAN;

HDD;

DI2

Switchover mode to second parameter set
NON: inhibition to use the second parameter group (the following parameter will be SB).
MAN: button 

M

 

switches the two parameter groups over.

HDD: automatic switchover to the second parameter group, when heavy duty conditions are detected.
DI2: switchover to the second parameter group when the auxiliary DI2 input makes.

IISL

-50...IISH

Minimum limit for 

IISP

 setting.

IISH

IISL...120°

Maximum limit for 

IISP 

setting.

IISP

IISL... IISH

Setpoint in mode 2.

IIHY

1...10°

OFF/ON differential in mode 2.

IIFT

NO/YES

Optimised fan control enabling in mode 2.

IIDF

0...99 hours

Defrost timer set to start a defrost in mode 2.

SB

NO/YES

Stand-by button enabling 

.

DS

NO/YES

Door switch input enabling (closed when door is closed).

DI2

NON;

HPS;

IISM;

RDS

DI2 digital input operation
NON : digital input 2 not active.
HPS: when contact opens a condensing unit high pressure alarm occurs. 
IISM : when contact makes the controller will use group 2 parameters.
RDS : when contact makes a defrost is started (remote control).

LSM

NON;

MAN;

DOR

Light control mode
NON : light output not controlled.
MAN : light ouput controlled through button  

M

 

(if 

OAU

=LGT).

DOR : light ouput switched on when door is opened (if 

OAU

=LGT).

OAU

NON;

0-1;

LGT; 
2CU;
2EU; 
AL0;

AL1

AUX output operation
NON : output disabled (always off).
0-1 : the relay contacts follow the on/standby state of controller.
LGT : output enabled for light control.
2CU : output programmed for the control of an auxiliary compressor.
2EU : output enabled for the control of the electrical defrost of a second evaporator.
AL0 : contacts open when an alarm condition occurs.
AL1 : contacts make when an alarm condition occurs.

INP

SN4; ST1

Temperature sensor selection. With 

INP

 = SN4, the probes must be the LAE models SN4..; with 

INP

 = ST1, the probes 

must be the LAE models ST1... 

OS1

-12.5..12.5°C

Probe T1 offset.

T2

NO/YES

Probe T2 enabling (evaporator).

OS2

-12.5..12.5°C

Probe T2 offset.

T3

NON;

DSP;
CND;

2EU

Auxiliary probe T3 operation

NON: probe T3 not fi tted.
DSP: temperature T3 to be displayed.
CND: condenser temperature measurement.
2EU: second evaporator temperature measurement.

OS3

-12.5..12.5°C

Probe 3 offset.

TLD

1...30 min

Delay for minimum temperature (TLO) and maximum temperature (THI) logging.

SIM

0...100

Display slowdown.

ADR

1...255

AD3-5 address for PC communication.

WIRING DIAGRAMS

TECHNICAL DATA

Power supply

AD-3…D 12Vac±10%, 

50/60Hz, 

3W

AD-3...W 

110 - 230Vac±10%, 50/60Hz, 3W

Relay outputs

Compressor  

12(5)A 240Vac

Evap. fans  

7(2)A 240Vac

Defrost 7(2)A 

240Vac

Auxiliary loads 

7(2)A 240Vac

Inputs

NTC 10K

Ω

@25°C,  

LAE part No. SN4...

PTC 1000

Ω

@25°C, 

LAE part No. ST1…

Measurement Range

-50…120°C,  

-55…240°F

Measurement accuracy

<0.5°C within the measurement range

Operating conditions

-10 … +50°C;  

15%...80% r.H.

CE (Reference Norms)

EN60730-1; EN60730-2-9;
EN55022 (Class B);
EN50082-1

Front protection

IP55

VIA PADOVA, 25
31046 ODERZO /TV /ITALY
TEL. +39 - 0422 815320
FAX +39 - 0422 814073
www.lae-electronic.com
E-mail: [email protected]

P

A

R

TNER VENEZIA • 041 5460713 

12(5)A

RS485

T2

T1

Door

Switch

7(2)A 7(2)A

AUX

115...230Vac

12A

7(2)A

AUX

Aux

Switch

DI2

T3

12

...

24Vac

17

18

19

20

21

23

22

24

3

2

4

8

7

6

5

1

AD3-5C24W-BG

AD3-5

INSTRUCTIONS FOR USE

ISTRUZIONI D’USO

ON

OFF

DRN

ON

OFF

ON

OFF

START

DLI

EVP1

DLI

EVP2

DEF2

DEF1

AD3-5

INSTRUCTIONS FOR USE

ISTRUZIONI D’USO

EN

IT

0LAD3001ENIT

12(5)A

RS485

T2

T1

Door

Switch

7(2)A 7(2)A

AUX

115...230Vac

12A

7(2)A

AUX

Aux

Switch

DI2

T3

17

18

19

20

21

23

22

24

3

2

4

8

7

6

5

1

AD3-5C14W-BG

Отзывы: