We thank you for choosing an LAE controller. Before proceeding to the installation of the CDC 12, please  read this instructions sheet carefully;
only in this way you will obtain maximum performances and safety.

1. INSTALLATION

1.1

The CDC122T1R2 and CDC122T1R3B have got a size of 77x35x77 mm (WxHxD), while the CDC122T1R3G and CDC122T1R3J have got a

size of 77x35x97 mm (WxHxD). The instrument is inserted into the panel through a 71x29 mm hole and secured via the suitable brackets exerting
corret strength. The rubber gasket must be placed between the panel and the instrument front, so please make sure that there are no gaps allowing
liquid infiltrations.

1.2

The unit works with an ambient temperature between -10°...+50°C and 15%...80% relative Humidity. To reduce the effects of electro-magnetic

interference, place the cables carrying signals (probes and serial connections etc.) and the controller as away as possible from power lines.

1.3

Probes, power supply, inputs and outputs must be wired strictly following the diagram indicated on the enclosure, where the maximum loads also

appear.  For supply voltage,  the suitable transformer (mod. TRxxx) must be used. 

1.4

Probe T1 measures air temperature and is used for the thermostat function; probe T2 measures the evaporator temperature and must be secured

to it on the place where the maximum frost growth occurs. 

1.5

The remote defrost start input needs an external activation voltage between 10 … 16Vac, 10mA. When this voltage is applied to the input,

defrost is started. 

1.6

The RS485 serial communication port or, if fitted, the TTL ouput for the remote display is available on the DATA connector. PIN 1 is identified by

a dot.

Caution: 

• If the relays switch a large load frequently, we suggest you contact us to obtain information about the relay contact life.
• Where delicate or valuable products have to be maintained under strict conditions, please use a different controller for limit and alarm functions.

2. CONTROL PARAMETERS

The adaptation of the CDC 12 to the system that it controls is achieved through the parameters in the SETUP. Access to the parameters is obtained
by pressing  + +

for 4 seconds. Scroll through the parameters by pressing 

or 

until you select the desired one. Check its value by means

of 

and change it via  +

or  . Exit from the SETUP occurs after 10 seconds of no key activation. To help yourself during programming, refer

to the following table.

SPL

minimum programmable temperature

[-50 ... +150°]

SPh

maximum programmable temperature

[SPL ... +150°]

hyS

thermostat on switching hysteresis

[+01 ... +20°K]

coF

cooler minimum off time

[00 ... 10 minutes]

con

cooler minimum on time

[00 ... 10 minutes]

cdc

cooler safety run in case of probe failure

[00=off ... 10(0)%=always on]

crS

cooler re-start delay after power failure

[00 ... 120 seconds]

drE

hours between two defrosts

[01 … 99 hours]

dLi

defrost limit temperature

[+01 ... +70°]

dto

defrost time-out

[01 ... 120 minutes]

drP

drain time

[00 ... 10 minutes]

diS

display control during defrost

[-01=”dEF”; 00=”T3”; 1... 30 minutes=timed “dEF”]

dty

defrost type

[FAn=off cycle; ELE=electrical; GAS=hot gas]

doP

time count for defrost optimisation

[con=continuous; Acc=frost accumulation]

Fct

evaporator fan control

[-01=always on; 00=on/off with cooler; 1... 10 minutes=delayed off]

FrS

fan re-start after defrost

[-50 ... +150°]

Fid

ventilation during defrost

[00=off; 01=T2<FrS; 02=always on]

Alo

low alarm threshold

[-50 ... +150°]

Ahi

high alarm threshold

[ALo ... +150°]

AdL

temperature alarm delay

[-01=excluded; 00... 120 minutes]

Ain

alarm temperature selection

[temperature 1, 2, 3]

oS1

thermostat probe offset 

[-20 ... +20°K]

oS2

evaporator probe offset 

[-20 ... +20°K]

oS3

displayed probe offset 

[-20 ... +20°K]

SiM

slowdown of displayed temperature

[00 ... 200]

Adr

peripheral number

[00 ... 255]

INSTRUCTIONS FOR INSTALLATION AND USE.

CDC122T1R2

CDC122T1R3B

CDC122T1R3G

CDC122T1R3J

Содержание CDC122T1R2

Страница 1: ... about the relay contact life Where delicate or valuable products have to be maintained under strict conditions please use a different controller for limit and alarm functions 2 CONTROL PARAMETERS The adaptation of the CDC 12 to the system that it controls is achieved through the parameters in the SETUP Access to the parameters is obtained by pressing for 4 seconds Scroll through the parameters by...

Страница 2: ...e cooler run isn t controlled according to setpoint but determined by cdc which represents the cooler duty cycle i e on time 10 minute cycle For ex 04 4 minutes on time 6 minutes off time The cdc value has to be set taking into consideration the normal cooler duty cycle If you wish to switch off the outputs you can put the CDC12 on a standby via the serial communication or manually by pressing dur...

Страница 3: ...s case the condition must be acknowledged by pressing any key The alarm output contact is also closed when the instrument is powerless During defrost and dripping the high alarm monitoring is inhibited 9 PROBE RE CALIBRATION Should it be necessary to recalibrate the unit for instance in consequence of probe replacement then act in the following way get an accurate reference thermometer or calibrat...

Страница 4: ...150 20 3 hyS 01 20 02 4 coF 00 10 00 5 con 00 10 00 6 cdc 00 10 05 7 crS 00 120 00 8 drE 01 99 06 9 dLi 01 70 10 10 dto 01 120 30 11 drP 00 10 03 12 diS 01 30 10 13 dty FAn ELE GAS ELE 14 doP con Acc con 15 Fct 01 00 10 01 16 FrS 50 150 10 17 Fid 00 01 02 00 18 Alo 50 150 32 19 Ahi Alo 150 22 20 AdL 01 00 120 10 21 Ain 1 2 3 01 22 oS1 20 20 00 23 oS2 20 20 00 24 oS3 20 20 00 25 SiM 00 200 00 26 Ad...

Отзывы: