10
Problems solution
Defect Cause/Remedy
Boiler has a lower output as it was
a new one
- Clean up air inlet system
- Clean up blades of fan
- Use dry wood
Afterclosing the flue shutter the boiler
burns for a while and then smoke
- Insufficient quantity of primary air
- Clean up the primary air inlet
- Check the shutter opening behind the fan
In combustion chamber arebigger
pieces of unburnt logs.
- Nozzle opening Increased
- Change the nozzle
- Set the air inlet into a closed position and turn
3 turns back from the closed position.
Smoke escape over the closed door.
- set up the door, check the tightness of the
door
- Change the sealing cord of the door
Flue shutter does not open.
- Flue shutter is sticked with tar
- Increase the boiler temperature
- Use the dry wood
- Open flue shutter manually
After opening the upper door and
chimney shutter the boiler room is full
of smoke
- Low flue draught
- The flue diameter should be bigger than the
diameter of boiler flue connection. It is
recommended 200mm.
- Chimney heigth should be minimum 8m
- Assembly suction fan
- Increase the chimney heigth
Boiler does not seal
- Contact service worker or dealer
Failure of electronic regulation
- Contact service worker or dealer