3.1  Mechanical Installation 

Before starting operation, check the process connection carefully for leaks under pressure. 

  

Use gaskets, if required, that are suitable for the process connection and resistant to the 
media. 

  

The  process  connection  determines  the  permissible  process  pressure.  Operating  the de-
vice beyond its nominal pressure limit, e.g. clamp-connections, requires specially designed 
and approved mounting elements. 

  

3.2  Electrical Connection 

Complete the mechanical installation before you connect the device electrically. 

Set up all electrical connections while the voltage supply is switched off. 

  

 

 

 

 

Circular connector M12 

Cable gland 

3-wire 

4-wire 

Transmitter 

3-wire  

 

 

 

 

 

Figure 1:  Variants of electrical connection 

  

Operation 

During operation, take care that the device remains within its intended pressure and tem-
perature ranges. No other monitoring is necessary. 

  

Permissible media temperature:  

-

50…200 °C 

  

Permissible ambient temperature:  

-

40…85 °C 

When  supplied  with  a  transmitter,  the  permissible  ambient  temperature  is  reduced  to  -
20…80 °C. 

  

Restricted  ambient  conditions  may  apply  in  explosion  protected  environments  (see 
XA_001). 

  

4.1  Maintenance / Service 

When  properly  installed  in  accordance  with  applicable  specifications,  this  device  is 
maintenance-free. However, we recommend an annual recalibration of the device. 

  

In the event of a device malfunction, you can only replace the measuring insert respective-
ly the head transmitter. 

  