SET/V
D27093_e
Operation and installation manual
We reserve the right to any changes.
Copyright © 2010, Labkotec Oy
2(4)
SYMBOLS
To be considered in installations in
potentially explosive atmospheres.
Warning/Attention
1. GENERAL
SET/V is a level switch sensor that is to be
connected to analogical and digital SET control
units of Labkotec. Operating principle of the sensor
is based on the measurement of the vibration of
the sensor.
Sensor is suitable to be used as a high level alarm
for liquid tanks, for example. Typical applications of
SET/V sensor include oil and grease separators.
The SET/V has been certified according to the
ATEX Directive (94/9/EC) in equipment category 1
and it can be installed in potentially explosive
atmospheres in zoned areas 0, 1, and 2.
Figure 1. Dimensional drawing of the SET/V
sensor
Figure 2. Application: high level alarm for an oil
separator
2. TECHNICAL DATA
Control unit
LevelSET S and SET control
units by Labkotec Oy
Signal
Operating voltage
Digital and
analogical 7mA/13mA
8V…16V (DC)
Cable
Shielded oil-proof cable 2 x 0.75
mm
2
. Standard length 5 m. Other
lengths optional. The max. length
of the fixed cable is 15 m. Can be
extended with a shielded cable.
The recommended maximum
cable loop resistance is 75
Ω
.
Materials
PA, PVC, aluminum, NBR
Temperature
range
Operation: 0…+60°C
Safety: -30…+60°C
EMC
Emissions
EN 61000-6-3
Immunity EN
61000-6-2
IP-classification
IP68
Ex-classification
II 1 G Ex ia IIB T5 Ga
VTT 09 ATEX 025X
IECEx VTT 10.0006X
Ui = 16 V
Pi = 400 mW
Ii = 80 mA
Ci = 3500 pF
Li = 85
μ
H
Operating
principle
Vibration
Manufacturing
year:
Please see the
serial number on
the type plate.
xxx x xxxxx xx YY x
where YY = manufacturing year
(e.g. 10 = 2010)
The sensor may be installed in potentially
explosive atmospheres of zones 0, 1, and 2 with
the following special conditions (X):
– The ambient temperature is –30…+60°C.
– The risk of electrostatic charge must be observed!
Standards to be considered in the installation:
IEC/EN 60079-25 Intrinsically-safe electrical systems
"i", and/or IEC/EN 60079-14 Electrical installations in
hazardous areas. If the cabling is voltage-tested, the
sensor must be detached from the system.