Labkotec SET-2000 Oil/Sludge Скачать руководство пользователя страница 7

SET-2000 (110 VAC) 

 

 

 

                                 D15349AE-1 

Installation and Operating Instructions 

 

Copyright © 2019 Labkotec Oy 

7/15 

We reserve the right for changes without notice 

OPERATION AND SETTINGS 

The SET-2000 control unit is initialized at the factory as follows. See a 
more detailed description in chapter 

3.1 Operation.

 

Channel 1 

Alarm takes place when the level hits the sensor (high level alarm) 

Channel 2 

Alarm takes place when the level leaves the sensor (low level alarm) 

Relays 1 ja 2 

Relays de-

energize in respective channels’ alarm and fault situations (so-

called fail-safe operation).  

Operational delay is set to 5 seconds. The trigger level is normally at 
the middle of the sensor

’s sensing element. 

3.1 

Operation 

The  operation  of  a  factory-initialized  SET-2000  is  described  in  this 
chapter. 

If  the  operation  is  not  as  described  here,  check  the  settings  and 
operation  (chapter  3.2)  or  contact  a  representative  of  the 
manufacturer. 

Normal mode 

– no alarms 

The level in the tank is between the two sensors. 

 

 

 

Mains LED indicator is on. 

 

Other LED indicators are off. 

 

Relays 1 and 2 are energized. 

 

 

High level alarm 

The level has hit the high level sensor (sensor in the medium). 

 

 

 

Mains LED indicator is on. 

 

Sensor 1 Alarm LED indicator is on. 

 

Buzzer on after 5 sec delay. 

 

Relay 1 de-energizes after 5 sec delay. 

 

Relay 2 remains energized. 

 

 

Low level alarm 

The level is below low level sensor (sensor in the air). 

 

 

 

Mains LED indicator is on. 

 

Sensor 2 Alarm LED indicator is on. 

 

Buzzer on after 5 sec delay. 

 

Relay 1 remains energized. 

 

Relay 2 de-energizes after 5 sec delay. 

 

 

 

After removal of an alarm, the respective alarm LED indicators and 
buzzer will be off and respective relay will be energized after 5 sec delay. 

 

 

Fault alarm 

A broken sensor, sensor cable break or short circuit, i.e. too low or too 
high sensor signal current. 

 

 

 

Mains LED indicator is on. 

 

Sensor cable Fault LED indicator is on after 5 sec delay. 

 

The relay of respective channel de-energizes after 5 sec delay. 

 

Buzzer is on after 5 sec delay. 

 

 

Reset of an alarm 

When pressing the Reset push button. 

 

 

 

Buzzer will go off. 

 

Relays will not change their status before the actual alarm or fault is off. 

 

TEST FUNCTION 

Test function provides an artificial alarm, which can be used to test the 
function  of  the  SET-2000  level  switch  and  the  function  of  other 
equipment, which is connected to SET-2000 via its relays. 

Содержание SET-2000 Oil/Sludge

Страница 1: ...8 29 006 260 Fax 358 29 006 1260 13 8 2019 Internet www labkotec fi D15349AE 1 1 15 Copyright 2019 Labkotec Oy We reserve the right for changes without notice SET 2000 110 VAC supply voltage Level swi...

Страница 2: ...in the same area and zone 5 2 1 2 Level sensors in different areas and zones 6 3 OPERATION AND SETTINGS 7 3 1 Operation 7 3 2 Altering settings 8 4 TROUBLE SHOOTING 10 5 REPAIR AND SERVICE 11 6 SAFET...

Страница 3: ...sh buttons and interfaces of the device are described in figure 1 Figure 1 SET 2000 level switch features SET 2000 can be used as a controller of level sensors located in potentially explosive atmosph...

Страница 4: ...r The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be installed back after executing cable connections...

Страница 5: ...the ground terminal Other components of the system that need to be grounded can also be connected to the same ground terminal The wire used for equipotential ground must be min 2 5 mm mechanically pr...

Страница 6: ...de with separate cables Also the equipotential grounds can be separate Figure 5 Cabling with a cable junction box when sensors are located in separate areas and zones Junction boxes of types LJB2 and...

Страница 7: ...nergized High level alarm The level has hit the high level sensor sensor in the medium Mains LED indicator is on Sensor 1 Alarm LED indicator is on Buzzer on after 5 sec delay Relay 1 de energizes aft...

Страница 8: ...f it has been reset earlier it will return to be on When the Test push button is released The device returns without delay to the preceding status Fault alarm on When pressing Test push button The dev...

Страница 9: ...iquid level is above the sensor s trigger level high level mode OPERATIONAL DELAY SETTING DELAY Switches S2 and S4 are used to set the operational delay of the device When the switch is in low positio...

Страница 10: ...8 V 3 If the voltages are correct measure the sensor current one channel at a time Do as follows 3 1 Disconnect sensor s wire from sensor connector poles 11 and 13 3 2 Measure short circuit current b...

Страница 11: ...eres the national requirements and relevant standards as IEC EN 60079 25 and or IEC EN 60079 14 must be taken into account If electrostatic discharges can cause hazards in the operating environment th...

Страница 12: ...y outputs Two potential free relay outputs 250 V 5 A 100 VA Operational delay 5 sec or 30 sec Relays de energize at trigger point Operation mode selectable for increasing or decreasing level Electrica...

Страница 13: ...1 9 F 1 6 F 0 15 mH 0 5 mH 1 0 mH 2 0 mH 5 0 mH Lo Ro 116 5 H IIC and 466 H IIB Table 2 Electrical parameters Maximum length of the sensor cable is determined by the resistance max 75 and other electr...

Страница 14: ......

Страница 15: ......

Отзывы: