Labcom 221 GPS

Data transfer unit

 

 

 

Installation and User Guide

EN

DOC002104-EN-2

5/19/2023

Содержание Labcom 221 GPS

Страница 1: ...Labcom 221 GPS Data transfer unit Installation and User Guide EN DOC002104 EN 2 5 19 2023 ...

Страница 2: ...stallation and commissioning 5 Connections 5 1 Passive mA sensor 5 2 Active mA sensor 5 3 Switch output 5 4 Switch inputs 5 5 Example connections 5 5 1 Connection idOil LIQ 5 5 2 Connection idOil SLU 5 5 3 Connection GA SG1 5 5 4 Connection SGE25 5 5 5 Connection 1 wire temperature sensor 5 5 6 Connection DMU 08 and L64 5 5 7 Connection Nivusonic CO 100 S 6 External voltage supply 6 1 Under Voltag...

Страница 3: ...arts of this document All of our products have been designed and manufactured with due consideration to the essential European standards statutes and regulations Labkotec Oy has a certified ISO 9001 quality management system and ISO 14001 environmental management system 1 2 Limitation of liability Labkotec Oy reserves the right to make changes to this user guide Labkotec Oy cannot be held liable f...

Страница 4: ...tenna is always internal and there is no support for an external antenna A more specific description of the product s operation installation and use is provided later in this guide The device must be used in accordance with the instructions provided in this document Other use is counter to the product s purpose of use Labkotec cannot be held liable for any damage caused by using the device in viol...

Страница 5: ...rnal antenna connector 2 SIM card slot 3 Device serial number device number also on the device cover 4 Battery connector 5 Additional card 6 TEST button 7 External antenna connector option 8 Connection wire lead throughs Installation and User Guide Labcom 221 GPS 5 14 DOC002104 EN 2 ...

Страница 6: ...orrectly and tightened firmly to the terminal strips If installed the antenna wire has been tightened properly to the antenna connector in the housing If installed the internal antenna wire installed in the device has stayed connected All lead throughs have been tightened to keep moisture out Once all of the above are in order the battery can be connected to the circuit board with the wire provide...

Страница 7: ...utput Vboost Out I O2 and the circuit s grounding conductor is connected to the device s analogue input 4 20 mA I O9 Figure 3 Example connection 5 2 Active mA sensor The voltage to the measurement circuit of the active measurement transmitter sensor is supplied by the transmitter sensor itself The measurement circuit s plus conductor is connected to the Labcom 221 GPS device s analogue input 4 20 ...

Страница 8: ...range is 0 40VDC and the maximum current is 2A For larger loads a separate auxiliary relay must be used which is controlled by the Labcom 221 GPS 5 4 Switch inputs 1 brown I O7 2 yellow DIG1 3 black GND 4 Two separate switches Figure 6 Example connections Installation and User Guide Labcom 221 GPS 8 14 DOC002104 EN 2 ...

Страница 9: ... unit idOil LIQ sensor must not be installed in potentially explosive atmospheres 5 5 2 Connection idOil SLU 1 black I O2 2 black I O9 Figure 8 Labcom 221 GPS idOil SLU sensor Connection The Labcom 221 GPS data transfer unit idOil LIQ sensor must not be installed in potentially explosive atmospheres Installation and User Guide Labcom 221 GPS 9 14 DOC002104 EN 2 ...

Страница 10: ...5 5 4 Connection SGE25 1 red I O2 2 black I O9 Figure 10 Labcom 221 GPS SGE25 sensor Connection 5 5 5 Connection 1 wire temperature sensor 1 red I O5 2 yellow I O8 3 black GND Figure 11 Labcom 221 GPS 1 wire temperature sensor Connection Installation and User Guide Labcom 221 GPS 10 14 DOC002104 EN 2 ...

Страница 11: ...ion e g LCJ1 1 with DMU 08 sensor wires and a separate extension wire to the Labcom 221 GPS s terminal strips not included in the delivery 5 5 7 Connection Nivusonic CO 100 S Nivusonic measurement circuit connection Nivusonic relay tip connection pos pulse Nivusonic optical tip connection neg pulse Figure 13 Labcom 221 GPS Nivusonic CO 100 S Connection Installation and User Guide Labcom 221 GPS 11...

Страница 12: ... the safe activation of the device The lockout mode protects the device and any other devices and sensors connected to it When an external voltage source is connected to the device once it has switched to the UVLO mode the device checks the stability of the voltage source before exiting the lockout mode If the voltage source is found to be stable the device exits the lockout mode If the voltage so...

Страница 13: ...n on the right side of the circuit board if the device is in the vertical position for three 3 seconds This forces the device to contact the server The device is connected to the server but the measurement accrual data is not updated to the server Make sure that the sensor transmitter is in order Check that the connections and conductors are tightened to the terminal strip The device is connected ...

Страница 14: ...rnal external GPS antenna internal Data transfer LTE M NB IoT Encryption AES 256 and HTTPS Positioning GPS Measurement inputs 1 pc 4 20 mA 10 µA 1 pc 0 30 V 1 mV Digital inputs 2 pcs 0 40 VDC alarm and counter function for inputs Switch outputs 1 pc digital output max 2 A 42 VDC Other connections SDI12 1 wire and i2c bus Approvals Health and Safety IEC 62368 1 EN 62368 1 EN 62311 EMC EN 301 489 1 ...