Figure 43. Software uploaded to the control unit

 Press the Updatebutton.

The software update begins and the message in the figure below is shown in the display.
The various phases of the software update are presented in the control unit display.

Figure 44. Software update started

Once the programming has been completed, the control unit reboots.

The WLAN connection to the device is lost during a software update.

 Establish the WLAN connection again according to the instructions in the Commissioning

through the browser-based interface section.

7.3.3.6. Restoring factory settings

In the Factory settings menu you can restore the control unit's original factory settings.

The  factory  settings  of  the  idOil  device  are  described  in  the  section
Commissioning
Restoring the factory settings clears the alarm and maintenance log. The
sensors connected to the control unit must also be identified again.

You can restore the factory settings as follows:

 Check the Restore  factory  settings  box  and  press  the  Restore settings  button  (see  the

next figure).

Installation and Operating Instructions | idOil-D30

39/51

DOC001602-EN-4

Содержание idOil-D30

Страница 1: ...idOil D30 Oil Separator Alarm Device Installation and Operating Instructions EN DOC001602 EN 4 8 27 2018...

Страница 2: ...udge sensor 4 Installation 4 1 Installing the control unit 4 2 Sensor installation 4 2 1 Installing the idOil LIQ high liquid level sensor 4 2 2 Installing the idOil OIL sensor 4 2 3 Installing the id...

Страница 3: ...7 3 3 6 Restoring factory settings 7 3 3 7 WLAN settings 8 Maintenance 8 1 Functional test 8 1 1 Test function 8 1 2 Functional test with sensors 8 2 Maintenance measures 8 3 Troubleshooting 9 Techni...

Страница 4: ...n issue that requires special attention during installation and when using the device in an explosive atmosphere Informative markings and symbols This marking highlights essential information This mar...

Страница 5: ...pose of use Labkotec cannot be held liable for any damage caused by using the device in violation of its purpose of use 2 3 Transport and storage Check the packaging and its content for any possible d...

Страница 6: ...fe electrical systems i and or IEC EN 60079 14 Explosive atmospheres Electrical installations design selection and erection must all be followed If it is possible that static electricity can cause haz...

Страница 7: ...e sensor 1 Control unit idOil D30 2 Cable connector LCJ1 3 3 High liquid level sensor idOil LIQ 4 Oil sensor idOil OIL 5 Sludge sensor idOil SLU A Air B Oil C Water D Sludge Figure 1 System descriptio...

Страница 8: ...dge sensor to detect the thickness of the sludge layer Accessories Type name Description LCJ1 1 Cable connector for one sensor LCJ1 2 Cable connector for two sensors LCJ1 3 Cable connector for three s...

Страница 9: ...e 3 High liquid level sensor idOil LIQ structure and dimensions mm 3 3 3 Dimensions of the idOil OIL oil sensor A Measuring electrode B Reference electrode S Alarm switching point Figure 4 Oil sensor...

Страница 10: ...4 Dimensions idOil SLU sludge sensor T Sensor gap S Alarm trigger point Figure 5 Sludge sensor idOil SLU structure and dimensions mm Installation and Operating Instructions idOil D30 10 51 DOC001602 E...

Страница 11: ...th of the sensor in the instructions of the separator in question For example sensors can be installed suspended from their cable see next figure Leave a sufficient length of the sensor or extension c...

Страница 12: ...nstallation depth depends on the following separator type separator shape volume and height of the separator s oil compartment The sensor must always be immersed in liquid The alarm is activated when...

Страница 13: ...arm is activated when the sludge layer reaches the alarm switching point S which is located inside the sensor gap T The sensor activates the alarm when it is in contact with air For this reason the se...

Страница 14: ...s de energised The legends for the connection diagrams can be found in the section following the diagrams 5 1 Connection diagrams 5 1 1 Connection with a single sensor cable connector Figure 12 Connec...

Страница 15: ...5 1 2 Connection with a two sensor cable connector Figure 13 Connection with a two sensor cable connector Installation and Operating Instructions idOil D30 15 51 DOC001602 EN 4...

Страница 16: ...clude a mains switch see Section General safety instructions 1 L phase connector 2 N neutral connector 3 PE protective earth connector The supply cable must feature copper wires 3 x 1 5 2 5 mm2 L N PE...

Страница 17: ...alarm situation 21 Contact that closes in an alarm situation RELAY 2 22 Relay common contact 23 Contact that opens in an alarm situation 24 Contact that closes in an alarm situation The maximum values...

Страница 18: ...accordance with the instructions in the previous paragraphs Connect power to the control unit A message is shown in the control unit display NO SENSORS Figure 16 Initial start up Briefly press the se...

Страница 19: ...connections After the check press the sensor identification button again The control unit will look for the sensors for approx 2 minutes unless it has already found three sensors The sensor identific...

Страница 20: ...t establish a local WLAN connection between the idOil control unit and a terminal device such as a smartphone PC or tablet More details on using the browser based interface is provided in the section...

Страница 21: ...erminal device and the idOil control unit The WLAN network will remain active for 10 minutes after terminal devices are no longer connected to it The following sections detail the measures required in...

Страница 22: ...34 in the password field and press the Log in button If no sensors have been identified before the view shown below is displayed Figure 24 Sensor identification no sensors found Press the Detect senso...

Страница 23: ...onducted the check press the Detect sensorsbutton again The control unit will look for the sensors for approx 2 minutes unless it has already found three sensors After the search the device shows the...

Страница 24: ...have been identified and individual descriptions have been provided for them Press the home screen button in the upper left corner The idOil separator alarm system is now operational at factory settin...

Страница 25: ...system Figure 27 Features of the idOil control unit 7 1 Local display and alarms Local display The four row local display in the front panel presents information on system status possible alarms and f...

Страница 26: ...its and breaks In a maintenance alarm the month counter has reached the limit value 1 3 6 or 12 months This function is used as a factory setting 7 2 Resetting an alarm An alarm can be reset by pressi...

Страница 27: ...You can also access the home screen by pressing the icon in the upper left corner Figure 28 Home screen The items listed in the following table are shown in the home screen The menus are described in...

Страница 28: ...rd The right to configure control unit settings in the Settings menu Status view The status of the sensors connected to the device is shown under the Status view heading Green means no alarm Red means...

Страница 29: ...Test alarm reset button has been pressed for 3 s Note Alarms caused during maintenance are recorded in the inspection log Power off on start and stop time of a power outage The buttons at the bottom o...

Страница 30: ...Press the Start inspection button to activate the inspection form In the Inspection notes field enter the inspection measures conducted and in the Inspector name field enter your name End the inspect...

Страница 31: ...can no longer be edited Press the Savebutton after any possible changes The buttons at the bottom of the inspection log perform the following functions Load more items Shows prior inspection measures...

Страница 32: ...e supported languages in the Language menu Select the desired language and press the Selectbutton This will change the language of the browser interface and local display to the selected language Inst...

Страница 33: ...tion when the first WLAN connection to the control unit is established Figure 34 Date and time 7 3 3 Settings menu The functions in the Settings menu can be used to change the control unit settings Th...

Страница 34: ...le The name is shown in the home screen and the control unit display The display shows the first 16 characters Contact name The name of the contact person for the above company for example The name is...

Страница 35: ...f never activates the inspection period counter which will activate the inspection alarm after the selected interval The time of the maintenance is shown in the home screen year month day and the cont...

Страница 36: ...conds minutes or hours for the setting Alarm reset button Off On If Off is selected the alarm cannot be reset by pressing the reset button in the front panel of the control unit i e the buzzer will ke...

Страница 37: ...Figure 40 Relay settings Installation and Operating Instructions idOil D30 37 51 DOC001602 EN 4...

Страница 38: ...w software packagebutton Select the software file to be uploaded format pkg from the terminal device memory The software will now be uploaded to the control unit The uploading process may take several...

Страница 39: ...g to the instructions in the Commissioning through the browser based interface section 7 3 3 6 Restoring factory settings In the Factory settings menu you can restore the control unit s original facto...

Страница 40: ...Figure 45 Restoring factory settings Confirm the restoration of the factory settings by pressing the Continue button Installation and Operating Instructions idOil D30 40 51 DOC001602 EN 4...

Страница 41: ...AN connection Configure the system settings and perform sensor identification 7 3 3 7 WLAN settings If the WLAN connection is poor several devices may be using the same WLAN channel You can change the...

Страница 42: ...o Menu Inspection and click the button Start inspection Perform the functional test by pressing the test button and with sensors see following paragraphs Record the desired information in the text fie...

Страница 43: ...n log 8 3 Troubleshooting PROBLEM The display is dark Explanation The voltage received by the device is too low or the fuse has blown Action 1 First check that the voltage has not been cut by the main...

Страница 44: ...nce instructions for explosive atmospheres The measuring device must be Exi classified if the sensor is in an explosive area If problems occur contact Labkotec Oy s service department Installation and...

Страница 45: ...annot be replaced The device does not have a mains switch Power consumption Max 12 VA Sensors Digital Labkotec idOil sensors Relay outputs 5 A 250 V AC 30 V DC 100 VA Potential free changeover contact...

Страница 46: ...Oil LIQ Operating principle Vibration Enclosure Enclosure class IP 68 Materials PVC aluminium PA CR Viton Weight 300 g incl 5 m cable Temparature Operation 0 C 60 C Environment 30 C 60 C Supply voltag...

Страница 47: ...x A VTT 17 ATEX 004X IECEx VTT 17 0002X II 1 G Ex ia IIA T5 Ga Ta 39 C 60 C Ui 16 V Ii 80 mA Po 400 mW Ci 5 2 nF Li 1 6 mH Manufacturing year Please see the serial number on the type plate xxxxxxx x x...

Страница 48: ...ppendix A VTT 17 ATEX 006X IECEx VTT 17 0004X II 1 G Ex and IIB T5 Ga Ta 25 C 60 C Ui 16 V Ii 80 mA Po 400 mW Ci 4 0 nF Li 1 6 mH Manufacturing year Please see the serial number on the type plate xxxx...

Страница 49: ...10 Appendices 10 1 APPENDIX A System digram Installation and Operating Instructions idOil D30 49 51 DOC001602 EN 4...

Страница 50: ...Installation and Operating Instructions idOil D30 50 51 DOC001602 EN 4...

Страница 51: ...Installation and Operating Instructions idOil D30 51 51 DOC001602 EN 4...

Отзывы: