6.
Commissioning
6.1. Sensor identification
Ensure that the sensors have been installed and connected in the control unit in
accordance with the instructions in the previous paragraphs.
DANGER OF ELECTRICAL SHOCK! Please observe the safety
instructions below!
Open the cover of the control unit and
ensure that the protection plate is in place!
Connect power to the control unit.
The voltage supply and fault indicator lights
(see Section Operation) are lit in green.
The sensor indicator lights are off.
Press the sensor identification button
briefly (1).
Figure 15. Sensor identification button.
The sensor identification function is initiated and the fault indicator light flashes green.
Once a sensor has been identified, the indicator light of the sensor in question becomes
green.
When all connected sensors have been identified, the lights of the connected sensors are
green and the fault indicator light stops flashing.
Close the cover of the enclosure.
The separator alarm system is now operational.
If the control unit does not identify all connected sensors.
Check the sensor connections.
After the check, press the sensor identification button again.
The control unit will look for the sensors for approx. 2 minutes, unless it
has already found three sensors.
The sensor identification can be stopped by pressing the sensor
identification button for 5 seconds.
Installation and Operating Instructions | idOil-20
18/34
DOC001600-EN-5
Содержание idOil-20
Страница 29: ...Installation and Operating Instructions idOil 20 29 34 DOC001600 EN 5...
Страница 30: ...Installation and Operating Instructions idOil 20 30 34 DOC001600 EN 5...
Страница 32: ...Installation and Operating Instructions idOil 20 32 34 DOC001600 EN 5...
Страница 33: ...Installation and Operating Instructions idOil 20 33 34 DOC001600 EN 5...
Страница 34: ...Installation and Operating Instructions idOil 20 34 34 DOC001600 EN 5...