38

F14

1

Function enabled 

if F12 = ON

OFF

Tests on opening safety sensor E.O. disabled; for sensors which are not pre-arranged for 

monitoring

S

ON

Test on opening safety sensors E.O. enabled; for sensors pre-arranged for monitoring by the 

automation (cat.2/pl.c). 

For details, refer to the paragraph "Safety sensors".

F15

1

Function active if 

F13 or 

F14 = ON

OFF

Safety sensors test with LOW logic level. 

For details, refer to the paragraph "Safety sensors".

S

ON

Safety sensors test with HIGH logic level. 

For details, refer to the paragraph "Safety sensors".

F16

OFF*

If  the  work  program  “Night  Lock”  is  selected,  the  door  remains  closed  and  can  only  be 

opened by actuating the OPEN-START inputs, or the Spyco radio control with the radio EN-

RF1 radio receiver.

ON

Selecting  the  work  program  “Night  Lock”,  the  door  opens  and  remains  open  10”  before 

reclosing to allow leaving the building.

F17

OFF*

Disabled function OFF

ON

Disabled function ON Refer to the paragraph “Courtesy operation for disabled” for details on 

the operating mode.

F18

OFF*

Operation with automatic closing

ON

Step-by-step function: an OPEN command opens the door; a second command is required 

to close back the door.

F19

Function enabled 

if F18 = ON

OFF*

In  the  step-by-step  function,  the  door,  when  open,  can  be  closed  only  with  a  closing 

command given by the OPEN-START input or by the Spyco radio control with the EN-RF1 

radio receiver.

ON

In  the  step-by-step  function,  the  door,  when  open,  automatically  closes  if  the  closing 

command is not given within 30 seconds.

F20

OFF*

Standard operation on the internal and external radar inputs.

ON

Operation with separate opening and closing commands. The external radar input controls 

the  opening,  the  internal  radar  input  controls  the  closing,  without  automatic  closing.  The 

OPEN and START inputs operate in standard mode.

F21

1

OFF

OPEN input configuration: normally closed contact.

When a device with N.C. contact is installed.

ON

OPEN input configuration: normally open contact.

When not in use or if a device with N.O. contact is installed.

F22

OFF*

The OPEN input is disabled in the work program “Manual free door”.

ON

The  OPEN  input  is  enabled  also  in  the  work  program  “Manual  free  door”,  to  allow  the 

automatic opening of the door.

F23

OFF*

Pause time with open door before constant automatic closing.

ON

Automatic increase of the pause time with door open if the door cannot close due to the high 

flow of people.

F24

OFF*

The pause time set by the potentiometer P4 is never reset.

ON

The pause time set by the potentiometer P4 is reset to the initial value if, with the door open, 

an opening command is given.

F25

For NB-

SMT/SMTB 

automations only

OFF*

In case of power failure, when mains supply is restored, the door remains in the current 

position.

ON

In  case  of  power  failure,  when  mains  supply  is  restored,  the  door  slowly  goes  to  closed 

position.

F26

OFF*

Interlock function disabled.

ON

Function of interlock between two doors enabled. A door may be opened only if the other one 

is closed. Please refer to the paragraph "Interlock system".

F27

Function enabled 

if F26 = ON

OFF*

In interlock function, door opening is delayed by 0.5” after the opening command. Please 

refer to the paragraph "Interlock system".

ON

In interlock function, door opening is immediate after the opening command. Please refer to 

the paragraph "Interlock system".

Содержание NEPTIS PLUS

Страница 1: ...lation Manual ENG Rel 1 0 04 2021 CD0450EN NEPTIS PLUS Automation for pedestrian automatic swing door EN English TRANSLATION OF THE ORIGINAL INSTRUCTIONS NB SLT NB SLTB NB LET NB LETB NB SMT NB SMTB I...

Страница 2: ...6 7 EXTENSION FOR EXTB Z TAPERED PIN 16 7 PREPARATION AND INSTALLATION OF THE AUTOMATION 17 7 1 TOOLS REQUIRED 17 7 2 AUTOMATION CHECK 17 7 3 AUTOMATION INSTALLATION 18 7 4 CHOICE OF THE SPRING LOAD...

Страница 3: ...RIC LOCK ELECTRIC STRIKE 53 25 2 ELECTROMAGNET 53 26 DUAL LEAF DOOR 54 26 1 DUAL LEAF ELECTRIC SETUP 54 26 2 DUAL LEAF DOOR COMMISSIONING 54 26 3 FUNCTIONAL TESTING 57 26 4 PARTIAL OPENING 57 26 5 CON...

Страница 4: ...be installed in explosive environments or atmospheres or in the presence of flammable gases or fumes Make sure that the characteristics of the electric distribution network are compatible with the tec...

Страница 5: ...emergency battery is required The automation must be installed in indoor environments All models are reversible so in case of power failure it is possible to open the door manually Before starting ins...

Страница 6: ...SHLESS GEARMOTOR 6 MOTION TRANSMISSION SHAFT OUTLET 7 INTERNAL WIRING BETWEEN LCB AND PWB CARDS 8 SPRING PRELOAD LOCKING SCREW 9 PLASTIC PLATE 10 SWITCHING POWER SUPPLY 11 NB BAT MODULE BATTERY CHARGE...

Страница 7: ...out the run The door requires mechanical stops consisting of a mechanical stop in open position and a final stop in closed position The mechanical opening stop is not supplied with the automation In c...

Страница 8: ...ease consider that the gearmotor must be on the hinged side of the door for a correct opening movement direction 5 1 ASSEMBLY OF THE AUTOMATION ON THE TRANSOM FROM THE HINGE SIDE SLIDE PULL ARM BDT2 F...

Страница 9: ...nsider that the gearmotor must be on the hinged side of the door for a correct opening movement direction Usable leaf length and weight Usable leaf length and weight with different fastening dimension...

Страница 10: ...PRING MODELS NB LET LETB SLT SLTB For this application please consider that the gearmotor must be on the hinged side of the door for a correct opening movement direction Automation with battery module...

Страница 11: ...oor position A STANDARD TAPERED PIN Should it be necessary to increase the distance between the automation and the arm dimension X replace the standard tapered pin with the following optional extensio...

Страница 12: ...n opening It is necessary to install a mechanical stop in open door position A STANDARD TAPERED PIN Should it be necessary to increase the distance between the automation and the arm dimension X repla...

Страница 13: ...For this application please consider that the PWB cabling board must be on the hinged side of the door for a correct movement direction when opening It is necessary to install a mechanical stop in ope...

Страница 14: ...f The pin 6 shall be inserted into the sliding guide shoe 6 2 SLIDING ELBOW ARM BSG 150 BSG 250 a Insert the M8 x 70 screw 2 in the tapered pin 1 b Insert the long arm rod 4 into the closed shell 3 c...

Страница 15: ...the pull arm pin shall operate c Insert the striker 5 into the sliding guide and fasten it at the opening limit position with the dowel d Place the cover casing 2 on the sliding guide 1 e Insert the t...

Страница 16: ...tension with the tapered pin and insert the central screw E tighten the two M6 X 65 side screws F insert the extension into the arm and tighten the two M6 X 20 screws G 6 6 EXTB Z TAPERED PIN Use the...

Страница 17: ...type and to the automation installation type carefully refer to the technical drawings in paragraph 5 For NB LET NB LETB NB SLT NB SLTB automations only do not remove the spring preload locking screw...

Страница 18: ...t with the leaf completely closed to obtain a high re closing force maximum spring load 7 5 INSERTION OF THE ARM TAPERED PIN Make sure that the plastic plate is inserted in the mechanical body of the...

Страница 19: ...ocked Removing the tapered pin s setscrew can cause the pulleys and gears of the automation to move if the re closure spring has not been locked in advance Move your fingers or other body part away fr...

Страница 20: ...r supply than cut the straps holding it fastened to the mechanical body of the automation b Remove the plastic side caps from the automation by unscrewing the relevant screws c Detach the NB BAT modul...

Страница 21: ...see paragraph ELECTRICAL CONNECTIONS d Erase the set up if it has already been stored on the automation control unit see paragraph MAINTENANCE e Press and hold pressed the PS1 START button on the PWB...

Страница 22: ...the automation Neptis Plus there are holes that must be broken open through which the electric cables must be inserted The installer must take care to secure the power supply cable inside the automati...

Страница 23: ...st be positioned corresponding to the end of the door O A E D G E T L LEFT SENSOR O A E D G E R R RIGHT SENSOR POWER SUPPLY CUT OFF SWITCH EARTH NEUTRAL LIVE MANUAL PROGRAM SELECTOR SECONDARY SENSOR M...

Страница 24: ...TART COMMON AUX1 E C COMMON AUX2 E O OPEN COMMON RADAR EX RADAR IN START COMMON ET DSEL DIGITAL PROGRAMMER M6 TEST GND AUX3 24V O C 24V L1 J5 M4 T NFC J1 25 26 27 28 29 8 9 10 11 A B 1 2 3 4 5 6 7 J4...

Страница 25: ...operating programs For details refer to the Interlock System paragraph Terminals 28 29 Open Collector NPN output The operation depends on the setting of function F41m see FUNCTION TABLE Connect a max...

Страница 26: ...e installer to configure the automatic door operation and perform the setup and function parameter setting operations to carry out the system diagnostics and to access the event memory containing info...

Страница 27: ...nsor installed on closing side F11 S05 ON Closing safety sensor F12 S06 ON Opening safety sensor F13 S07 ON TEST of closing safety sensor F14 S08 ON TEST of opening safety sensor F15 S09 OFF Test leve...

Страница 28: ...eaf automatic door refer to the paragraph Dual leaf door Follow chapter 16 1 only if the digital selector ET DSEL is new and is powered on for the first time Follow chapter 16 2 if the digital selecto...

Страница 29: ...default password See paragraph Password Management 16 3 INITIAL SETUP From the general programming menu the F1 button allows moving forward among menu symbols Select the INITIAL SETUP symbol Press qu...

Страница 30: ...he safety sensors The setup depends on the characteristics of the sensor installed If the type of sensors in use is FLAT SCAN or OA EDGET select OFF If the type of sensors in use is TOP SCAN S select...

Страница 31: ...n the power limit is reached set the F49 function to ON see Functions setup The buzzer noise for almost the entire run means that the leaf exceeds the limits allowed or that the installation dimension...

Страница 32: ...al box of the PWB control unit if the mechanical selector EV MSEL is installed ELECTRIC CONNECTIONS Terminal 1 of EV MSEL to terminal 9 Internal radar of the PWB of the Neptis Plus automation Terminal...

Страница 33: ...g Manual free door Automatic operation is disabled and the door can be opened manually Automatic bidirectional program The door automatically opens after an opening command Automatic unidirectional en...

Страница 34: ...TENTIOMETER TABLE Press again button F2 in order to activate the virtual spring function The symbol F2 on the display disappears F1 Door opening command Press the button F1 to open the door but only i...

Страница 35: ...the selected sub menu press briefly the ENTER button To exit the general programming menu and return to the work program view press the EXIT button DIAGRAM 1 If you enter the initial setup section se...

Страница 36: ...of the display it is displayed the letter M button to return to the general programming menu 19 1 FUNCTIONS SETTING In this section the display describes the purpose of the selected function the butto...

Страница 37: ...anual program selector in position II selection of the work program night lock ON Operating mode of manual program selector in position II selection of the work program open door F071 OFF Battery modu...

Страница 38: ...l and external radar inputs ON Operation with separate opening and closing commands The external radar input controls the opening the internal radar input controls the closing without automatic closin...

Страница 39: ...ure during the first opening movement the leaves start respecting the offset F36m Multiple selection function Multiple selection function allowing to set the position of the manual or mechanic program...

Страница 40: ...FUNCTION F78 Function enabled if the function F77 ON OFF for electromagnet not equipped with open closed status sensor factory setting The Neptis Plus automation automatically detects the closed door...

Страница 41: ...af speed in the last degrees of the closing movement to ease the engagement of the electric lock S P10 Potentiometer enabled if F02 ON Closing thrust to release the electric lock At the default value...

Страница 42: ...losing ledge in which the closing movement stop is achieved without reversing the running direction in case of detection of an obstacle S P25 Intensity of door braking at the end of the opening after...

Страница 43: ...is automatically released after the door has been locked from the inside If the value is 0 factory setting time is infinite therefore the electromagnet remains locked until the user activates the insi...

Страница 44: ...password and to be very careful not to forget it b PRIMARY PASSWORD for the system owner user It is a 5 character password used by the user to prevent unauthorized persons from having access to the se...

Страница 45: ...ct PRIMARY PASSWORD Press OK F1 Enter the default primary password A A A A A pressing 5 times the button A If the primary password is not the default password since it had already been changed before...

Страница 46: ...rocedure Enter the primary password Enter the new service password selecting a combination of 5 characters from the letters A B C D You are prompted to repeat the new password so enter again the previ...

Страница 47: ...to enable password usage it is recommended to change the combination of both primary and service password 21 5 DISABLING USER PASSWORD USAGE From the PASSWORD MANAGEMENT section select PASSWORD ON OFF...

Страница 48: ...o use Bidirectional program The buttons in this submenu are used as follows The button allows going to the next function The button F2 allows returning to the previous function The button F1 sets the...

Страница 49: ...mation of the Slave automation Each pulse on the button F3 allows switching from M to S and vice versa In case of single leaf automation on the top right of the display it is displayed the letter M Th...

Страница 50: ...ation I5 Version of microcontroller B Displays the software release of the microcontroller B of the logic card LCB of the automation I6 Identification number Identification number including data for m...

Страница 51: ...ected It is necessary to turn off the 230V power supply then turn it on again after a few seconds Check that the motor is running that the motor connector is properly plugged in and that the motor cab...

Страница 52: ...automation on the top right of the display it is displayed the letter M The GENERAL RESET clears the setup 24 1 PLUG AND PLAY The PLUG and PLAY option allows to set the functions and the parameters o...

Страница 53: ...st degrees of the closing movement to ease the engagement of the electric lock P10 Power of the closing thrust before door opening to ease electric lock release At value 0 the function is disabled fro...

Страница 54: ...e electric lock must be connected to the Master automation The safety sensors installed on the master leaf must be connected to the Master automation the safety sensors installed on the slave leaf mus...

Страница 55: ...Enter the 10 character technical password to access setup for information about the use of the technical password refer to the paragraph Password management 21 and 21 1 BEFORE STARTING THE SETUP MOVE...

Страница 56: ...to monitor the safety sensors The setup depends on the characteristics of the sensor installed Select OFF when using OA EDGE T or FLAT SCAN sensors Contact configuration on OPEN input between terminal...

Страница 57: ...at slow speed and you can choose with the function F35 if both leaves must start together or one after the other respecting the leaf delay F35 OFF In the first opening cycle the leaves start together...

Страница 58: ...ay On the top right of the display appears the letter M if the information is related to the Master operation the letter S if it is related to the Slave automation button F3 toggles from Master to Sla...

Страница 59: ...The radio control opens the door in all the operating programs of the automation 5 RECEIVER MEMORY ERASURE Should it be necessary to erase all the transmitter codes saved in the memory of the receive...

Страница 60: ...of the automation The disabled can also use the SPYCO radio control paired with the radio receiver EN RF1 Set the pause time P05 potentiometer so as to keep the door open for a sufficient time to all...

Страница 61: ...TERY CHARGED WITHOUT MAINS VOLTAGE OFF ON WARNING Periodically check battery efficiency To allow recharging the batteries must always be connected to the electronic control unit The equipment must be...

Страница 62: ...automatic doors can operate independently To enable interlocked operation you need to install the digital selector ET DSEL or T NFC as program selector on each door You cannot use the manual selector...

Страница 63: ...ration includes the following steps a the person approaching from the outside activates the external radar of door 1 and door 1 opens b the person enters the inner area between the two doors and engag...

Страница 64: ...e de energised from the inside G 1 ON OFF key selector allowing the electromagnet to be de energised from the outside in case of emergency 31 1 ELECTRIC CONNECTIONS 17 24V 16 8 EXT RAD 9 INT RAD 11 CO...

Страница 65: ...cts the closed door status ON for electromagnet equipped with open closed status sensor Connect the N O output contact of the electromagnet built in status sensor to the AUX1 input of the LCB control...

Страница 66: ...counter and the event memory see paragraph 24 MAINTENANCE Warning Any potentially damaged or worn component must be replaced Make use of original spare parts only for this purpose check LABEL Parts li...

Страница 67: ...on Neptis Plus has been realized to be incorporated in a machinery or to be assembled with other devices to constitute a machinery covered by Machine Directive 2006 42 EC Harmonized European regulatio...

Страница 68: ...NEPTIS PLUS Made in Italy by S p A Via Ilariuzzi 17 A S Pancrazio P se 43126 PARMA ITALY Tel 39 05 21 67 52 Fax 39 05 21 67 52 22 infocom labelspa it www labelspa com...

Отзывы: