LB-762 Controller Installation Manual

LAB-EL

3.7

Outputs of analog servomotors

LB-762 regulator is equipped with 8 connectors used for connection of analog servomotors. The outputs permit control of
any servomotors which accept control signal within the range 0-10V or 2-10V. Apart from control of servomotor it is also
possible to connect return signal from servomotor, informing about the current position of the servomotor. Scope of voltages
of return signal is analogous to the control output: 0-10 or 2-10V. The return signal is used by the regulator to control
correct operation of the servomotor (check whether the servomotor is set in accordance with the preset control signal). If the
servomotor has no return signal output or is not used in the given installation, one should make the connection according to
Figure 

3.9

.

Connectors of regulator LB-762 intended for cooperation with servomotors are marked as follows:

ACTUATOR #1

- servomotor no. 1,

ACTUATOR #2

- servomotor no. 2,

ACTUATOR #3

- servomotor no. 3,

ACTUATOR #4

- servomotor no. 4,

ACTUATOR #5

- servomotor no. 5,

ACTUATOR #6

- servomotor no. 6,

ACTUATOR #7

- servomotor no. 7,

ACTUATOR #8

- servomotor no. 8.

3.7.1

Servomotor power supply

LB-762 regulator does not supply power to servomotors – servomotors require a separate source of power supply. The manner
of power supply depends on the type of servomotors. Popular BELIMO servomotors can be powered with voltage 24V AC
or 24V DC, Johnson Control servomotors require only 24V AC power supply.

For 24V AC power supply the so-called safety transformer can be used 230V/24V, one should however ensure proper anti-
shorting protection.

The power supply unit can be one common for all servomotors – it must however ensure appropriate current efficiency (one
should calculate the sum of input power by all servomotors and depending on this power accordingly select efficient power
supply). Configuration is also possible in which each servomotor has its own individual power supply.

If both analog and digital servomotors are used in the system, their common power supply is possible – see description of
digital servomotor power supply, found below in the manual.

3.7.2

Connection diagrams - actuator with analog input

3 contacts are provided for connection of each servomotor:

IN

- return signal input informing about position of the servomotor,

OUT

- control signal output fixing servomotor position,

GND

- ground.

GND contact is present on each of the connectors, but this is a common signal without galvanic insulation between different
connectors, what can be use to possibly simplify cabling.

Figure 

3.7

and Figure 

3.8

present typical connection diagrams for Belimo and Johnson Control servomotors.

18

Содержание LB-760

Страница 1: ...KA LABORATORYJNA Herbaciana 9 05 816 Regu y PL tel 48 22 7536130 fax 48 22 7536135 www www label pl email info label pl LB 762 Controller Installation Manual Release 7 24 pa dziernika 2019 Copyright 2...

Страница 2: ...hermometers 15 3 4 Analog input 0 10V 16 3 4 1 Connection of analog CO2 concentration meter 16 3 5 Inputs of S300 measurement sensors 16 3 5 1 Connection of CO2 concentration meter type LAB EL LB 850...

Страница 3: ...er 16 3 5 Scheme of connection of LAB EL LB 710 type meter 17 3 6 Scheme of connection system of a typical valve to relay output 17 3 7 Scheme of connection of analog servomotors Belimo 19 3 8 Scheme...

Страница 4: ...common for the entire system such as measurement of external air parameters or CO2 concentration measurement Regulator LB 764 is LB 762 model with special modifications prepared for Baltic Champignon...

Страница 5: ...r more than one hall what permits reduction in the cost of the installation Detailed description further the manual External hytherograph to ensure better operation of mechanisms controlling climate i...

Страница 6: ...outers the network can be expanded over any area The number of devices in an Ethernet network is relatively unrestricted the only practical limits result from the type of network devices used switches...

Страница 7: ...ximum total length of cable is 1200 meters RS 485 network requires the application of LB 480 module that works as converter of communication interfaces Connection between a PC computer and LB 480 modu...

Страница 8: ...rk Rysunek 1 5 Scheme of a system with LB 762 and LB 760 regulators 1 6 Collective measurement of external air parameters In the measuring system consisting of more regulators both LB 762 and LB 760 i...

Страница 9: ...The whole continues in cycles Additionally it is possible to incorporate to the system CO2 concentration measurement for external air This has two functions periodic blowing Of the CO2 meter with fres...

Страница 10: ...ent in external air for reasons previously discussed Separate groups of collective CO2 measurement operate independently but within one network of data transmission it is not required here to split th...

Страница 11: ...pose unscrew four plastic screws on the front panel open the Casing lifting up the front panel on hinges Connections are placed in the rear part of the casing mostly along side edges The exception are...

Страница 12: ...the rear part of the casing there are several light diodes which are supposed to signal regulator status The function of these diodes is above all to provide a diagnostic tool they are important most...

Страница 13: ...o 2 each LED flash is associated with data receipt 2 2 1 Errors in operation Errors in operation of the regulator are signalled both on the display on the the front panel as well as by means of signal...

Страница 14: ...nity to interference it is necessary to ensure appropriate connection of the earth clamp IT IS NOT allowed to connect the earth clamp to contact N of the power supply connector Separate earthing is re...

Страница 15: ...e thermometer of air conditioning tunnel no 3 additional TEMP SENSOR AC 4 the thermometer of air conditioning tunnel no 4 additional TEMP SENSOR COMP 1 base thermometer no 1 TEMP SENSOR COMP 2 base th...

Страница 16: ...ped with two inputs permitting attachment of any S300 sensors extending measurement possibilities of the regulator In typical cases these are concentration meters CO2 LB 850 or hytherographs LB 710 Fo...

Страница 17: ...tion Normally Open normally no contact Switching on the relay causes short circuit of output contacts Relay no 8 is of contact no contact type pairs of contacts are marked as N O what means inactive c...

Страница 18: ...otors require a separate source of power supply The manner of power supply depends on the type of servomotors Popular BELIMO servomotors can be powered with voltage 24V AC or 24V DC Johnson Control se...

Страница 19: ...not have a return signal one should short circuit contacts IN and OUT in the given connector of regulator LB 762 in accordance with figure Figure 3 9 Such connection will ensure cheating of the regul...

Страница 20: ...US bus suitable servomotors must be used consistent with this standard Before connection to the system they require configuration address setting Default factory servomotor setting permits operation i...

Страница 21: ...um up power collected for all connected servomotors For example for servomotor LM24A MP consumed power is 2 5 W for 24V DC and 5 0 VA for 24V AC With 8 servomotors we have the sum of powers 20 W for 2...

Страница 22: ...ls such as MFT H programmer or interfaces ZIP RS232 ZIP USB MP ZIP 232 MP ZIP 232 KA plus dedicated Belimo PC Tool MFT P configuration software description the method of conduct is in the respective d...

Страница 23: ...ollision with other servomotors In such situations immediate disconnection can help of the other servomotors and conduct of the address setting procedure with a single servomotor connected Continuous...

Страница 24: ...for all nodes Regulator address settings can be applied using lbnetcfg tool PC with Windows operating system requires changes to network card settings under TCP IP protocol properties 3 11 RS 485 net...

Страница 25: ...but in practice it is not present RS 485 interface in converter LB 480 has similar termination mechanisms of RS 485 network This can be done using 3 contacts which can be found on the interface plate...

Отзывы: