Pennant Pool Heater

Page 7

Figure 2. Combustion Air and Vent Through Roof.

TERM

DESCRIPTION

Pipe

Single-wall galvanized steel pipe, 24 gauge

minimum (either insulated or non-insulated)

Joint

Permanent duct tape or aluminum tape

Sealing

Table 4. Required Combustion Air Piping Material.

(5.5 square cm/kW) of total input rating of all
equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening
shall have a minimum free area of not less than
1 square inch per 2000 Btu/hr (11 square cm/kW) of
total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method, for each
Pennant model.

Method 2

: One permanent opening, commencing

within 12 inches (30 cm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors or
spaces that directly communicate with the outdoors
and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (7 square cm/kW) of the total input
rating of all equipment located in the enclosure. This
opening must not be less than the sum of the areas of
all vent connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform
to the requirements in the applicable codes listed
above.

In Canada, consult local building and safety

codes or, in absence of such requirements, follow
CAN/CGA B149.

2.1.2 Intake Combustion Air

Never obtain combustion air from the pool area.

Corrosion of and/or damage to the pool heater may
result. The combustion air can be taken through the
wall, or through the roof. When taken from the wall, it
must be taken from out-of-doors by means of the
Laars horizontal wall terminal (see Table 1). When
taken from the roof, a field-supplied rain cap or an
elbow arrangement must be used to prevent entry of
rain water (see Figure 2).

Use single-wall galvanized pipe, per table 4,

for the combustion air intake (see Table 1 for
appropriate size). Route the intake to the heater as
directly as possible. Seal all joints with tape. Provide
adequate hangers. The unit must not support the
weight of the combustion air intake pipe. Maximum
linear pipe length allowed is 50 feet (15.2m). Three
elbows have been calculated into the 50-foot (15.2m)
linear run. Subtract 10 allowable linear feet (3.0m) for
every additional elbow used (see Table 1). When
fewer than 3 elbows are used, the maximum linear
pipe length allowed is still 50 feet (15.2m).

The connection for the intake air pipe is on the

filter box. The Pennant appliances may have venting
and combustion air ducting attached to the top or the
back. They are shipped with the connections at the
top. For attaching either or both pipes to the back, the
mounting flanges are reversible by removing the
mounting screws and orienting the flanges in the
desired position. Replace the screws after positioning
flanges. Run a bead of silicone around the collar and
slide the pipe over the collar. Secure with sheet metal
screws.

In addition to air needed for combustion, air shall

also be supplied for ventilation, including all air
required for comfort and proper working conditions
for personnel. The Pennant loses less than 1 percent of
its input rating to the room, but other heat sources may
be present.

2.2 Venting

2.2.1 Vent Categories

Depending upon desired Pennant venting, it may

be considered a Category I or a Category III
appliance. In general, a vertical vent system will be a
Category I system. However, in rare instances, a
Pennant’s vertical vent system may be considered
Category III. In the U.S., the National Fuel Gas Code
(American National Standard Z223.1-Latest Edition),
or in Canada the CSA B149.1 (latest edition), defines
a Category I vent system, and includes rules and tables
to size these vent systems. If the Pennant’s vertical
vent system does not satisfy the criteria for Category I
venting, it must be vented as a Category III system.

All Pennant vent systems which discharge

horizontally (without the use of a power venter) are
considered Category III vent systems.

Содержание PNCP

Страница 1: ...ualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or deat...

Страница 2: ...ntrol 14 5 3 1 Temperature Control Overview 14 5 3 2 Programming Control Parameters 14 5 3 3 Setpoint LSP 15 5 3 4 Differential dLS 16 5 3 5 Pump Operation 16 5 3 6 Heater Purge Pump Delay PD 16 5 4 L...

Страница 3: ...oper installation The Pennant appliance is protected against over pressurization A pressure relief valve is fitted to all appliances It is installed on the outlet header at the water outlet of the app...

Страница 4: ...of the structure When such a location is not available it is recommended that a suitable drain pan adequately drained be installed under the appliance The appliance is design certified by CSA Interna...

Страница 5: ...86 101 8 26 30 78 29 75 8 22 8 22 80 203 8 20 12 30 8 20 1500 78 199 39 101 101 8 26 30 78 29 75 8 22 8 22 91 231 8 20 12 30 8 20 1750 89 226 44 113 101 8 26 30 78 29 75 8 22 8 22 101 256 8 20 14 36...

Страница 6: ...stion Air From Room In the United States the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2 which follow Where ducts are used they...

Страница 7: ...d pipe per table 4 for the combustion air intake see Table 1 for appropriate size Route the intake to the heater as directly as possible Seal all joints with tape Provide adequate hangers The unit mus...

Страница 8: ...to excessive stack spill or backpressure indicating a blocked vent condition that all appliances attached to the vent be locked out and prevented from operating Note that the Pennant Pool Heater is e...

Страница 9: ...al so the vent exhaust does not settle on building surfaces and other nearby objects Vent products may damage such surfaces or objects 6 Locate the terminal at least 6 feet 1 8m horizontally from any...

Страница 10: ...3 4 Vertical Combustion Air Terminal When combustion air is taken from the roof a field supplied rain cap or an elbow arrangement must be used to prevent entry of rain water see Figure 2 The opening...

Страница 11: ...gas by checking the rating plate Laars Heating Systems appliances are normally equipped to operate at elevations up to 2000 feet 610m Pennant appliances may be adjusted to operate properly at higher e...

Страница 12: ...are installed Maintain 1 clearance to combustibles for hot water pipes Pipe the discharge of the relief valve full size to a drain or in a manner to prevent injury in the event of pressure relief Inst...

Страница 13: ...e latest edition of the National Electrical Code ANSI NFPA 70 in the U S and with latest edition of CSA C22 1 Canadian Electrical Code Part 1 in Canada Do not rely on the gas or water piping to ground...

Страница 14: ...exchanger to prevent damage from condensation The sensors for the control are installed as shown in Figure 6 and Section 4 3 Sensor Locations The automatic mixing system sensor already installed is sh...

Страница 15: ...15 15 750 20 15 15 1000 20 20 15 1250 30 25 15 1500 30 25 15 1750 25 20 2000 25 20 Table 8 Electrical Data Amps Figure 9 Typical Control Panel Figure 8 Pool Heater Controller The last parameter that m...

Страница 16: ...up to three times only once if optional lockout ignition module is used Loss of flame signal from the first ignition module will cause shutdown of the heater When the call for heat is satisfied the g...

Страница 17: ...roblems such as failure to start rough ignition strong exhaust odors etc can be due to improper setup Damage to the heater resulting from improper setup is not covered by the limited warranty 1 Using...

Страница 18: ...t this process until all gas valves have been set Note The pressure can be set only when the appliance is operating and only when the particular gas valve being adjusted is energized by a call for hea...

Страница 19: ...go through a prepurge period and ignitor warm up period followed by ignition 6 9 Therapeutic Pools Spas Therapeutic pools or spa pools are usually piped and controlled so that very warm or hot water o...

Страница 20: ...rough the ignitor hole s using a flashlight to illuminate If there is any indication of debris on the burners that are visible all the burners will need to be inspected more thoroughly Remove the scre...

Страница 21: ...mer is not capable of supplying control voltage for external devices Should a transformer need replacing shut off the 120 volt power Unplug the transformer wires remove the mounting screws and remove...

Страница 22: ...e inspected There should be no distortion or perforations in the burners outside of the active burner port area Replace if indicated 8 3 Short Cycling Because of the large mass of pool systems short c...

Страница 23: ...and 2000 A diagnostic panel that includes test points as well as diagnostic lights is provided in the control module It is located on the right side of the module behind the display To access remove t...

Страница 24: ...5C3502 5C3502 5C3502 5C3502 5C3502 5C3502 11 Plate Vent 5C3004 10C3004 10C3004 20C3004 20C3004 20C3004 20C3004 12 Cover Vent Plate 20C3006 20C3006 20C3006 20C3006 13 Plate Cover Filter 5C3002 5C3002...

Страница 25: ...2004 12C2010 15C2004 17C2010 20C2010 29 Door Chamber Access 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005 5C2005 1 1 1 2 2 2 2 30 Cover Chamber Front Right 12C2008 15C2004 17C2008 20C2008 Gasket Tape Rear...

Страница 26: ...64501 10364501 10364501 46 Well Temperature Control RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 RE2058300 47 Gasket Flange S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S006370...

Страница 27: ...ltion Control 3 Try non CSD 1 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900 E2313900 1 1 2 2 2 2 2 67 Diagnostic Board E2105500 E2105500 E2105500 E2105500 E2105500 E2105500 E2105500 68 Indicat...

Страница 28: ...t 10C6500 10C6500 10C6500 10C6500 2 2 2 4 Burner Manifold Assy 3 Burners Right LP 5C6620 5C6620 5C6620 5C6620 5C6620 1 1 2 1 1 Burner Manifold Assy 3 Burners Left LP 5C6520 5C6520 5C6520 5C6520 5C6500...

Страница 29: ...00 L2012600 L2012600 L2012600 2 2 2 4 82 Burner Tray 3 Burners L2012200 L2012200 L2012200 L2012200 L2012200 2 3 5 2 3 Burner Tray 4 Burners L2012500 L2012500 L2012500 L2012500 3 3 3 6 82A Gasket Burne...

Страница 30: ...LAARS Heating Systems Page 30 Figure 10 Sheet Metal Components...

Страница 31: ...Pennant Pool Heater Page 31 Figure 11 Internal Components...

Страница 32: ...LAARS Heating Systems Page 32 Figure 12 Heat Exchanger Components A Enlargement from previous page...

Страница 33: ...Pennant Pool Heater Page 33 Figure 13 Pennant 500 1000 Ladder Diagram SECTION 10 Wiring Diagrams...

Страница 34: ...LAARS Heating Systems Page 34 Figure 14 Pennant 1250 2000 Ladder Diagram...

Страница 35: ...Pennant Pool Heater Page 35 Figure 15 Pennant 500 1000 Wiring Schematic...

Страница 36: ...LAARS Heating Systems Page 36 Figure 16 Pennant 1250 1500 Wiring Schematic...

Страница 37: ...Pennant Pool Heater Page 37 Figure 17 Pennant 1750 2000 Wiring Schematic...

Страница 38: ...LAARS Heating Systems Page 38 Figure 18 Field Wiring...

Страница 39: ...Pennant Pool Heater Page 39...

Страница 40: ...335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1201 Document 3...

Отзывы: