background image

LAARS Heating Systems

Page 16

Pennant appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the gas
valve manifold pressure and the air shutter(s). The
required instruments used to assist in these
adjustments are a CO

2

 or O

2

 Analyzer and a U-Tube

Manometer or other device capable of reading a
pressure of 2.5-3.0 inches W.C. (0.62-0.75 kPa).

Start the adjustment process by checking the CO

2

in the “as installed” condition. Adjust the air shutter(s)
so that the CO

2

 is about 8% or the O

2

 is about 6.8% for

appliances operating on Natural Gas. For appliances
operating on LP Gas adjust the air shutter(s) so that
the CO

2

 is about 9.2% or the O

2

 is about 6.8%.

Appliances with two blowers should be adjusted so
that the air shutters below each blower are open the
same amount.

Once the CO

2

 or O

2

 has been set, the manifold

pressure may be adjusted. Remove the 1/8 NPT plug
from the lower side of the gas valve that is to be set
and install a fitting, hose and manometer. Start the
appliance and observe the manifold pressure. Manifold
pressure must be adjusted to 3.0 in. W.C. (0.75 kPa)
(for high altitude only, standard operating pressure is
2.5 in. W.C. (0.62 kPa)). It is adjusted by removing the
slotted cap on the gas valve and turning the adjustment
screw (beneath the cap) clockwise to increase pressure
. After the adjustments have been completed, the
fitting, hose and manometer have been removed and
the 1/8" plug has been replaced, replace the cap.
Repeat this process until all gas valves have been set.
Note: The pressure can be set only when the appliance
is operating and only when the particular gas valve
being adjusted is energized by a call for heat.

After all of the gas valve manifold pressures

have been set, the CO

2

 or O

2

 must be reset. CO

2

 or O

2

will have changed when the manifold pressure was
adjusted. Open the air shutter(s) to reduce the CO

2

 or

O

2

 to the values achieved previously.

The procedure is complete when all gas valves

are adjusted to a manifold pressure of 3.0 in. W.C.
(0.75 kPa) and the CO

2

 is adjusted to 8.0% for Natural

Gas appliances or 9.2% for LP appliances. When
using an O

2

 analyzer, the correct O

2

 is 6.8% for both

Natural Gas and LP appliances.

 Caution

Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, close main shutoff valve, do not
shut off switch, and contact your heating contractor,
gas company, or factory representative.

6.4 Shutting Down the Pennant

1.

Switch off the shutdown switch (located above
the Main Power Switch).

2.

Wait until the “pump” light (located on the front
panel) goes out.

warm-up is complete and all safety devices are
verified, the gas valves open. If ignition doesn’t
occur, check that there is proper gas supply. Wait
5 minutes and start the unit again. During initial
start up, air in the gas line may cause the Pennant
to "lock out" during the first few trials for
ignition.  Depending on the ignition modules
installed, the manual reset button on the ignition
module(s) may need to be depressed to restart the
heater.

6.

When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not
exceed 13" W.C. (3.2kPa). The minimum inlet
gas pressure is 5" W.C. (1.2kPa).

7.

Once the inlet gas pressure is verified, the outlet
gas pressure from each valve (manifold gas
pressure) must be checked, and adjusted, if
necessary. The manifold gas pressure must be
2.5" W.C. (0.62kPa).

8.

Complete the setup by checking the CO

2

 at the

outlet of the unit. The CO

2

 should be 8% for

natural gas, or 9.2% for propane.

9.

After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested

.

To test:
(a)

Close gas shutoff valve with burner
operating.

(b)

The flame will go out and blower will
continue to run for the post purge cycle.
Three (3) additional attempts to light will
follow (only one (1) attempt for optional
module). Ignition will not occur as the gas
is off. The ignition control will lockout, and
will have to be reset before the unit will
operate. The ignition control reset button is
located on each ignition control, in the
lower right corner, and can be reset by
depressing. It is not marked on the ignition
control label.

(c)

Open gas shutoff valve. Restart the
appliance. The ignition sequence will start
again and the burner will start. The
appliance will return to its previous mode
of operation.

NOTE:

Models 1250, 1500, 1750 and 2000 have two

ignition controls and two ignitors.

6.3.2 High Altitude Adjustment and Set Up

Pennant appliances may be operated at high altitude

(7700 ft., 2347 m) with a reduction in output of
approximately 10%. At elevations higher than 7700 ft.
(2347 m) the reduction in output will exceed 10% and at
elevations below 7700 ft. (2347 m) it will be less than
10%. When adjusted properly, the appliance will perform
properly at any altitude. High altitude adjustment must
not be made on appliances operating at elevations below
2500 ft. (762 m).

No orifice changes are required to adjust the

Содержание Pennant PNCP 500

Страница 1: ...ualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or deat...

Страница 2: ...trol Parameters 14 5 3 3 Setpoint LSP 14 5 3 4 Differential dLS 14 5 3 5 Pump Operation 14 5 3 6 Heater Purge Pump Delay PD 14 5 4 Limit Controls 14 SECTION 6 Operating Instructions 6 1 Sequence of Op...

Страница 3: ...oper installation The Pennant appliance is protected against over pressurization A pressure relief valve is fitted to all appliances It is installed on the outlet header at the water outlet of the app...

Страница 4: ...of the structure When such a location is not available it is recommended that a suitable drain pan adequately drained be installed under the appliance The appliance is design certified by CSA Interna...

Страница 5: ...86 101 8 26 30 78 29 75 8 22 8 22 80 203 8 20 12 30 8 20 1500 78 199 39 101 101 8 26 30 78 29 75 8 22 8 22 91 231 8 20 12 30 8 20 1750 89 226 44 113 101 8 26 30 78 29 75 8 22 8 22 101 256 8 20 14 36...

Страница 6: ...se Never obtain combustion air from the pool area Corrosion of and or damage to the pool heater may result 2 1 1 Combustion Air From Room In the United States the most common requirements specify that...

Страница 7: ...e pipe Maximum linear pipe length allowed is 50 feet 15 2m Three elbows have been calculated into the 50 foot 15 2m linear run Subtract 10 allowable linear feet 3 0m for every additional elbow used se...

Страница 8: ...ppliance trips due to excessive stack spill or backpressure indicating a blocked vent condition that all appliances attached to the vent be locked out and prevented from operating Note that the Pennan...

Страница 9: ...metering regulating or relief equipment 7 If the Pennant uses ducted combustion air from an intake terminal located on the same wall locate the vent terminal at least 3 feet 0 9m horizontally from th...

Страница 10: ...e ell facing down to prevent rain infiltration The combustion air inlet opening must still be high enough to prevent blockage by snow see Section 2 3 2 SECTION 3 Gas Supply and Piping 3 1 Gas Supply a...

Страница 11: ...and contraction of copper pipe consideration should be given to the type of hangers used Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers It is rec...

Страница 12: ...pool loop Figure 6 Pool Heater Piping The Pennant Pool Heater is shipped with a field installed mixing system and must be piped in primary secondary style as shown A remote pool temperature sensor and...

Страница 13: ...e to the next parameter Figure 7 Pool Heater Controller wiring terminal strip which is located at the right side of the appliance NOTE All internal electrical components have been prewired No attempt...

Страница 14: ...LS is the number of degrees between the temperature at which the heater turns off and the temperature at which the heater restarts It is adjustable from 1 F to 10 F 5 3 5 Pump Operation The pump energ...

Страница 15: ...nant 1250 1500 1750 and 2000 models have two ignition modules that control different burners 6 2 Filling the Heater System 1 Ensure the system is fully connected filled with water and all valves are o...

Страница 16: ...act your heating contractor gas company or factory representative 6 4 Shutting Down the Pennant 1 Switch off the shutdown switch located above the Main Power Switch 2 Wait until the pump light located...

Страница 17: ...y drained before the first frost Drain the heater by removing the plug at the end of the inlet outlet header casting Also remove the small plug at the bottom of the pump housing Do not replace either...

Страница 18: ...the burners in the reverse order 7 2 2 Filter The filter used in the Pennant is washable with an 83 arrestance Since the filter is washable it will 3 Spas are excellent for relaxation body conditioni...

Страница 19: ...nit has water flow before ignition is allowed only need replacement in very rare cases If filter replacement is needed it should only be replaced with a factory part Inspect the air filter If there is...

Страница 20: ...ol 7 2 13 Heat Exchanger Coil Caution Black carbon soot buildup on a dirty heat exchanger can be ignited by a random spark or flame To prevent this from happening dampen the soot deposits with a wet b...

Страница 21: ...is within the proper range No significant flue gas odor should be detected when combustion is proper A strong piercing smell indicates poor combustion and generally a lean mixture low CO2 or high O2 T...

Страница 22: ...e inducer terminals F1 and F2 of the Fenwal ignition module The 24V power to the T STAT terminal of the ignition module s are routed through the safety interlocks The ladder diagram for models 1250 15...

Страница 23: ...eft Side Front 5C2015 5C2015 5C2015 5C2015 5C2015 5C2015 5C2015 18B Chamber Right Side Front 5C2016 5C2016 5C2016 5C2016 5C2016 5C2016 5C2016 Item Description Model Model Model Model Model Model Model...

Страница 24: ...00 T2017900 T2017100 T2017900 T2017100 1 1 1 1 1 1 35B Tile Front Center T2016900 T2016900 T2016900 T2016900 1 1 2 2 36 Tile Rear T2015700 1 37 Tile Rear Left Side T2017500 T2016600 T2016600 T2016600...

Страница 25: ...utlet Bronze 20150301 20150301 20150301 20150301 20150301 20150301 20150303 51 Flow Switch RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 RE0013000 52 Gauge Temperature Pressure RA0079000...

Страница 26: ...imit Auto Reset 135 F E2104800 E2104800 E2104800 E2104800 E2104800 E2104800 E2104800 72 Relay Pump SPST E0098300 E0098300 E0098300 E0098300 E0098300 E0098300 E0098300 72A Relay Fan DPDT E0076600 E0076...

Страница 27: ...000 6 9 12 15 18 21 24 Orifice Gas Propane L2012400 L2012400 L2012400 L2012400 L2012400 L2012400 L2012400 6 9 12 15 18 21 24 81 Burner Manifold 3 Burners Right L2012900 L2012900 L2012900 L2012900 L201...

Страница 28: ...LAARS Heating Systems Page 28 Figure 9 Sheet Metal Components...

Страница 29: ...Pennant Pool Heater Page 29 Figure 10 Internal Components...

Страница 30: ...LAARS Heating Systems Page 30 Figure 11 Heat Exchanger Components A See pump chart below for pump numbers...

Страница 31: ...Pennant Pool Heater Page 31 Figure 12 Pennant 500 1000 Ladder Diagram SECTION 10 Wiring Diagrams...

Страница 32: ...LAARS Heating Systems Page 32 Figure 13 Pennant 1250 2000 Ladder Diagram...

Страница 33: ...Pennant Pool Heater Page 33 Figure 14 Pennant 500 1000 Wiring Schematic...

Страница 34: ...LAARS Heating Systems Page 34 Figure 15 Pennant 1250 2000 Wiring Schematic...

Страница 35: ...Pennant Pool Heater Page 35 Figure 16 Field Wiring PNCP 500 1000...

Страница 36: ...rvice Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars c...

Отзывы: