User’s Manual - Mascot LX Boilers and Water Heaters

Page 5

the building’s heating loop. only after the value shifts 

position will the firing sequence begin. 

3.4 Modulation Control

the control uses a PID algorithm to adjust 

the firing rate of the boiler as the control point is 

approached. the goal of the control is to operate at a 

minimum firing rate to match the load on the appliance. 

3.5 Pump Control

the boiler pump is active anytime there is a call for 

heat applied to the control. When there is a central heat 

call the system pump relay is active. If there is a DHW 

call while the central heat call is active the system pump 

turns off. this happens because of domestic hot water 

priority, which forces the control to satisfy the domestic 

water demand prior to the hydronic demand. When the 

last heat demand is satisfied the boiler pump enters an 

overrun time.

3.6 High Limit

the control uses a dual thermistor sensor to 

monitor the Mascot LX’s maximum temperature. the 

high limit sensor is installed in the outlet water. A dual 

thermistor sensor is used, so that the two temperatures 

can be monitored and compared to confirm accuracy. 

The control will automatically reduce the firing of the 

Mascot LX to prevent the high limit from tripping. the 

high limit setpoint is not adjustable.

3.7  Stack Temperature

the stack temperature is a dual thermistor sensor 

and is limit rated. the control compares each of the 

temperature readings to determine accuracy. the stack 

sensor is used as a limiting feature to avoid excessive 

temperatures in the venting.

3.8  Domestic Hot Water Temperature

the domestic hot water temperature sensor is used 

to control the DHW temperature. the DHW setpoint can 

be adjusted through the Base / Home state and the User 

Mode. on LX ‘C’ or Combi models, the DHW sensor is 

pre-installed in the DHW exchanger.  on LX ‘H’ or Heat 

models the DHW can be can be controlled by an aquastat 

or optional DHW sensor installed in an indirect tank. 

connected. Repeat this process for terminal B and 

GnD.

To configure the control system, identify which 

boiler is going to be the “master” boiler for the cascade 

system and navigate to installer parameter P06, 

“Cascade Address”. set the address to “0” and press 

and hold “select”. When “auto cfg” appears on the 

display press “select” to start the auto configuration 

process. The auto configuration process will find all 

boilers connected to the “master” boiler and assign 

addresses. When auto configuration is complete the 

display should show “boilr #” where # is the total 

number of boilers found in the cascade system.

The final steps are to set the individual setpoints 

in the cascade system, which include P07 “Cascade 

setpoint”, P08 “Cascade off Hysteresis” and P09 

“Cascade on hysteresis”. these variables must be set to 

the appropriate values for the installation. When setting 

P09 “cascade on hysteresis” the value should not be 

less than P08 “Cascade off Hysteresis” as P09 references 

the off point (P07+ P08) as the starting point for the on 

hysteresis. An example of this is shown below.

Correct settings:

P07 = 120

°

P08 = 10

°

F

P09 = 20

°

F

With these setting the modulation point is 120

°

the off point is 120

°

F + 10

°

F = 130

°

F

the on point is 130

°

F – 20

°

F = 110

°

F

Incorrect settings:

P07 = 120

°

P08 = 10

°

F

P09 = 5

°

F

With these setting the modulation point is 120

°

the off point is 120

°

F + 10

°

F = 130

°

F

the on point is 130

°

F – 5

°

F = 125

°

F

In this case the boiler is turning back on prior to 

reaching the modulation point, which could lead to 

short cycling.

3.9.1 Cascade Manual Configuration

In some applications it may be necessary to 

configure the cascade system manually. To do this, the 

boilers should be wired as shown in the Auto Cascade 

section of the manual. then each individual control in 

the cascade must have a specific address assigned by 

adjusting P06 “ Cascade address” on each boiler. to 

start, identify the boiler that will be the “master” boiler. 

navigate to parameter P06 “cascade address” set to 

“0” and press “select” (do not press and hold select). 

then press and hold select. 

Repeat this process for each boiler in the cascade 

setting each address to a unique number.

the last step is to adjust all of the setpoints 

for the installation application as shown in the Auto 

cascade section of the manual.

3.9   Cascade Auto Configuration

to operate up to 8 boilers in cascade, the boilers 

must be “daisy chained” together using Modbus 

terminals A, B and GnD, located on the boilers terminal 

block. the wiring should be completed with at least 

three wire shielded cable with ground. the ground wire 

should be connected to a suitable chassis ground on one 

end of the daisy chain only. Wire each boilers terminal 

A in series with the next boilers terminal A until all are 

Содержание MASCOT LX

Страница 1: ...as in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructions don...

Страница 2: ...ranty will be voided The installation must conform to the requirements of the local jurisdiction having authority and in the United States to the latest edition of the National Fuel Gas Code ANSI Z223...

Страница 3: ...SIDE PANEL MISSING FOR VISUAL PURPOSES COMBUSTION INLET HEAT EXCHANGER ASME TAG AUTOMATIC AIR VENT LOW WATER CUT OFF OPTIONAL EXHAUST SERVICE HATCH GAS SUPPLY HEAT EXCHANGER WATER PRESSURE SWITCH USER...

Страница 4: ...lator to provide at least 12 psi 81 8 kPa at the highest point in the heating loop 4 Open bleeding devices on all radiation units at the high points in the piping throughout the system unless automati...

Страница 5: ...through a prepurge period and ignitor warm up period followed by ignition AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d ince...

Страница 6: ...Mode Parameters and full details on using the User Interface please see the Mascot LX Installation and Operating Manual Document 1285 available on laars com To change the value of that parameter pres...

Страница 7: ...g appears on the display press select to start the auto configuration process The auto configuration process will find all boilers connected to the master boiler and assign addresses When auto configu...

Страница 8: ...Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1410 Document 128...

Отзывы: