background image

Page 14

LAARS Heating Systems

will require resetting. If a lockout occurs for any of the
reasons stated in this section the “VALVE/FLAME”
light on the boiler control will flash.

Tripouts of the manual reset safety limit can be

caused by a failure of the thermostat in the diverting
valve, short cycling or a calibration change in the
safety limit. If the thermostat in the diverting valve
fails in the closed position, all of the water leaving the
outlet of the primary heat exchanger will be
recirculated back to the inlet and the temperature will
rise rapidly. This rapid temperature rise may cause the
safety limit to trip before the operating control senses
high temperature. Short cycling may cause a tripout in
the same manner. A calibration shift in the safety limit
may also cause it to trip out. If the temperature of the
water leaving the unit is well below 240°F (116°C) and
the recirculation line from the diverting valve to the
pump inlet is not extremely hot the safety limit may be
defective. These same conditions may also indicate a
pump failure, however, knocking generally occurs
when a pump fails.

1X. Routine De-Liming Procedure

ROUTINE DE-LIMING PROCEDURE in hard

water areas. This should be done on a regularly
scheduled basis.

1.

Close the gas cock or manual gas shutoff (see
Figure 9) and shut off the main disconnect switch.

2.

Isolate the HeatMaker 9600 HWG unit from the
system by closing the shutoff valves. If recirc.
lines are piped, isolate the return system from
water heater.

3.

Remove the lower front panel from the water
heater and connect a hose to the drain fitting.
(Located under the cylindrical chamber.) Relieve
pressure at drain.

4.

Connect a hose to the drain (provided by
installer) on the cold (return) side piping to the
appliance.

5.

Remove cover from thermostatic valve and
remove thermostat. Wrap tape around / over
cutaway sections in the cover and replace all
parts except thermostat. Reinstall valve cover and
tighten bolts.

6.

Fill the water heater combustion coil with
deliming solution from the hose connected under
boiler coil assy. until it exits from upper hose. A
small pump should be used to do the filling from
a plastic container. The upper hose should then
be placed in this container and the pump should
run until the circulator solution is no longer
foamy.

7.

Shut off pump and disconnect from hose.
Carefully drain solution from hoses and connect
city water to lower hose to flush combustion coil.
Flush for approximately 5 minutes with city
water.

8.

Remove hoses, close drain cock, close drain on
cold / return, and replace lower front panel .

9.

Remove cover from thermostatic valve and
remove tape. Replace thermostat, spring brass
ring and valve cover, and tighten bolts.

10.

Open shut off valves and purge air from petcock
at top of thermostatic valve cover.

11.

Re-open gas supply and turn on main disconnect
switch to return heater to service.

1Y. Sequence of Operation

On a call for heat from the room thermostat on

9600 CB series boilers, or the tank aquastat on 9600
HWG series, the boiler control is energized through the
control, the vent TCO and the safety limit. It energizes
the pump, checks to ensure that the stack switch
contacts close and the red “PURGE” light lights. The
pump and blower continue to run and for 15 seconds
the red “PURGE” light goes out, the red “igniter” light
lights and the igniter heats for 20 seconds. At the end
of the 20 seconds, the red “VALVE/FLAME’ light is
lit and the gas valve is energized. For 2 seconds the
valve and igniter are energized and burner will ignite.
Following this the igniter is deenergized and the red
“IGNITER” light goes out and the pump and blower
continue to run and the burner operator under the
supervision of the boiler control. If for any reason the
full sequence is completed and the burner doesn’t
ignite, the sequence will be repeated after a blower
“on” time of 45 seconds (30 seconds post purge and 15
seconds prepurge for the next cycle). During this part
of the sequence, the igniter remains on for 30 seconds
and the balance of the sequence is unchanged. If no
ignition occurs again, a third cycle will follow with the
same sequence as the second. After the third “trial for
ignition”, if the burner does not ignite, the system will
“lock out” (valve/flame light flashing) and reset can
only be accomplished by momentarily switching the
power off. At the end of the heating cycle, after the gas
valve is deenergized, the blower will continue to run
for a 30 second post purge and the pump will run for
about another minute. If normal burner operation
during a heating cycle is interrupted by any of the limit
controls the blower will continue to operate for a 30
second post purge and the pump continues to operate
until the call for heat is satisfied.

Содержание HWG-M2-250

Страница 1: ...r installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss...

Страница 2: ...h 10 1G BoilerControl 10 1H Stack Switch 11 1I Igniter 11 1J Transformer 11 1K Unit Pump 11 1L Blower 11 1M GasValve 11 1N TimeDelayRelay TDR 11 1O OperatingControl 11 1P VentTCO 12 1Q IntakeTCO 12 1R...

Страница 3: ...ondensation temperature of the water vapor in the flue gases A circulator is built into the unit to provide enough head to circulate water through the H X s and to a secondary heating loop or separate...

Страница 4: ...pical D Combustion Coil Outlet E Hot Water Outlet To Tank or System 160 170 F Typical 160 FTHERMOSTAT Figure 2a Water Flow through a Heatmaker 9600 HWG Before S N 394 068 CB Before S N 795 0014 THERMO...

Страница 5: ...urner 8 Secondary Heat Exchanger 9 Primary Heat Exchanger 10 Return From Primary Loop 11 Gas Valve 12 Flow To Primary Loop A Secondary Heat Exchanger Inlet B Secondary Heat Exchanger Outlet C Primary...

Страница 6: ...ow Through Heatmaker 9600 43 INTAKE TERMINAL 50 WALL PLATE AIR INTAKE 45 WALL PLATE 44 EXHAUST TERMINAL EXHAUST AIR ORIFICE GAS ORIFICE GAS 1 COMBUSTION COIL 2 ECONOMIZER 7 FLAMEHOLDER 46 EXHAUST ASSE...

Страница 7: ...9600 CB HWG Service Manual Page 7 Figure 4 Cut Away View of Heatmaker 9600 Figure 5 Control Box...

Страница 8: ...nd input desired Part Description Part 23 Jacket Front Removeable 10 402 24 Jacket Top 10 406 25 Jacket Bottom 10 010 26 Control Boiler Integrated 2400 224 27 Transformer 40 VA 2400 006 28 Time Delay...

Страница 9: ...minal and at least 6 152mm into the flue pipe The unit must operate for 5 minutes before taking a sample Take a sample and determine the CO2 or O2 CO2 8 to 8 5 natural gas O2 7 to 6 CO2 9 to 9 8 propa...

Страница 10: ...ostatically controlled device which keeps the primary heat exchanger H X from operating in the condensing mode When return water from the storage tank or the system is below 130 F 54 C the diverting v...

Страница 11: ...d unplug the power wires from the blower motor Disconnect intake exhaust vents and remove top jacket Remove the six bolts and nuts from the blower discharge flange and the four nuts from the blower in...

Страница 12: ...n the gas valve The gas supply to the boiler must be shut off before making this connection The Heatmaker boiler is designed to operate with supply pressures of 4 14 in W C 8 1 oz in2 with the boiler...

Страница 13: ...se the flame signal The control then causes a restart and if the flame signal is sensed on the restart then the burner will operate again The intermittent sending and losing of the flame signal by the...

Страница 14: ...solution is no longer foamy 7 Shut off pump and disconnect from hose Carefully drain solution from hoses and connect city water to lower hose to flush combustion coil Flush for approximately 5 minutes...

Страница 15: ...on and no indicator lights are flashing check for an open vent TCO operating control or safety limit switch For additionaltroubleshootinginformationrefertothe trouble shooting flow charts on the page...

Страница 16: ...VOLTAGE 120 VAC BETWEEN BLACK AND WHITE WIRES AT BACK OF 120 VAC CONNECTORON BOILERCONTROL DIDBOILERRUNTHROUGHA COMPLETE CYCLE AS DE SCRIBED IN SEQUENCE OF EVENTS PAGE 20 TESTLIMIT CIRCUIT PAGE 17 PUM...

Страница 17: ...OHMSCALE CONTINUITY CONTINUITY CONTINUITY NOCONTINUITY OHMS NOCONTINUITY TESTING LIMIT CIRCUIT YOU MUST COMPLETE PAGE 16 FIRST NOTE AFTER COMPLETEING LIMIT CIRCUIT TESTING PLUG IN CONTROL PLUG AND REC...

Страница 18: ...EAVESETC AGAINST VENTTERMINAL CYCLE BOILER MANY TIMES TO TRY TO CREATE A MALFUNCTION CLEAR BLOCKAGE AND RECYCLEBOILER CHECKSTACKSWITCH BLOCKAGE EXISTS NO BLOCKAGE NO YES YES NO RED PURGE LIGHT FLASHIN...

Страница 19: ...TSTACKSWITCH TUBES AND CHECK FOR CONTINUITYBETWEENSTACK SWITCHTERMINALSWITH BLOWEROPERATING CHECKFORVENTOBSTRUCTIONS CLEAROBSTRUCTIONS RECONNECTTUBES ELEC TRICALWIRESTOSTACK SWITCH START BOILER RUN TH...

Страница 20: ...SSURETAP ON GAS VALVE PRESSURE DURING BLOWER OPERATIONWITHOUTGASFLOW VALVE FLAME LIGHT NOT LIT IS 4 IN W C CHECK FOR VOLTAGE 120 VAC ATBLOWERWIRECONNECTOR WITHIN5MINS AFTERGREEN LIGHT BLOWER O K REPLA...

Страница 21: ...G LITE CHECKCOMBUSTION CHECKIGNITER IGNITEROK CHECK FOR GAS FLOW IS METER MOVING REPLACE IGNITER REPLACEINTEGRATEDBOILERCONTROLP N2400 224 INSTALL CORRECT ORIFICES BOILERCYCLESTHROUGHTHREECYCLESAFTER...

Страница 22: ...L PLUG CN6 THERE IS 120 VAC AT CIRCULATOR PLUG CN5 TURNUPT STATORAQUASTATOR CORRECTSTATPROBLEM NO YES NO YES SEETROUBLESHOOTING CHART PAGE 16 THERE IS 120 VAC AT PUMP REPLACEBOILER CONTROLP N2400 224...

Страница 23: ...23 Figure 9 9600 Ladder Diagram Figure 10 9600 Wiring Diagram Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify pr...

Страница 24: ...sure of 9 3 Remove blower and inspect flameholder burner for hole 4 Check that the blower flanges and gas piping are sealed D OCCASIONAL LOCKOUTS Requires interruption of power to re start or reset of...

Отзывы: