Cascading the FT Series ‘Heating Only’ Boiler

Domestic Hot Water Parameters

For a complete list of parameters, reference the FT Series Installation and Operation Manual 1342.

If a DHW aquastat is used, the maximum DHW load needs to be calculated to determine the number of boilers 
required to meet max DHW load. The aquastat must be installed in the tank and wired to each boilers’ terminal 
strip “DHW TEMP SENSOR” connection (page 10). They can be wired either in parallel (straight from the 
aquastat to each boiler) or in series (aquastat to first boiler and then from boiler to boiler). 

The DHW System Pump must be connected to the first boiler among those selected to handle the domestic 
water load on the terminal strip labeled “DHW Pump” (page 10). 

 
Domestic Hot Water Parameters  

For a complete list of error codes reference the Mascot FT Installation and Operation Manual 1342 

Index 

Numbers 

Parameter 

Description 

21: dH 

Indirect Storage Tank 
Temperature Set Point 

Sets Maximum Indirect storage tank 
Temperature Range: 95 - 180°F , Default 120 °F 

22: dd 

Indirect Storage Tank 
Differential Set Point 

DHW Differential Set Point Range: 5°F-30°F, 
Default 7 °F 

23: Pr 

DHW Pump Post Run Time 

DHW Pump Post Run Time Range: 0-10 Min, 
Default 1 Min 

24: dP 

DHW Priority Timer 

DHW Priority Timer Range: 0 – 60 Min , Default 
30 Min 

25: St 

Boiler Set-point Temperature 
for DHW Demand 

Boiler Set-point Temperature for DHW Demand, 
Range: 120 °F– 180 °F , Default 180 °F 

 

ADD NEW ERROR SECTION 

D. Typical Cascade Error Codes 

For a complete list of error codes reference the Mascot FT Installation and Operation Manual 1342 

Er:30 

System Sensor Short 

NOTE: 

This error will only appear if the boiler is used in a cascaded system. 

This Error Code will go away when system sensor is repaired or replaced. 
1. Check system temperature sensor. Ensure connections are secure. 
2. Check system sensor resistance. If resistance is zero, replace the sensor. 
3. If the problem persists, replace the main control. 

NOTE: 

During the error state the units will continue to operate. Boiler setpoint 

will be the same as the system sensor setpoint until the issue is remedied. 
During normal operation boiler setpoint is defaulted to 20°F higher than the 
system setpoint to a maximum of 180°F setting

 

Er:78 

Cascade  

Communication Error 

NOTE: 

This error will only appear in a cascaded system. 

1. Turn power OFF and ON at the boiler display panel. 
2. If error reappears, ensure all cascaded boilers are powered ON. 
3. If error reappears, check Installer Mode parameter 28 at the Leader boiler. 
Ensure the number of cascaded units chosen in this parameter matches the 
number of cascaded units in the system. 
4. If error reappears, check Installer Mode parameter 27 at all cascaded 
boilers. Ensure the address number matches that of the connected boiler (00 
for Leader, 01 for Follower 1, etc.) and that no numbers are skipped or 
repeated. 
5. Ensure every unit in the cascade system is connected properly. Inspect the 
cascade cables and ensure all are connected without damage or defect.  
Repair or replace any damaged cables. 
6. If the problem persists, contact technical support.

 

 

5.D   

Domestic Hot Water ‘Storage Mode’ for Cascade System

 (continued)

 

Using a DHW Sensor (thermistor type)

When using a DHW sensor, the boiler monitors the temperature of the indirect water heater. Connect the 

sensor to the “DHW Temp Sensor” terminals of the boiler piped to the indirect water heater. When using a 

DHW sensor, Parameter # 39 (39:SA) must be set to “SEnS”. The temperature of the DHW in the indirect 

water heater is determined by Parameter #21 (21:dh) in the table below.  The sensor differential is determined 

by parameter #22 (22:dd) in the table below.  The boiler setpoint temperature during a DHW demand is 

determined by Parameter #25 (25:st) in the table below. Connect the DHW Pump to the “DHW Pump” terminals 

of the boiler piped to the indirect water heater. A relay is required if the DHW pump draws more than 2 amps. 

Confirm the sensor is fully inserted in the tank well to ensure accurate temperature readings.

Table 3. 

Index Parameters. 

Содержание FT Series

Страница 1: ...ious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructions donn es dans cette notice pour r duire au...

Страница 2: ...g and Wiring Diagrams 8 2 A Cascade FT Floor Heating Only Boilers Piping and Wiring Diagrams 8 2 B Cascade FT Wall Mounted Heating Only Boilers Piping 18 SECTION 3 Cascade Communications the cascade c...

Страница 3: ...design delta T Non adherence to these sizing guidelines may result in premature boiler failure and resulting problems are NOT covered by product warranty CAUTION Use both thread tape and pipe dope to...

Страница 4: ...tional CH Supply CH Return Combustion Air Vent GAS INPUT V3 V1 The floor standing models have a built in low loss header The boiler circulation pump circulates the CH water in the boilers contained lo...

Страница 5: ...s header The boiler circulation pump circulates the CH water out the common header up to 15 of equivalent pipe at 1 5 diameter pipe Max Amp draw per pump 1 6 Amps 1 C 2 Wall Mounted CH Circulation 1 D...

Страница 6: ...uge Wire TACO LTR STD Wire Harness Hydrolevel harness Green White Red Yellow Yellow TACO LTR0243T 1 Low Water Cut Off Hydrolevel SAFGARD Model 1100 Low Water Cut Off Thermostat or Endswitch 18 Gauge W...

Страница 7: ...W TEMP SENSOR DHW PUMP N G L N G SYSTEM PUMP Outdoor Sensor 18 Gauge Wire L N G MAIN POWER L ZC L T T PUMP N G L ZC L T T CASCADE SYSTEM SENSOR Line Voltage Terminals Low Voltage Terminals POWER TO 24...

Страница 8: ...st the internal LLH valves V 1 V 2 V 3 to their proper positions PRIOR to boiler installation WARNING This drawing shows suggested piping configuration and valving Check with local codes and ordinance...

Страница 9: ...ONE 1 1 2 3 4 1 ZONE 4 PRIORITY 2 3 4 ZONE 2 1 2 3 4 ZONE 3 1 2 THERMOSTAT 3 4 ZONE 4 JUMPER 3 4 2 WIRE ZONE VALVE NO END SWITCH 3 WIRE ZONE VALVE POWER OPEN 4 WIRE ZONE VALVE SELF CLOSING 1 2 3 MOTOR...

Страница 10: ...ECTION 3 on page 22 for cascade kit details WARNING This drawing shows suggested piping configuration and valving Check with local codes and ordinances for additional requirements See Section 1 C on p...

Страница 11: ...CARDS RESET NORMAL SR 504 EXP T STATS ZONE 1 ZONE 3 POWER ZONE 1 ZONE 2 ZR Wiring Diagram for Cascaded Reverse Return with Zone Pumps Floor Model Boiler 1 Lead Floor Model Boiler 2 Follow P3 P2 P1 Ou...

Страница 12: ...ON 3 on page 22 for cascade kit details WARNING This drawing shows suggested piping configuration and valving Check with local codes and ordinances for additional requirements See Section 1 C on page...

Страница 13: ...P N G L ZC L T T CASCADE SYSTEM SENSOR INPUT 120 VOLT CIRCULATORS X X END SWITCH ZC 120V RELAY FUSE 1 AMP SLAVE MASTER 1234 ZONE 4 PRIORITY ON OFF POWER ZONE 2 ZONE 3 FOUR ZONE SWITCHING RELAY WITH OP...

Страница 14: ...or common pipe sizes for system and return supply headers for different system Delta T s See SECTION 3 on page 22 for cascade kit details WARNING This drawing shows suggested piping configuration and...

Страница 15: ...minals Line Voltage Terminals Low Voltage Terminals Low Voltage Terminals DHW PUMP N G L N G SYSTEM PUMP L N G MAIN POWER 14 Gauge Wire 14 Gauge Wire L Z C L T T PUMP N G L ZC L T T CASCADE SYSTEM SEN...

Страница 16: ...ge 4 for reference to adjust the internal LLH valves V 1 V 2 V 3 to their proper positions PRIOR to boiler installation WARNING This drawing shows suggested piping configuration and valving Check with...

Страница 17: ...or Cascaded Reverse Return with Zone Pumps and Indirect P4 DHW Aquastat Stage 1 18 Gauge Wire P3 P2 P1 Line Voltage Terminals Low Voltage Terminals R 0 10V W INPUT LWC O S T T AC24V OUTPUT DHW TEMPERA...

Страница 18: ...responsible for all equipment and detailing required by local codes NOTE The cascading communications cable is 60 long This must be considered during installation as this leaves only about 12 between...

Страница 19: ...ding communications cable is 60 long This must be considered during installation as this leaves only about 12 between adjascent units Leader Follower CASCADE SYSTEM SENSOR SUPPLY RETURN RETURN SUPPLY...

Страница 20: ...long This must be considered during installation as this leaves only about 12 between adjascent units Cascade FT Wall Mounted Heating Only Boilers Piping Diagrams continued Mixing Valve Zone Valve Ac...

Страница 21: ...r dedicated to Domestic Hot water Cascade System System Application DHW Tank Follower Leader CLOSELY SPACED TEES MAKE UP WATER Indirect DHW Tank DHW SYSTEM PUMP DHW TEMP SENSOR SPACE HEATING ZONE CIRC...

Страница 22: ...Installation and Operation Instructions for details Make sure that power is disconnected OFF at boiler before continuing with these instructions The FT heating only boilers can be controlled by only...

Страница 23: ...n end Leader Control Board Leader Control Board Follower Control Board Follower Control Board Last Female Connector Plug the included Ending Resistor into it Last Female Connector Plug the included En...

Страница 24: ...e is 60 long Routing for the FT Floor models can be via the side floor plastic knock outs provided Place boilers within 16 from each other Routing for the wall mounted units can be via the bottom or b...

Страница 25: ...for DHW Ensure the DHW circulator is wired to the DHW Pump contacts on a boiler that is piped to the indirect water heater If there is an active call for Heat and a simultaneous call for DHW the boile...

Страница 26: ...Display Power was Off Installer Mode C Heating Water CH set point change mode Maxium 82 C 180 F D Time Date Set No Change To SET Year Month Week Day Time Min E Scroll Select Menu select or value up d...

Страница 27: ...cation DHW Demand Demand Call indication Info Installer mode Information Installer mode indication Communication state Communication state indication Time setting mode Time Display Install mode indica...

Страница 28: ...f Before connecting the cascading cables to the boiler there are 2 items that need to be programmed on all units Start with the Lead Unit and then Repeat on all Following Units make sure to power down...

Страница 29: ...4 Cascade mode operates via system sensor Units shut off when system sensor reaches system target temperature 5 Each boiler s built in circulator operates anytime the boiler fires 6 If a system pump...

Страница 30: ...is 30 minutes and can be adjusted from 0 to 60 minutes using parameter 24 dP see parameter table below Using an Aquastat When using a DHW aquastat the aquastat monitors the temperature of the indirec...

Страница 31: ...roblem persists replace the main control NOTE During the error state the units will continue to operate Boiler setpoint will be the same as the system sensor setpoint until the issue is remedied Durin...

Страница 32: ...NOTE This error will only appear in a cascaded system 1 Turn power OFF and ON at the boiler display panel 2 If error reappears ensure all cascaded boilers are powered ON 3 If error reappears check Ins...