FOR SERVICE

Contact your installing contractor, gas utility, Laars
dealer, or call Laars for the nearest authorized
representative in your area.

1G. Trouble Shooting – Fault Codes

The Endurance boiler uses an electronic boiler

controller that shows operation information and fault
codes in a three-character alphanumeric display.

Boiler Operation Information

default display = supply temperature, the temperature

of the water leaving the boiler heat exchanger

rtn =

return temperature, the temperature of the
water entering the boiler heat exchanger

tnt =

tank temperature, the temperature of the water
in the transfer tank (EBP only)

dt =

delta tee, the difference in temperature
between the inlet and outlet of the boiler heat
exchanger

Oat =

outdoor air temperature, the temperature at the
outdoor air sensor, if outdoor reset is used.

CSP = calculated setpoint, the calculated boiler

supply temperature, if outdoor reset is used.

Boiler Control Fault Codes

F1 =

Boiler control internal error.  Switch off boiler
and restart.  If F1 repeats, replace boiler
control.

F3 =

Gas valve status is on, with no call for heat.
This is an indication of a wiring error or a
seized relay.  Check relay first, and then boiler
wiring.

F4 =

Supply sensor error.  Check for damaged
wiring or poor connection first.  Check sensor
resistance per installation manual.

F5 =

Tank sensor error (EBP only).  Check for
damaged wiring or poor connection first.
Check sensor resistance per installation
manual.

F6 =

Return sensor error.  Check for damaged
wiring or poor connection first.  Check sensor
resistance per installation manual.

F8 =

Outdoor air sensor error.  Check for damaged
wiring or poor connection first.  Check sensor
resistance per installation manual.

LO =

Lockout.  Many conditions can cause a boiler
lockout.  See boiler manual for possible
causes and resolution.

OFF = Controller is off.  Press and hold the upper left

(power) button on the boiler control for 3
seconds.

ICE = Low temperature protection – boiler has

detected water temperature below 39°F (4°C),
and will attempt to run the boiler’s circulator.
Correct low temperature situation to avoid
freezing conditions.  Although the pump
attempts to run, the Endurance boiler cannot
prevent boiler or system freeze-up.  When
water freezes, it expands, and this expansion
can burst pipes and cause damage to the
boiler, or to the pipes and components
throughout the whole heating system

Содержание EBP Series

Страница 1: ...les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne touchez ...

Страница 2: ...TION 1 Caring For Your Endurance 1A General Care 5 1B Annual Inspection of Flues and Vents 5 1C Shutting Down the Endurance 5 1D To Restart Endurance 5 1E In the Event of Power Failure 5 1F Full Service Every 3 Years 5 1G Trouble Shooting Fault Codes 8 ...

Страница 3: ... to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 5 Removecontrola...

Страница 4: ...e plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque appareil que ce soit Ne touchez pas à un commutateur électrique N utilisez pas le téléphone de votre résidence Appelez immédiatement votre fournisseur de gaz en utilisant le téléphone de votre voisin Suivez les instructions de votre fournisseur de gaz Si vous ne pouvez joindre votre fournisseur de gaz appelez le s...

Страница 5: ... 3 5 If after three attempts you still are unable to achieve ignition shut down the boiler and call your service technician If drained follow these steps 1 Follow Installation Manual for proper filling and purging 2 Turn on main manual gas valve 3 Remove control access panel and top front cover and turn on gas shutoff valve above combination gas control valve 4 Switch on main disconnect switch dep...

Страница 6: ...LAARS HEATING SYSTEMS Page 6 Figure 1 EBP Assembly View Figure 2 EDP EDN Assembly View Figure 3 Vent Terminal Outside Wall Vent Terminal Gas Shutoff Valve Gas Shutoff Valve ...

Страница 7: ...ge Reset Button Return Supply Heating Systems Fittings Main Disconnect Switch Field Wiring Box Relief Valve Gas Supply Manual Main Shutoff Domestic Hot Water Connections Drip Leg Cap Front View Side View Rear View Removable Front Cover Temperature LED Display Removable Control Access Panel Reset Button Heating Systems Fittings Return Pressure Gauge Supply Manual Main Shut Off Drip Leg Cap Relief V...

Страница 8: ...er Control Fault Codes F1 Boiler control internal error Switch off boiler and restart If F1 repeats replace boiler control F3 Gas valve status is on with no call for heat This is an indication of a wiring error or a seized relay Check relay first and then boiler wiring F4 Supply sensor error Check for damaged wiring or poor connection first Check sensor resistance per installation manual F5 Tank s...

Отзывы: