Appendix A: SC3 Specifications

ELECTRICAL

AC Input

Voltage range: 100

150Vac

Frequency Range: 45-65Hz

DC Output

5A/10A @ 2.25Vdc
5A/10A @ 4.50Vdc
5A/10A @ 6.75Vdc

Output Filtering

Suitable for Valve-Regulated batteries

Regulation

± 0.5% from no load to full load over the specified input voltage, frequency
and ambient temperature range.

LCD Display

Digital DC Ammeter & DC Voltmeter ± 1% Accuracy

PROTECTION

Current Walk-In

The output current will gradually increase after the charger is turned on,
eliminating surges and overshoot

Environmental

Thermal Protection

Emergency
Restoration

The battery charger may be connected to a battery which is heavily
discharged and recharge it without clearing any protective devices.

ENVIRONMENTAL

Audible Noise

Less than 65dBA at any point 5 feet from any vertical surface

Operating
Temperature

-4 to 122

˚F (

-20 to 50

˚C)

Storage
Temperature

-40 to 185° F (-40 to 85°C)

Relative Humidity

0 to 95% (non-condensing)

Shock

The battery charger in its shipping container withstands shock developed
when one edge of the container is dropped six inches while the opposite
edge is resting on the ground, or it is dropped two inches without any
physical damage or degradation of the electrical performance.

Vibration

The battery charger in its shipping container withstands vibration
encountered in shipping without physical damage or degradation of the
electrical performance.

Altitude

This battery charger is capable of operation at altitudes up to 3,000 feet at
an ambient temperature of up to +40 degrees C.

Ventilation

The unit should be mounted so that ventilating openings are not blocked
and air entering the cabinet does not exceed 50 degrees C (122 degrees F).

Содержание SC3

Страница 1: ...Operation Manual This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com 106 Bradrock Dr Des Plaines IL 60018 1967 CPN 136504 Instructio...

Страница 2: ...n contact with any internal components Do not operate this unit outside the input and output ratings listed on the unit nameplate Do not use this unit for any purpose not described in the operation ma...

Страница 3: ...y that you have all the necessary parts per your order for proper assembly CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty s...

Страница 4: ...d Indicators 9 3 2 1 Controls 10 3 2 2 LED Indicators 10 3 3 Flow Chart 11 3 3 2 Setting Timer 12 Timer start from 1 24 Hours and default value is 8 hours using UP DOWN switch 12 3 3 3 Cell Selection...

Страница 5: ...s required for maintaining and recharging batteries This filtered unit is designed and built to charge flooded Lead Acid batteries The SC3 is the perfect solution for maintenance or conditioning of a...

Страница 6: ...Storage should not exceed 2 years due to the limited shelf life of the DC filter capacitors when they are not in service 1 2 Moving the SC3 After careful inspection and upon verification that the SC3...

Страница 7: ...7 2 Installation 2 1 Mounting The SC3 can be wall mounted using four 4 bolts Install the SC3 using appropriate hardware on the wall Figure 1 SC3 Mounting Dimensions...

Страница 8: ...ration instructions Once the configuration is set remove AC cord of the charger 2 2 2 Output Connections The SC3 is equipped with Alligator clip type terminals for the output connections The positive...

Страница 9: ...that all connections are correct and are tightened securely Check that the input voltage and frequency of the power source match the rating of the charger Plug in AC Power Cord of the SC3 in order to...

Страница 10: ...er single cell option is selected Two Three Cell Red The Two Three Cell LED will illuminate and blink when Two Cell is selected and solid glow when three cells is selected 5 AMPS MAX CC Red The 5 AMPS...

Страница 11: ...ttons to cycle through the available options and the Start button to run the charger See the chart below for the adjustable settings in the calibration mode Except timer hours the controller settings...

Страница 12: ...DOWN switch will scroll from SINGLE CELL to THREE CELLS 3 3 4 Current Selection Press Current selection button for selecting current mode using UP DOWN switch Pressing the DOWN switch will Scroll fro...

Страница 13: ...l meters and LEDs for accuracy 4 2 Troubleshooting Procedure Troubleshooting should be performed only by trained service personnel or experienced electricians Before setting up any complicated testing...

Страница 14: ...e Less than 65dBA at any point 5 feet from any vertical surface Operating Temperature 4 to 122 F 20 to 50 C Storage Temperature 40 to 185 F 40 to 85 C Relative Humidity 0 to 95 non condensing Shock Th...

Страница 15: ...de Input Voltage AC Current Single Cell 5 A CC 120V 0 5 10 A CC 120V 1 5A C V Mode 120V 0 5 10A C V Mode 120V 1 Two Cell 5 A CC 120V 0 5 10 A CC 120V 1 5A C V Mode 120V 0 5 10A C V Mode 120V 1 Three C...

Страница 16: ...000 2 66360 900 900000 1 83690 1000 1000000 0 105600 1250 1250000 00 133100 1500 1500000 000 167800 1750 1750000 0000 211600 2000 2000000 Table of Conventions CMA Cross section of wire in circular MIL...

Страница 17: ...r elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service labor rates will...

Страница 18: ...18 Appendix E Document Control and Revision History Part Number 136504 Instruction Number P25 LSC3 1 Issue ECN 21497 21515 7 17 21497 6 17...

Отзывы: