12
2
Operation
2.1
Starting the ESCR
All equipment is shipped from the factory fully tested and adjusted based on the factory settings listed below.
Before connecting the battery, verify the recommended voltage settings with the battery manufacturer and adjust
the output settings accordingly. Failure to match the charger settings with the connected battery may damage
or shorten the life of the battery.
Factory Settings
The adjustable factory settings of the ESCR are based on the model number, unless otherwise specified. All chargers are
set at the factory with the following settings:
Parameter
Lead Acid / VRLA
Nickel Cadmium
Delay (sec.)
Float Voltage
2.25 V/C
1.40 V/C
Equalize Voltage
2.33 V/C
1.55 V/C
Low DC Voltage
1.98 V/C
1.20 V/C
5
Low DC Current
0.5 Amps
5
Current Limit
105% of nominal output current
High DC Voltage
2.45 V/C
1.61 V/C
5
High Voltage Shutdown
2.50 V/C
1.65 V/C
25
AC Failure
90 VAC / 180 VAC
5
Equalize Timer Mode
Manual
Equalize Time
8 Hours
Table 6 – Factory Default Values
NOTE:
V/C – Volts per Cell, LA – Lead Acid, VRLA – Valve Regulated Lead Acid, NC – Nickel Cadmium
2.1.1 Checking the Installation
Before starting the ESCR, verify that all connections are correct and all terminations are securely tightened. Verify the
input voltage, frequency, and output voltage is correct per application against the nameplate ratings of the charger.
2.1.2 Starting/Stopping the ESCR
Once proper connections are established, energize the charger by applying AC input voltage. This will charge the
capacitors inside the unit and eliminate heavy arcing when the batteries are connected. Shut down the charger by
removing AC input voltage, then the batteries.
2.1.3 Start-Up Sequence
Upon powering up the ESCR, the LCD will display the model and software number. During the startup sequence, the Low
DC voltage alarm will be temporarily activated.