INSTRUCTION / TROUBLESHOOTING MANUAL FOR MODEL A75M  

PAGE 6 OF 13 

 

The Model A75M charger accomplishes its charge cycle completely automatically without the use of any moving 

parts except for the input AC contactor. 

 

It  is  recommended  that  the  connector  used  for  the  battery/charger  connection  have  an  auxiliary  control 

contact.  (A contact that makes last and breaks first.)  This contact should be wired to the battery positive on 

the battery side of the connector and to Pin #2 of the terminal strip on the charger side of the connector.  (The 

jumper bar between Pins 1 and 2 must be removed when using the auxiliary control contact.) 

 

An SCR regulator controls the charge rate so that the charger puts out near maximum output current up to the 

gassing point of the battery, then automatically reduces the output current down to a trickle charge.  

 

The charger provides automatic AC input line compensation.  This eliminates the need for adjusting taps to 

match  the  input  line  voltage.    After  the  AC  voltage  taps  are  set,  see  INSTALLATION.    The  automatic 

compensation also eliminates charging problems that arise from a varying input line when charging continually 

or for two or three shift operations. 

 

The unit is self-protecting when subjected to abnormal overloading conditions. 

 

It should not be necessary to make any adjustments to this charger.  Because of the stability of design, the unit 

needs no periodic adjustment.  This, along with the rugged construction and conservatively rated components, 

insures long life and trouble-free operation. 

 

Should any adjustments be necessary, a factory service representative should be contacted. 

 

The  automatic  start/stop  feature senses  the  connection  of  the  battery  and  determines if  it is in  the  proper 

range, 1.4 volts per cell to 2.5 volts per cell, and then slowly ramps the output current up to start the charge.  

If the discharged battery is not the correct number of cells or if the correct battery is over discharged the unit 

will not start and the digital display will indicate number "0003".  The charger will automatically turn off at the 

end of the charge cycle. 

 

An on/off switch is provided to de-energize the charger.  Be sure to turn this switch off before disconnecting 

the  battery  during  the  charge  cycle.    (After  disconnecting  the  battery,  place  the  on/off  switch  to  the  "ON" 

position to activate the auto/start function.) 

 

In the normal mode, the charger will charge the battery for 3 hours after the 80% point is reached (unless the 

rate program terminates the charge first) or the battery is disconnected.  In the equalize mode, a 6 hour timer 

is initiated after the 80% point is reached. 

 

A momentary equalize switch is provided so that equalizing may be selected to give a 6 hour charge after the 

80% point is reached. Equalizing should be done periodically as recommended by battery manufacturer. This 

switch, when activated, will start the equalize charge mode for that cycle only. After completion of the cycle, 

the charger will automatically be reset to the "normal" mode. 

 

When the 80% point is reached, the 80% charge lamp will flash at a one second rate.   At this point, the timer 

in the SCR is set for 3 or 6 hours depending on whether or not the equalize mode is active.  The charger will 

continue the trickle rate until the SCR control turns unit completely off.  When a charging cycle is completed 

correctly, the 80%/Complete light will be on solid until the battery is unplugged and the amp hours returned, 

elapsed charging time and elapsed time from charge complete will be displayed.  Unplugging a charged (charge 

complete light "ON") battery will place the unit back in the autostart mode.  

 

Disconnecting the output connector while a battery is being charged is not recommended. 

 If the 

battery is disconnected during a charge cycle, the control will turn off the charger, the complete light will not 

light, all timers will reset, and the unit will go into the autostart mode.  

 

If the battery never reaches the 80% charge point (due to battery failure), the unit will turn off in 12 hours 

from the override timer. The complete light will not light. The "ON CHARGE" light will turn off, the  "FAILURE" 

Содержание A75M

Страница 1: ...L A75M MINING BATTERY CHARGER Digital Volt Amp Meter and Electronic Timer ECN DATE CPN112410 17268 10 06 17589 9 07 17076 2 06 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 306...

Страница 2: ...low a spark or flame in vicinity of a battery f Be extra cautious DO NOT drop metal onto a battery It might spark or short circuit the battery or cause an explosion g Remove personal metal items such...

Страница 3: ...the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for hand...

Страница 4: ...Charged Battery Automatic 12 hour override timer 3 Hour timing after 80 normal mode 6 Hour timing after 80 equalize mode 3 Selectable current ratings Digital Display Indicates amps volts amp hours ela...

Страница 5: ...sensing is being disabled and the wrong battery could be being connected An On Off switch allows you to turn off the charger when disconnecting the battery during the charge cycle The on off switch m...

Страница 6: ...unit will not start and the digital display will indicate number 0003 The charger will automatically turn off at the end of the charge cycle An on off switch is provided to de energize the charger Be...

Страница 7: ...is connected to the positive battery terminal and the negative terminal is connected to the negative of the battery A grounding connection is also provided for complete protection Once properly instal...

Страница 8: ...tween the AMP HOURS CHARGE TIME and COOLING TIME The COOLING TIME is the time since the charge cycle completed and is indicated in hours and minutes When showing the CHARGE TIME the AMP HOURS light wi...

Страница 9: ...check output voltage and voltage across charger shunt bar If output voltage is below 2 3 Vpc the voltage across shunt must not exceed 135mV If it is over 135mV adjust pots on the S2A 320 printed circ...

Страница 10: ...ective S2A 320 Drive Board 2 Shorted MOV Metal Oxide Varistor NOTE Voltage across secondary of control transformer X1 X2 120Vac Problem Complete ON but battery not charged 1 Record all readings on dig...

Страница 11: ...DULES A75M 3 PHASE 1 Disconnect power transformer secondary wire from top connection of module 2 Disconnect positive bus bar from module 3 Disconnect negative bus bar from module 4 Disconnect 6 wires...

Страница 12: ...t panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION O...

Страница 13: ...purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service labor rat...

Отзывы: