Revised 3/27/20 Copyright © 2020 La Cornue Page 10
Range of Remote Control
The infrared transmitter at the top of the remote must be pointed in the direction of the electronic control at the right
front of your hood or Insert. Range distance will vary depending on your installation, but see diagram below for
approximate range area.
PART 4 Electrical Connection
IMPORTANT: Copy this page and the next page to your electrical installer.
WARNING!
Ensure that the power supply is disconnected before proceeding. Verify that the power supply
matches the ratings found on the appliance data label before proceeding. The complete appliance must be
properly grounded at all times when electrical power is applied. Do not ground the appliance with the neutral
(white) house supply wire. A separate ground wire must be utilized. Failure to complete electrical connections
properly may result in damaged or non-functional systems. Follow instructions carefully to ensure proper
installation.
It is
the owner’s responsibility to ensure that a qualified person performs the electrical connection of this appliance.
The electrical installation, including minimum supply wire size, must comply with the National Electric Code
ANSI/NFPA 70-1990 (or latest revision) and local codes and ordinances. A copy of this standard may be obtained
from: National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 02269-9101
INSTRUCTIONS:
A 15 to 20 amp electrical service is recommended for proper electrical supply. Before
determining, calculate amp ratings based on the product label found on the Insert and the ventilator. Always
observe local building codes.
Always use a dedicated circuit.
Line load is calculated by adding the amperage of
the halogen lights to the rated amperage of the ventilator (either in-line or roof top). If the ventilator is rated in watts
rather than amps, divide the watts by 120 and this will give you the amperage rating. The La Cornue
Insert Series
for Wood Hoods, without the internal motor, is supplied with a 6.0 amp variable speed fan control. Make sure the
rated amperage on the remote ventilator does not exceed 6.0 amps (or 700 watts).