SPA EQUIPPED SAFETY DEVICES
Your spa is equipped with the following safety features:
1.
Overheat Protection
– All pumps and heater are shut off when the water temperature reaches
112.5°F (44.7°C). This protection is turned off when the water temperature drops below 112°F
(44.4°C).
2.
High Limit Protection
– When the water temperature reaches 119°F (48°C), the high limit circuit
has tripped. All pumps and heater are shut off. This protection requires the power to be reset at
the circuit breaker.
3.
Ambient Overheat Protection
– The light output is disabled when an on-board temperature
sensor reaches 194°F (90°C). This protection automatically turns off when the on-board
temperature sensor drops back down to 192°F (89°C). If the internal temperature continues to rise
and reaches 212°F (100°C), all outputs are turned off. This protection automatically turns off if the
temperature at the on-board sensor cools back down to 210°F (99°C).
4.
Heater Dry Run Protection
– This protection is a water flow detection algorithm of the heater that
prevents the heater from turning on until there is sufficient water flow.
5.
Smart Winter Mode
– The Smart Winter Mode is used to prevent water from freezing in the
plumbing. When SWM is enabled, the system periodically starts a purge of all pumps and the
blower (if equipped) to ensure there is always warm water in the plumbing. This function is
achieved by measuring the temperature of an on-board sensor to estimate the temperature in the
equipment area. This protection starts as soon as there is a risk of freezing. The SWM protection
will turn back off only after 24 hours without a risk of freezing. The delay between each SWM
purge cycle depends on the pumps’ idle time (see table below).
Freeze Risk
Temperature Range at
On-Board Sensor
Temperature Range in
Equipment Area
Max. Idle Time
None
> 62°F (16.7°C)
> 42°F (5.6°C)
120 minutes
Low
62 – 53°F
(16.7 – 11.7°C)
42 – 33°F
(5.6 – 0.6°C)
Medium
53 – 48°F
(11.7 – 8.9°C)
33 – 28°F
(0.6 – -2.2°C)
60 minutes
High
48 – 44°F
(8.9 – 6.7°C)
28 – 24°F
(-2.2 – -4.4°C)
30 minutes
Severe
< 44°F (6.7°C)
< 24°F (-4.4°C)
15 minutes
6.
Timeouts
– The pumps and light turn off automatically after 30 minutes of continuous operation.